Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 4

An American National Standard

IEEE Guide for Calculation of


Fault Currents for
Application of AC High-Voltage Circuit Breakers Rated
on a Total Current Basis

ings for the standard duty cycle (CO + 15 s + C O ) must


1. Scope
2

be reviewed on the basis of other standards applicable to


This standard is a guide for the calculation of fault total current-rated breakers. 3

currents for the application of ac high-voltage circuit


Fault current calculation examples, using the procedures
breakers rated on a total current basis.
outlined in this guide, are included in the appendix.

3.2 Procedure. In those instances where it is desired to use


2. Purpose
impedances instead of reactances for determining short-
circuit current magni tudes, E/Z may be substituted for E/X
This guide is intended for general use in the application
in the descriptions which follow.
of circuit breakers. Familiarity with other American
National Standards applying to circuit breakers is assumed,
3.2.1 Interrupting Current. The procedure involves
and provisions of these standards are indicated herein only
relatively simple steps of applying fac tors to an E/X
when necessary for clarity in describing application
calculation to determine total current at the time of breaker
requirements.
contact parting. The multiplying factors depend upon the
point on the system at which the short circuit occurs and
upon the system X/R ratio as seen from that point. This
3. Fault Current Calculations
total current is then compared with the breaker total
current interrupting capability for proper rating selection.
3.1 General. This guide gives a simplified method of
approximating the magnitude of fault currents: however,
other more rigorous methods should be used where
required. Step 1: Determine EIXi for three-phase faults
This guide uses basically the same calculating procedures or — for single line-to-ground faults. (2X, +X )
0

as ANSI/IEEE C37 . 010 - 1979, (Con solidated edition),


Application Guide for A C High-Voltage Circuit Breakers Step 2: Determine the system X/R ratio viewed from the
Rated on a Sym metrical Current Basis, to compute fault point from Xi/Ri for three-phase faults or (2-ΧΊ Xq) +

interrupt ing and momentary short-circuit currents for for single


direct comparison with short-circuit ratings of circuit (2R +R )
l 0

breakers rated on a total current basis.


1 line-to-ground faults.
For determination of the system X/R ratio, it should be
The adequacy of breaker characteristics other than noted that there is no completely
momentary and interrupting current rat-

7
accurate way of combining parallel circuits with different interrupting capability of the total current-rated circuit
values of X/R into a single cir cuit with one value of X/R since breaker being considered.
the current from the several circuits will be the sum of
several exponentially decaying terms, usually with different 3.2.2 Momentary Current. For this calcula tion, the E/X
exponents, while that from a single circuit contains just one current should be calculated using the reactances given in
such term. Investigation has shown that for practical pur 3.2.4.
poses the procedure of reducing the reactance to a single The application will be proper if the E/X current times a
value with the resistance assumed to be zero, and reducing factor of 1.6 does not exceed the momentary (or making)
the resistance to a single value with the reactance assumed current of the circuit breaker.
to be zero, gives, in general, better accuracy than any other
reasonably simple procedure (including the phasor
representation used at system frequency). In addition, the 3.2.3 Electrical Quantities Used
error for practical cases is on the conservative side. Ε Line-to-neutral voltage corresponding to the
highest typical operating voltage which occurs at
the circuit breaker location.

X Corresponding lowest value of system reactance


In cases where an E/Z calculation is made, it is acceptable
(determined with R assumed
to substitute Z/R for X/R pro vided that the R is obtained 0) as viewed from fault point with all rotating
from a separate reduction of resistance with the reactance machines represented by appro priate reactances
assumed to be zero. as specified in 3.2.4. It may be either X or 2X , +
x

X accord ing to whether three-phase or single


0

Step 3: The factors taken from the appro priate figure line-to-ground currents are being calcu lated.
(Fig 1, Fig 2, or Fig 3) should be applied to the E/X
calculation so that the dc and ac decrements are properly
included in the final result.
X x Positive sequence reactance.
The following procedure is usually conserva tive: X 2 Negative sequence reactance.
X 0 Zero sequence reactance — may be ob tained from
(1) The factors of Figs 1 and 2 include the effects of both design data, by calculation, or by test.
ac and dc decay. The E/X cur rent should be multiplied by a
factor from Fig 1 for a three-phase fault and by a factor X¿ Subtransient — direct axis reactance of a
from Fig 2 for a line-to-ground fault if the short-circuit
synchronous machine or locked rotor reactance of
current is fed predominantly from generators through:
an induction machine. This is always a positive
sequence reactance.

(a) Not more than one transformation, or


(b) A per-unit reactance external to the generator X¿ Transient — direct axis reactance of a
which is less than 1.5 times generator per-unit synchronous machine. This is always a positive
subtransient react ance on a common system M V sequence reactance.
A base. R Corresponding lowest value of system resistance as
(2) The factors of Fig 3 include only the effects of dc viewed from the fault point (determined with X
decay. The E/X current should be multiplied by a factor assumed 0) with the resistances of the system
from Fig 3 for a three-phase or a line-to-ground fault if the components determined as specified under 3 . 2 . 5
short-circuit current is fed predominantly from generators . Instead of calculating R, an estimate of the
through: system X/R ratio may be determined from Table 4.
R may be either R or 2R + R according to
x X 0

(a) Two or more transformations, or whether three-phase or single line-to-ground


(b) A per-unit reactance external to the generator that currents are being calculated.
is equal to or exceeds 1.5 times the generator per-
unit subtransient reactance on a common system
M V A base.
R, Positive sequence resistance.

The resulting product must not exceed the R 2 Negative sequence resistance.

