Delta UPS Connectivity

Training
Delta Confidential
SNMP Card

Golden Finger: 12V DC, Communicate with UPS.


Dip Switch: Normal, Configuration, Pass Through and Sensor modes.
Reset: Reset SNMP card.
Console Port: Connect to HyperTerminal for configuration or
Sensor Box for Environmental Monitoring.
RJ45 Network Port: 10/100 M Auto-Negotiation ethernet interface.

Technical Spec:
Network Connection RJ-45 jack connector No SW1 SW2 Function Mode
Operating Temperature 0 ~ 40° C .
1 ON ON Console Configuration Mode
Operating Humidity 10 ~ 80 % 2 ON OFF For Environmental Sensor
Power Input 9~24VDC 3 OFF ON Pass Through Mode
Power Consumption 1 Watt Maximum 4 OFF OFF Normal Mode
Size 130 mm x 60 mm (L x W)
Weight 58 g

Delta Confidential
SNMP Card
Features:
SNMP agent and web server implemented for UPS
Support the following protocols: ARP, IP, ICMP, SNMPv1, UDP, TCP, HTTP,
FTP, TFTP, SMTP, BOOTP, SNTP, DN and Telnet
Security login by MD5
Users level management
Firmware upgrade for new features through TFTP
Batch configuration through FTP
Save UPS event log and history values in EEPROM
Schedule shutdown, restart and test UPS
Wake On LAN packet to wakeup PC
Send e-mail and SNMP trap to notify users
Provide InsightPower Client software to protect public operating systems
Provide InsightPower Manager to monitor all of the UPS information in the
network
Provide InsightPower EzSetting software to easily configure at the first time and
upgrade firmware
Delta Confidential
SNMP Card Configuration-1

Connect the RJ45 of configuration cable to the SNMP console port.

Connect the D-sub9 of configuration cable to a Windows PC.


Run the HyperTerminal from Windows (baud rate 2400, non-parity, 8 data bits, 1
stop bits).
Switch these 2 dip switches to the ON position.
The default login account and password are “admin” and “password”.
Switch these 2 dip switches to the OFF position once you have made changes.
Delta Confidential
SNMP Card Configuration-2

Connect the SNMP card to the network.


Run the EzSetting utility in the same LAN.
Press “Discover” button to search all of the SNMP cards in the LAN.

Select one of the SNMP cards in the Device List and press “Modify” button to
input the account and password.
If you want to search in a different LAN, please change the subnet and subnet
mask.
Delta Confidential
SNMP Card Configuration-2

Press “Configuration” button to change the basic settings.


Press “Upgrade” to upgrade the new firmware for SNMP card.

Delta Confidential
Before Deploy the SNMP card

The DHCP is enabled by default such that the IP address will be assigned
automatically, if there is not a DHCP server in your network then the default IP
address is 192.168.1.100.
User cannot login from web or telnet unless the Allow Any option is selected.
If the Time server is unreachable then the event log and history data will not be
recorded in the EEPROM because loss of date and time.

Setup Time Server:


Install the InsightPower Client and
enable the Time Server from
Property dialog box.
install the “Simple TCP/IP Services”
of “Networking Services” from
“Add/Remove Windows
Components”. You may need a
Windows CD while installing.
Delta Confidential
SNMP Card Application
Small Data Center

Unix Windows
Router
Servers Servers
HUB
(ShutdownAgent) (ShutdownAgent)
(InsightPower Client)
3KVA UPS 5KVA UPS 5KVA UPS
(SNMP Card) (SNMP Card) (SNMP Card)

SMS
(InsightPower Client)

e-mail

(Internet Explorer)
Mail Server
Delta Confidential
SNMP Card Application
Large Data Center

Unix Windows
Router
Servers Servers
HUB
(ShutdownAgent) (ShutdownAgent)

3KVA UPS 5KVA UPS 5KVA UPS


(SNMP Card) (SNMP Card) (SNMP Card)

e-mail

Centralized Monitoring
Mail Server (InsightPower Manager)
Delta Confidential
SNMP Card Application
Manufacture Factory

Ethernet

RS485
Note: We suggest connect less than 20 units of
UPS in one bus line

Fiber MOXA NPort 5230


ID1 ID2
Ring (485-Ethernet)
RS485

ID1 ID2

Ethernet
Play Audio

Insightower Manager
Delta Confidential
SNMP Card Application
Manufacture Factory – Integrate ATS, PLC

Delta Confidential
SNMP Card Application
Bank
e-mail
SMS

Database

Data Center Device Manager


(Manager-Service) (Manager-Monitor)

e-mail

SMS
UPS+SNMP
UPS+SNMP
Repaire Center Local Monitor
(Manager-Monitor) (Manager-Monitor)

UPS+SNMP UPS+SNMP

UPS+SNMP UPS+SNMP Delta Confidential


SNMP Card Application
Bank -- Architecture
Windows 2003 Server + MS SQL Server

SNMP
InsightPower Manager UPS
Office Network Service InsightPower
TCP or Business Network SNMP Card
InsightPower Manager Internet
Monitor
TCP UPS

InsightPower
SNMP Card
InsightPower
InsightPower Manager SNMP Card UPS
Monitor

On the client side users can run multiple InsightPower Manager Service program
InsightPower Monitor programs then connect collects all of the UPS information through
to login the same InsightPower Manager SNMP from SNMP cards and keep data
Service. InsightPower Manager records all of in the database.
the operation actions of the login users and
keeps in the database.
InsightPower Manager Monitor
communicates with InsightPower Manager
Service through TCP protocol to retrieve UPS
Delta Confidential
information in a real-time manner.
SNMP Card Application
Bank -- Notification

Windows 2003 Server + MS SQL Server

InsightPower Manager TCP


Monitor SNMP UPS
InsightPower Manager
Office Network Service InsightPower
TCP or Business Network SNMP Card
Internet
InsightPower Manager
Monitor
UPS
SMTP
InsightPower
Mail Server SNMP Card
SMS InsightPower
SNMP Card UPS

E-mail InsightPower Manager has the ability to


notify device managers the detailed
power events through e-mail and SMS. It
is not necessary for users to stick on the
front of monitoring server.

