BFP Motor

SN DETAILS
1. Manufacturer Hyundai Heavy Industry Co. Ltd.
2. Type, frame, size and design code no. CACA / 1000 / IEC:60034, IS:325
3. Rated continuous output of motor
a. At 40°C ambient kw 9500
b. At 50°C ambient kw 8800
6. Type of enclosure & ventilation TEWAC / IC81W
7. Degree of protection IP55
8. No. of phases, Frequency& Voltage 3- Phase, 50hz & 11000V
9. Permissible variations in % Voltage: ±10, Frequency: ±5, Combined:
10
10. At rated voltage & frequency
a. Full load current A 534.6
b. No load current A 117.4
c. Full load Speed rpm 1489
d. Rated Power factor 0.90
15. Min. permissible Voltage during starting % 75
16. Max. permissible time at min. permissible At 75% voltage for 7 min
voltage during running at full load
17. Max. permissible time at 75% of rated min 5
Voltage during running at full load
18. Efficiency & power factor at rated voltage % Efficiency PF
and frequency
a. Full load 96 0.9
b. 3/4 load 95.7 0.88
c. ½ load 95.5 0.84
d. ¼ load 94 0.6
e. No load - 0.04
f. At start - 0.09
g. Duty point 96 0.9
26. Stator winding
a. Connection Star
b. No. of Terminals brought out no 6
c. Resistance Between terminals at 20°C ohm 0.0866
d. Resistance per Phase at 20°C ohm 0.0433
e. Inductance per Phase henry 0.0068
f. Capacitance per Phase uF 0.2816
33. Starting current as % of FLC %V 80 100 110
a)With_IS_tolerance % 360 460 495
b)Without IS Tolerance % - - -
36. Torque at full load kgm 5744.8
37. Break away torque in % of full load torque % 50 (starting torque)
38. Pull up torque in % of full load torque % 47
39. Pull out torque in % of full load torque % 205 (max. torque)
SN DETAILS
40. Starting time Without coupled Coupled
a. With rated voltage sec 4.6 5.7
b. With 80% of rated Voltage sec 7.9 9.7
c. With 110% of rated Voltage sec 3.7 4.6
44. Safe stall time
a. With rated voltage sec 15.6 19.5
b. With 80% of rated Voltage sec 25 30.9
c. With 110% of rated Voltage sec 12.8 15.8
48. Permissible maximum accelerating time
a. With rated voltage sec 15.6 19.5
b. With 80% of rated Voltage sec 25 30.9
c. With 110% of rated Voltage sec 12.8 15.8
0
52. Limiting motor temperature to determine C Max. 450
Safe stall time
53. Heating Time constant min 30
54. Cooling Time constant min 180
55. Insulation F with Temperature rise limited to Class B
56. Temp. rise under normal conditions over °C 81 based on water inlet temp 39°C
50°C ambient temp.(By resistance method)
57. Impulse withstand voltage of stator winding kVp 49
58. Impulse withstand voltage (inter turn) kVp 32
59. Stator Thermal time Constant min 60
60. Time required for voltage to Decay down to
when during Voltage is removed
a. At 50% of rated voltage sec 1.86
b. At 40% of rated voltage sec 2.5
c. At 25% of rated voltage sec 3.74
d. At 0% of rated voltage sec 20
65. Method of cooling IC81W
66. Bearing details
a. Manufacturer Hansung
b. Number 2
c. Type Split‐Sleeve
d. Lubrication system Forced Oil Lub
e. Quantity of lubrication required for both DE (16.2 l/min.), N‐DE(12.2 l/min.)
the bearings
f. Recommended lubricant Oil ISO VG 32
0
g. Maximum permissible temperature rise C 45
above ambient temperature (50 deg)of
bearing
h. Bearing end play Total 12 mm
i. Inlet oil pressure barg 2
0
j. Temp. rise of oil through bearing C About 30
0
k. Max. permissible temp of oil C 50
l. Permissible running time without forced oil min 2
at full load & full speed
SN DETAILS
79. Motor Space heaters 4x250 W, 240V
80. Winding temp. detector PT100, single, 3 wire, 4 ea/phase
81. Bearing temp. detector PT100, Dual, 3 wire, 1 ea/bearing
82. Temperature indicators Dial type with contact, 2ea for Bearing,
2ea for Inner Air
83. Flow switch Rotameter, 1ea/motor, at water inlet
84. Differential C.T. details
a. C.T.ratio A 750/1A
b. Knee point voltage V Vk >60V, Rct ≤ 4 Ω
c. S. C. withstand capability 44 kA/1sec.
d. Class PS Class
e. Excitation current at Vk/2 mA 30
90. Shaft C.W viewed from DE Side
91. Shaft extension Double
92. Motor GD2 (Rotor) kgm2 734
93. Details of water cooling system
94. a. No. of cooler 2
b. Water requirement per cooler m3/hr 47.4
c. Losses removed by cooler kW 366.7
0
d. Max. Permissible temp. of cooling water C 39
at inlet
0
e. Max. Permissible temp. of cooling water C 43
at outlet
f. Max. permissible pressure at water outlet barg 5.8
0
g. Temperature of cold air coming out & C 59 / 104
entering the machine for permissible
cooling temp