8
APPLICATION OF AC HIGH-VOLTAGE CIRCUIT BREAKERS
3 PHASE

R 0 Zero sequence resistance — may be obtained from


design data, by calcula tion, or by test.

L Inductance (henries) = X/2nf (where f is system


frequency).
C Capacitance.
Ζ Impedance.
/ Current.
Isc Calculated symmetrical short-circuit current.

Tdc Direct-current time constant for the circuit


1.0 1.1 L2 1.3 1.4 LS 16
involved in the short circuit being calculated. MULTIPLYING FACTORS FOR
E / X AMPERES

3.2.4 Rotating Machine Reactances. Basically, initial short-


Fig l
circuit current of rotating machines is determined by the
Three-Phase Fault Multiplying
machine subtransient re actances. For the short-circuit and
Factors Which Include Effects
momentary current calculation, the reactances in Table 1
of AC and DC Decrement
are used.

Fig 2 Fig 3
Line-to-Ground Fault Multiplying Three-Phase and Line-to-Ground
Factors Which Include Effects Fault Multiplying Factors Which
of A C and DC Decrement Include Effects of DC Decrement Only

N O T E : Contact parting is defined as breaker opening time plus 0.5 cycle tripping delay. 2 cycle, 3 cycle, and 4 cycle contact parting times are typical mínimums
for 3 cycle, 5 cycle , and 8 cycl e breakers ( o n a 6 0 Hz basis), respectively. Exceptions: with minimum tripping delay, certain 8 and 5 cycle circuit breakers, such
as air magnetic (15 k V and b e l o w ) and oil (1 5 k V through 72 . 5 k V ) , often part contacts in less than the foregoing times and demonstrate corre sponding
higher total current interrupting ability. For specific cases, consult the manufacturer.

9
Table 1
Rotating Machine Reactances for
Short-Circuit Current Calculation

Positive Sequence Reactances


for Calculating

Interrupting Momentary
Duty Duty
T y p e o f Rotating Machine (Per Unit) (Per Unit)

All turbogenerators, all hydrogenerators l.OXd l.OXd


with amortisseur windings, and all condensers
[see Not e ( 1 ) ]

Hydrogenerators without amortisseur windings O.TbXd 0.75X¿


[see Not e ( 2 ) ]

All synchronous motors [see Notes ( 1 ) , ( 4 ) , and ( 5 ) ] l.bX'a l.OXd


Induction motors [see Notes ( 3 ) , ( 4 ) , and ( 5 ) ]
A b o v e 1 0 0 0 hp at 180 0 r/min or less
A b o v e 25 0 hp at 360 0 r/min 1.5X'd l.OX'd

Fro m 5 0 t o 100 0 hp at 180 0 r/min or less


Fro m 50 t o 250 hp at 360 0 r/min 3.0X'd 1.2X'd

Neglect all three-phase induction motors belo w


5 0 hp and all single-phase motors .

NOTES:
this result must not exceed the momentary capability
( 1 ) X'd o f synchronous rotating machines is the "rated
o f the circuit breaker being used.
voltage" (saturated) direct axis subtransient reactance.
( 5 ) When the contribution o f large individual induc-
( 2 ) X¿ o f synchronous rotating machines is the "rated
tion motors is an appreciable portion o f the short-
voltage (saturated) direct axis transient reactance.
circuit current, substitution for the tabulated multiply-
( 3 ) X'J o f induction motors equals 1.00 divided b y ing factors o f more accurate multipliers based o n man-
per-unit locked rotor current at rated voltage. ufacturer's time constant data is appropriate. Using
( 4 ) The current contributed t o a short circuit b y / = (E/X'd)i-tlT'\ as the expression for the exponential
induction motors and small synchronous motors may decay o f induction moto r symmetrical current to a
usually be ignored o n utility systems except station terminal short circuit, the reactance multiplying factor
service supply systems and at substations supplying is i tlT"t
+
where t is the proper time after initiation of
large industrial loads. A t these locations, as well as in the short circuit and T" is the moto r short-circuit time
industrial distribution systems or locations close to constant. (Both should be in the same time units.) For
large motors, or both the current at V4 cycle will be example, using manufacturer's moto r data for T" , the
increased b y the moto r contribution to a greater reactance multiplying factor for determining the inter-
degree, proportionately, than the total current will be rupting duty may be found using t equal t o the circuit
increased at minimum parting time. In these cases, an breaker minimum contact parting time. For a circuit
additional calculation o f the Vá cycle current should be breaker with a five-cycle rated interrupting time, t = 3
made using the appropriate reactance values given in cycles (0 . 05 s). For determining the momentary duty,
Table 1 under the heading "Momentary Duty . " A 1.6 use t = 0.5 cycles (0 . 0083 3 s) in the reactance multiply-
multiplying factor should be used for asymmetry, and ing factor calculations.

3 . 2 . 5 Resistance of System and Typical X/R of the equivalent X/R ratio of any system,
Ratio. For the purpose of determining the rotating machine resistance values obtained
equivalent X/R ratio, it is recommended that from the manufacturer or through use of the
the manufacturer's advice be obtained concern- following table should be adjusted by the ap-
ing the resistance value to be used for important plicable rotating machine reactance multipliers
electrical devices. In the absence of such recom- from Table 1.
mendations, the approximate resistance is sug- The ranges and typical values of the X/R
gested in Table 2. In both cases, measured ratios of system components may be obtained
values on rotating machines should be converted from Table 3. An estimate of the total system
to normal operating temperature. equivalent X/R ratio to the point of fault may
In setting up the R network for the calculation be obtained from Table 4.

10

You might also like