Full DC Inverter CMV System Outdoor Unit: GD Chigo Heating & Ventilation Equipment Co., LTD
Full DC Inverter CMV System Outdoor Unit: GD Chigo Heating & Ventilation Equipment Co., LTD
Outdoor Unit
Technical Support Division
2014-7-16
Content
Part 1.
General information
Supercooling flow path design, separates the refrigerant inlet and outlet, increase the supercooling degree, reduce the effect of high
temperature inlet gas refrigerant to low temperature outlet liquid refrigerant, therefore, the system efficiency will be greatly
increased.
1.2.9 Cross Flow Fins.
Has low air resistance and great heat transfer coefficient
Frosting improved, frost on the heat-exchanger will be well-distributed, easy for defrosting.
1.2.10 New internal structure.
Thanks to the optimization pipeline design, 5% pressure drop is reduced.
EER and COP increase, because of evaporating temperature increase and compressor work decrease.
CMV - D 280 W / Z R1
CMV - V 280 W / Z R1 - B
Design code
B: 2nd generation
Refrigerant type
R1: R410atype
Refrigerant
R1: R410a
Power supply
Power supply
Z: 380-415V/3PH/50Hz
Z: 380-415V/3PH/50Hz
Outdoor unit
Outdoor unit
Capacity (*100W)
Capacity (*100W)
CMV - V 150 TB / H R1 - B
Design code
B: 2nd generation
Refrigerant type
R1: R410a
Function code
H: Heat pump
Capacity (*100W)
DC inverter system
3 Outdoor units
3.1 External appearance
56HP 58HP
8 CMV-D252W/ZR1 ● 13
10 CMV-D280W/ZR1 ● 16
12 CMV-D335W/ZR1 ● 16
14 CMV-D400W/ZR1 ● 20
16 CMV-D450W/ZR1 ● 20
18 CMV-D500W/ZR1 ● 20
20 CMV-D560W/ZR1 ●● 24
22 CMV-D615W/ZR1 ● ● 24
24 CMV-D680W/ZR1 ● ● 28
26 CMV-D730W/ZR1 ● ● 28
28 CMV-D785W/ZR1 ● ● 28
30 CMV-D850W/ZR1 ● ● 32
32 CMV-D900W/ZR1 ●● 32
34 CMV-D950W/ZR1 ● ● 36
36 CMV-D1000W/ZR1 ●● 36
38 CMV-D1065W/ZR1 ● ● ● 36
40 CMV-D1130W/ZR1 ● ● ● 42
42 CMV-D1180W/ZR1 ● ●● 42
44 CMV-D1235W/ZR1 ● ●● 42
46 CMV-D1300W/ZR1 ● ●● 48
48 CMV-D1350W/ZR1 ●●● 48
50 CMV-D1400W/ZR1 ●● ● 54
52 CMV-D1450W/ZR1 ● ●● 54
54 CMV-D1500W/ZR1 ●●● 54
56 CMV-D1580W/ZR1 ● ● ●● 58
58 CMV-D1630W/ZR1 ● ●●● 58
60 CMV-D1685W/ZR1 ● ●●● 58
62 CMV-D1750W/ZR1 ● ●●● 64
64 CMV-D1800W/ZR1 ●●●● 64
66 CMV-D1850W/ZR1 ●●● ● 64
68 CMV-D1900W/ZR1 ●● ●● 64
70 CMV-D1950W/ZR1 ● ●●● 64
72 CMV-D2000W/ZR1 ●●●● 64
Part 2.
Outdoor units
1. Specifications
2. Dimensions
3. Outdoor refrigerant circuit diagram
4. Outdoor unit wiring diagrams and field wiring
5. Operation limits
6. Operation sound levels
7. Outdoor fan performance
8. Functional parts and safety devices
9. Exploded view
Notes:
1) The cooling conditions: indoor temp.: 27˚C DB (80.6˚F), 19˚C WB (60˚F) outdoor temp.: 35˚C DB (95˚F) equivalent pipe length: 5m
drop length: 0m.
2) The heating conditions: indoor temp.: 20˚C DB (68˚F), 15˚C WB (44.6˚F) outdoor temp.: 7˚C DB (42.8˚F) equivalent pipe length: 5m
drop length: 0m.
3) Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.3 m. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
4) Maximum 85Pa outdoor ESP can be set on outdoor PCB.
5) The above data may be changed without notice for future improvement on quality and performance.
Notes:
1) The cooling conditions: indoor temp.: 27˚C DB (80.6˚F), 19˚C WB (60˚F) outdoor temp.: 35˚C DB (95˚F) equivalent pipe length: 5m
drop length: 0m.
2) The heating conditions: indoor temp.: 20˚C DB (68˚F), 15˚C WB (44.6˚F) outdoor temp.: 7˚C DB (42.8˚F) equivalent pipe length: 5m
drop length: 0m.
3) Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.3 m. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
4) Maximum 85Pa outdoor ESP can be set on outdoor PCB.
5) The above data may be changed without notice for future improvement on quality and performance.
765
970
1620
53
765 203
502
840
765
1260
1620
203
53
765 695
1130
CMV-D252W/ZR1 8 HP
700 1012 703 817
CMV-D280W/ZR1 10 HP
CMV-D335W/ZR1 12 HP
CMV-D400W/ZR1 14 HP
998 1302 703 817
CMV-D450W/ZR1 16 HP
CMV-D500W/ZR1 18 HP
Outdoor heat-exchanger
T4
(Outdoor temperature sensor)
SV6
EXV-A
T3
(heat-exchanger outlet temperature sensor)
ST
SV5
Liquid
receiver
Low pressure
accumulator
SV2
SV1
SV4
T7-2 Low
pressure
Pressure gauge valve
sensor
DC inverter
compressor
Oil balance valve
Outdoor heat-exchanger
T4
(Outdoor temperature sensor)
SV6
EXV-A
EXV-B
T3
(heat-exchanger outlet temperature sensor)
ST
SV5
Liquid
receiver
Low pressure
accumulator
SV2
SV1
SV4
Oil
separator
High pressure High pressure
switch sensor Low pressure
switch
T7-3 T7-1
Low pressure
sensor
Stop valve (High pressure)
Stop valve (Low pressure)
T7-4 T7-2
Pressure gauge valve
DC inverter
DC inverter
compressor
compressor
Oil balance valve
Running indoor unit Stop or standby indoor unit Fan only indoor unit
Caution: The E1 E2 electrolytic capacitors must finish releasing electricity after outage.
4.1.2 12HP
Caution: The E1 E2 electrolytic capacitors must finish releasing electricity after outage.
Caution: The E1 E2 electrolytic capacitors must finish releasing electricity after outage.
Remarks:
E1 E2 X1 X2 DZ1 DZ2 SV1
Electrolytic Electrolytic Main Power Module solenoid
Common terminal 3 phase bridge Single phase bridge
capacitor capacitor terminal valve
SV2 SV4 SV5 SV6 4-WAY F1 F2
Bypass solenoid Oil balance Defrost solenoid Fixed speed Fixed speed
Flow valve 4-way valve
valve solenoid valve valve compressor 1 compressor 2
2) Communication terminals
L1 L2 L3 N
A B C N H1 H2 E P Q E A B C N H1 H2 E P Q E A B C N H1 H2 E P Q E
L N P Q E L N P Q E L N P Q E
Sheilded layer
Note:
a) The signal connecting line between outdoor units, indoor and outdoor units and indoor units has polarity. When connecting, be
careful to prevent error connection.
b) Signal line shall adopt three-core shielded wire with an area above 0.75 mm2.
c) Do not bind signal line and copper pipe together with belting.
d) Make sure that the shield metal layer should be grounded well indoor control box in order to prevent interference.
e) It’s forbidden to connect 200V or above high-volt live wire to the communication terminal.
a) Case 1:
GND
(a) Outdoor unit
b) Case 2:
Outdoor unit
Leakage GND
protector
Manual
(a) switch
Outdoor unit
GND
(b)
Outdoor unit
GND
Branch box
Outdoor unit
GND
Power facilities 2
(with leakage protector)
Outdoor unit
GND
Note:
Select power wire for these five models separately according to relevant standard.
The wiring diameter and the length in the table indicate the condition that the voltage dropping range is within 2%. If the length
exceeds the above figure, please select the wire diameter according to relevant standard.
