M MPC II Professional Multi-channel control system for 24 heating circuits

Technical data
Inputs
16 sensor inputs, pre-configured for Pt100,
alternatively reprogrammable
0 to 5 V, 1 to 5 V, 4 to 20 mA
Input impedance
1 MΩ
Measuring current (Pt100)
1 mA
Measuring range
-199.9 °C to 850 °C for Pt100
-1999 to +9999 counters for
current and voltage measurement
MPC II Professional Measuring accuracy
±0.1% of the display range ±1 digit
Outputs
24 logic outputs for relay actuation
Features Description (contactor with integrated varistor/SSR)
DC 24 V, 100 mA
■ Cost-effective solution for max. 24 heating The MPC II Professional, as the highest configura-
circuits tion level, rounds off the MPC II family. The device 8 relay outputs N/C contacts,
is pre-configured for monitoring 8 heating circuits to emit alarms, (2 A - AC 1, 230 V)
■ Inputs for temperature measurement and but the temperature regulation of up to 24 heat-
current monitoring with default parameter Interface
ing circuits can be enabled by reprogramming the 2 x RS485 (optically isolated)
settings inputs. 1 x RJ45
■ Easy-Start: three measuring inputs are directly Alternatively, the MPC II Professional has an Communication protocol
assigned to each output, commissioning Ethernet interface for local programming and can be Modbus RTU
directly after input of setpoints programmed directly via software. The RS485 inter- Ethernet TCP/IP
face allows easy integration into the process control
technology. Speed
1200 to 19200 bauds
In addition to the LED displays, status messages
and fault alarms are emitted through the additional
relay outputs.

Wiring diagram MPC II Professional Selection chart


Supply voltage Code no.

AC 100 to 240 V 7

AC/DC 24 V 2

17-8845-33 4/1400
Complete order no.
Please enter code number. Technical
data subject to change without notice.

24 x Control Out, 24 V, 100 mA 8 x Alarm Out, 230 V, 2 A

5 x Temperature In, 5 x Load Current In, 5 x Leakage Current In, 1 x Voltage In


03-0330-0737/A-09/2014-BEH-352435

K1 = Control contactor for heating circuit 1


K2 = Control contactor for heating circuit 2
Kn = Control contactor for heating circuit n
F1, F2, Fn = breaker for regulators, heating , etc.
B1 = Pt100 for heating circuit 1

165