Watts Per Square Metre Method:: Coefficient of Utilization or Utilization Factor
Watts Per Square Metre Method:: Coefficient of Utilization or Utilization Factor
mentioned: 1. Watts per Square Metre Method 2. Lumen or Light Flux Method 3. Point to
Point or Inverse-Square Law Method.
From the size of lamp or lamps employed and from their efficiency total lumens output are
determined. Multiplying the total lumens output from the source by coefficient of utilization,
the lumens received on the working plane are determined. If the lamps and surroundings
are not perfectly clean, then in determination of lumens received on working plane, the
depreciation factor or maintenance factor should be included, i.e.,
Also Lumens received on working plane = Number of lamps x wattage of each lamp x
efficiency of each lamp in terms of lumens per watt x coefficient of utilization x maintenance
factor.
The whole light radiated by the lamps does not reach the working plane. The ratio of lumens
reaching the working plane to the total lumens given out by the lamp or lamps, is known as
utilization factor or coefficient of utilization. Higher the value of utilization factor, more
lumens will reach the working plane for the given lumens output of the lamps.
(ii) Area to be illuminated—for given height, proportion of direct light becomes more and
more if floor area increases, i.e., utilization factor increases with the increase in area to be
illuminated
ADVERTISEMENTS:
(iii) Type of lighting—more for direct lighting and low for indirect lighting and
(iv) Colours of surroundings etc.— more for light colours and less for dark colours. Its value
varies from 0.25 to 0.5 and from 0.1 to 0.25 for direct and indirect lighting schemes
respectively.
Maintenance Factor:
The illumination produced by a lighting installation is considerably less after a year or two of
use than it was initially. The loss is due partly to the aging of the lamps and partly to the
accumulation of dust on the lamps, on the reflecting and transmitting surfaces of the fixtures
and on the ceiling and walls. This fact is taken into account by including the maintenance
factor, which is defined as the ratio of the ultimate maintained metre-candles on the working
plane to the initial metre- candles. Its value is more if the lamp fittings are cleaned regularly,
say 0.8, and less if there is much dust etc. say 0.6.
ADVERTISEMENTS:
Depreciation Factor:
This is merely the inverse of the maintenance factor and is defined as the ratio of the initial
metre- candles to the ultimate maintained metre-candles on the working plane. Its value is
more than unity.
ADVERTISEMENTS:
Example 1:
A small assembly shop 16 m long, 10 m wide and 3 m up to trusses is to be illuminated to a
level of 200 lux. The utilization and maintenance factors are 0.74 and 0.8 respectively.
Calculate the number of lamps required to illuminate the whole area if the lumen output of
the lamp selected is 3,000 lumens.
Solution:
Working area, A = 16 x 10 = 160 m2
Required illumination level, E = 200 lux
Example 2:
A minimum illumination of 80 lumens/m2 is required in a factory shed of 100 m x 10 m.
Calculate the number, location and the wattage of the units to be used. Assume that the
depreciation factor is 0.8, coefficient of utilization is 0.4 and efficiency of the lamp is 40
lumens/watt.
Solution:
Area to be illuminated, A = 100 x 10 = 1,000 m2
Illumination required, E = 80 lumens/m2
Total lumens required = A x E = 1,000 x 80 = 80,000
42 lamps of 150 W rating in 2 rows, each row having 21 lamps, can be used giving spacing
of 4.76 m in length and 5 metres in width.
Example 3:
An illumination on the working plane of 75 lux is required in a room 72 m x 15 m in size. The
lamps are required to be hung 4 m above the work bench. Assuming a suitable space-
height ratio, a utilization factor of 0.5, a lamp efficiency of 14 lumens per watt and a candle
power depreciation of 20%, estimate the number, rating and disposition of lamps.
Solution:
Area to be illuminated, A = 72 x 15 = 1,080 m2
Illumination required, E = 75 lux
80 lamps in 4 rows, each row having 20 lamps, can be used giving spacings of 3.6 metres
in length and 3.75 metres in width and space- height ratios of 0.9 and 0.9375 respectively.