Total Total
Minimum wire diameter (mm2 ) Minimum wire diameter (mm2 )
capacity capacity
(HP) Wire length ≤ 20m 20m<Wire length≤ 50m (HP) Wire length ≤ 20m 20m<Wire length≤ 50m
8 10 16 38 35 50
10 10 16 44 50 70
12 10 16 46 50 70
14 16 25 48 50 70
16 16 25 50 70 95
18 16 25 52 70 95
20 16 25 54 70 95
22 16 25 56 90 110
24 25 35 58 90 110
26 25 35 60 90 110
28 25 35 62 90 110
30 35 50 64 90 110
32 35 50 66 90 110
34 35 50 68 90 110
36 35 50 70 90 110
40 35 50 72 90 110
42 50 70
Remark:
The above selection is for reference.
For an actual electrical project, it should be considered that the cable layout, space between cable and surroundings, etc.
5 Operation limits
Cooling Heating
50 30
45 25
40 20
35 15
0 -16
-5 -20
-10
10 16 21 25 32 10 16 21 25 32
Indoor temperature (°C DB) Indoor temperature (°C DB)
Notes:
If the unit is operating beyond above condition, protection device will be activated; even then the units will abnormality run.
These figures base on the operation conditions between indoor units and outdoor units: equivalent pipe length is 5m, and height
difference is 0m.
Precaution: the indoor relative humidity should be lower than 80%. If the air conditioner works in an environment with a relative
humidity higher than mentioned above, the surface of the air conditioner may condensate. In this case, it is recommended to set the air
speed of the indoor unit to high.
Test value
1m Microphone
Sound level
Outdoor unit
dB(A)
10 HP 58
1.3 m
12 HP 58
14 HP 60
16 HP 60
18 HP 60
6.2 NC curve
70 70
Sound pressure level dB (0dB=0.0002μ bar )
NC-60 NC-60
60 60
NC-50 NC-50
50 50
NC-40 NC-40
40 40
NC-30 NC-30
30 30
NC-20 NC-20
20 20
Audibility limits Audibility limits
of continuous of continuous
white sound white sound
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
8HP, 10HP Octave band center frequency (Hz) 12HP Octave band center frequency (Hz)
70
Sound pressure level dB (0dB=0.0002μ bar )
NC-60
60
NC-50
50
NC-40
40
NC-30
30
NC-20
20
Audibility limits
of continuous
white sound
100
90
80
100
70
90 Can be set in outdoor PCB
60
80
(Pa)pressure (Pa)
50
70
40 Can be set in outdoor PCB
60 Standard
30
static
50
20
pressure
40
External
10 Standard
30
External static
0
208000 8400 8800 9200 9600 10000 10400 10800 11200 11600 12000 12400 12800 13200 13600 14000
10 Air flow (m3/h)
0
8000 8400 8800 9200 9600 10000 10400 10800 11200 11600 12000 12400 12800 13200 13600 14000
90
80
100
70
90 Can be set in outdoor PCB
60
80
(Pa) pressure (Pa)
50
70
40 Can be set in outdoor PCB
60 Standard
30
pressurestatic
50
20
External staticExternal
40
10 Standard
30
0
2010000 10400 10800 11200 11600 12000 12400 12800 13200 13600 14000 14400 14800 15200 15600 16000
10 Air flow (m3/h)
0
10000 10400 10800 11200 11600 12000 12400 12800 13200 13600 14000 14400 14800 15200 15600 16000
Air flow (m3/h)
Electronic expansion
PMV UKV-32D210 ( Foshan Hualu)
valve
Functional
parts 4-W/V 4-way valve CMV-V280WM6A/M+4.0.ZLT.7-5(Foshan Hualu)
Table 2.
Item Symbol Name CMV-D400W/ZR1 CMV-D450W/ZR1 CMV-D500W/ZR1
Inverter
Inverter compressor E405DHD-42D2YG E405DHD-42D2YG E655DHD-65D2YG
Compressor Compressor *2
OFF:0.5(±1)kg/cm2
LP Low pressure switch
ON:1.5(±1)kg/cm2
Temperature sensor
T3,T4 (condenser outlet/ambient 25°C=5KΩ
Temperature
temperature)
sensor
Discharge Thermostat (Inverter/Fixed
thermostat discharge) BW120°C ON:120°C OFF:90°C