SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 1 of 4
-
A. General Data and Information

SITE CT RATIO 200/1 A

MAKE Elster PT RATIO 13.8/0.120 KV

MODEL A1800 ACCURACY CLASS 0.2

SERIAL NO. FEEDER AUX-2

B. Function Test
NO FUNCTIONS
1 Physical /Visual Inspection.
2 Electrical check.
3 Metering Minimum Current
4 Current Measurement
5 Voltage Measurement
6 POWER(MW-MVAR) Measurement
7 Accuracy Test
8 Maximum Demand

1. Mechanical Check and Visual Inspection


Item Description Remark

1 Inspect for physical damage and defects. 

2 All connection check according to the wiring diagram. 

3 Verify tightness for external wiring. 

2. Electrical Checks:
Item Description Remark

1 Wiring check as per Ref (approved) Drawing 

2 Auxiliary power supply checked for rating and polarity 

3 Test Switch checked for correct function 

3. Metering

CREEP TEST

APPLIED VOLTAGE APPLIED REMARKS


TEST PERFORMED BY TEST WITNESSED BY DATE
File : 505771602.doc
SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 2 of 4
CURRENT
-
69.28 0.0 A No Increment In Energy Values

69.28 0.001A Minimum current value.

4- Current Measurements:

Current (A) measurement Current (A) measurement


3 ph Secondary Expected Actual
Current injected (A)
A B C A B C

0.00 0.00 0.00 0.00 0 0 0

0.25 50 50 50 0.049 K 0.050 K 0.049 K

0.50 100 100 100 0.099 K 0.100 K 0.099 K

1.00 200 200 200 0.199 K 0.2 K 0.199 K

5- Voltage Measurements:

3Ph Phase Voltage (KV) meas. Phase Voltage (KV) meas


Secondary Expected Actual
Voltage applied
(V) PH-N VA VB VC VA VB VC

0.00 0.00 0.00 0.00 0.006 0.005 0.004

90%
7.17 7.17 7.17 7.168 7.165 7.167
62.355 V
100%
7.967 7.967 7.967 7.963 7.961 7.964
69.28 V
110%
8.764 8.764 8.764 8.760 8.758 8.760
76.212 V

6- Power Measurements: (+VE IMPORT & -VE EXPORT)

3 ph Phase
current Power factor MW meas. MVAR meas.

TEST PERFORMED BY TEST WITNESSED BY DATE


File : 505771602.doc
SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 3 of 4
3 Ph
-
Voltag
e injected Angle
Exp Actual Exp Actual Exp Actual
applie (A) set @
d (V)

69.28 1.00 0.0 1 1 4.78 4.777 0 0

69.28 1.00 45 0.707 0.707 3.379 3.377 3.379 3.777

69.28 1.00 90 0 0 0 0 4.780 4.777

69.28 1.00 180 -1 -1 -4.78 -4.777 0 0

69.28 1.00 270 0 0 0 0 -4.78 -4.777


69.28 1.00 315 0.707 0.707 3.379 3.377 -3.379
-3.379

7. Accuracy Test

Accuracy Test of Meter (Active Energy)


Result Result
Test # Test Description IEC 62053-22 Import Export
Limitations (Error %) (Error %)
1 10% In, 100%Vn UPF ± 0.2 -0.0257 -0.0458
2 100% In, 100%Vn UPF ± 0.2 0.0141 -0.0565
3 300% In, 100%Vn UPF ± 0.2 0.0125 0.0487
4 600% In, 100%Vn UPF ± 0.2 -0.0124 0.0965
5 10% In, 100%Vn 0.5Lag ± 0.3 -0.0159 -0.0215
6 100% In, 100%Vn 0.5Lag ± 0.3 0.0141 -0.0112
7 300% In, 100%Vn 0.5Lag ± 0.3 -0.0125 -0.0255
8 600% In, 100%Vn 0.5Lag ± 0.3 0.0258 0.0514
9 10% In, 100%Vn 0.8Lead ± 0.3 0.0147 0.0254
10 100% In, 100%Vn 0.8Lead ± 0.3 0.0123 0.0658
11 300% In, 100%Vn 0.8Lead ± 0.3 -0.0125 0.0554
12 600% In, 100%Vn 0.8Lead ± 0.3 -0.0159 -0.0148

Accuracy Test of Meter (Reactive Energy).


Result Result
Test # Test Description IEC 62053-23 Import Export
Limitations (Error %) (Error %)

1 10% In, 100%Vn UPF ± 2% 0.0408 -0.0547

TEST PERFORMED BY TEST WITNESSED BY DATE


File : 505771602.doc
SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 4 of 4
2 100% In, 100%Vn UPF ± 2% -0.0532 0.0570
-
3 300% In, 100%Vn UPF ± 2% 0.0515 0.0893
4 600% In, 100%Vn UPF ± 2% -0.0123 0.0998
5 10% In, 100%Vn 0.5Lag ± 2% 0.0555 -0.0570
6 100% In, 100%Vn 0.5Lag ± 2% 0.0155 0.0155
7 300% In, 100%Vn 0.5Lag ± 2% -0.0002 0.0155
8 600% In, 100%Vn 0.5Lag ± 2% 0.0146 -0.0164
9 10% In, 100%Vn 0.8Lead ± 2% 0.0587 0.1262
10 100% In, 100%Vn 0.8Lead ± 2% 0.0669 0.0155
11 300% In, 100%Vn 0.8Lead ± 2% -0.0365 0.0146
12 600% In, 100%Vn 0.8Lead ± 2% -0.0149 -0.0152

8.Maximum Demand Test:

3 Ph Phase MW meas. MVAR meas.


3 ph current
Voltage Angle
injected (A)
applied (V) set @
Exp Actual Exp Actual

69.284 0.5 60 1.195 1.191 2.0698 2.0670

69.284 1.00 60 2.390 2.389 4.139 4.137

TEST PERFORMED BY TEST WITNESSED BY DATE