Delta Confidential
SNMP + 5 Port Switching
Technical Spec:
Network Connection RJ-45 jack connector, MIDX No SW1 SW2 Function Mode
Operating Temperature 0 ~ 40° C .
1 ON ON Console Configuration Mode
Operating Humidity 10 ~ 80 %
2 ON OFF For Environmental Sensor
Power Input 12V DC
3 OFF ON Pass Through Mode
Power Consumption 4.5 Watt Maximum
4 OFF OFF Normal Mode
Size 143 mm x 65 mm x 28mm (L x W x H)
Weight 320 g

D-Sub9 to UPS
Pin 2 Rxd←UPS
Pin 3 Txd→UPS
Pin 5 GND

Console Cable for Configuration

RJ45 DB9 (Female) Description


1 1 12VDC
3 2 Txd→PC
4 5 GND
6 3 Rxd←PC

Delta Confidential
SNMP + 5 Port Switching
Features:
Fast ethernet 5 ports 10/100M smart switching hub
SNMP agent and web server implemented for UPS
Support the following protocols: ARP, IP, ICMP, SNMPv1, UDP, TCP, HTTP, FTP,
TFTP, SMTP, BOOTP, SNTP, DN and Telnet
Security login by MD5
Users level management
Firmware upgrade for new features through TFTP
Batch configuration through FTP
Save UPS event log and history values in EEPROM
Schedule shutdown, restart and test UPS
Wake On LAN packet to wakeup PC
Send e-mail and SNMP trap to notify users
Provide InsightPower Client software to protect public operating systems
Provide InsightPower Manager to monitor all of the UPS information in the network
Provide InsightPower EzSetting software to easily configure at the first time and
upgrade firmware
Delta Confidential
Environmental Sensor Box
Technical Spec:
Temperature Measurement Range 0oC to 65 oC (32oF to 149 oF)
Temperature Measurement accuracy +/- 2%of full scale
Humidity Measurement Range 10%to 90%
Humidity Measurement Accuracy +/- 8%of full scale for 15 to 35 ℃
Contact Closure Inputs 4 dry-closure Contact zones
Pin-1 Common
Pin-2 Smoking
Pin-3 Fire
Pin-4 Watter
Pin-5 Security
Contact Closure Input Configure Configure for normal Open or closed
Size 18mm x 60mm x 50mm (Hx W x D)
Weight 142 g

Features:
Real-time temperature/humidity and other environmental conditions monitoring
Monitors the status of 4 user-provide contact devices to protect your critical
equipments

Delta Confidential
Sensor Box Configuration
Connect the sensor box in the console port of SNMP card.
Switch these dip switches to the DIP-1 ON and DIP-2 OFF positions.

Network

Login to the SNMP card from web browser and open the Sensor web page.

Delta Confidential
Sensor Box Configuration
Set the thresholds of temperature and humidity.
Set the normal open/normal close.
Apply to Smart Shutdown is used to turn the servers off gracefully when
environment alarm raises.

Delta Confidential
Sensor Box Application

Smoking Sensor

UPS

Network

Door Switch
Delta Confidential
Programmable Relay I/O Card
Technical Spec:
Size 130 x 60 mm Maximum
Weight 200 g DC Voltage DC Current
Operating Temperature 0 ~ 40° C Relay R1~R6 24 V 1A
Operating Humidity 10 ~ 80 % Maximum
Power Input 8 ~ 20V DC DC Voltage DC Current
Power Consumption 1.2 Watts Input 24 V 10 mA

I/O Pinout: Features:


GND-R: Ground for relays
Common: 12~24VDC UPS status information presented as 6 contact
Default Alarm Event
R1 Summary Alarm closures
R2 Power Fail
Programmable output contacts, monitors the
R3 Battery Low
R4 On Bypass UPS events that users really concern in different
R5 Overload
R6 Over Temperature
application practices
Input: Remote shutdown or battery test Configurable UPS shutdown delay time
Tx: Transmit to PC, connect to sub9-pin2
Rx: Receive from PC, connect to sub9-pin3 Configurable input signal as shutdown UPS or
GND-C: Ground for configuration Tx and Rx pins
battery test
OFF (Default) ON
SW1 Normal open Normal close Has the ability to protect up to 6 computers
SW2 Default settings Customized settings unattended shutdown gracefully
Delta Confidential
Relay Card Configuration

GND-R
Common
R1
R2 Pin-2
R3
R4
R5
R6
Input Pin-3
Tx
Rx
GND-C
SW1 Pin-5
SW2

Connect the configuration cable to the Relay


card Tx, Rx and GND-C.
Connect the D-sub9 to a Windows PC.
Run the HyperTerminal from Windows
(baud rate 2400, non-parity, 8 data bits, 1
stop bits).

Delta Confidential
Relay Card Application
Common

R1

R2

R3
Common +12V
R4

R5 GND-R
+5V R6
CPU Pin
R1
Summary Alarm
GND-R R2
Power Fail
Input
R3
Battery Low
R4
UPS Events:
On Bypass
Summary Alarm Power Fail R5
Low Battery On Bypass Overload
Overload Over Temperature
R6
Output Off UPS Shutdown
Over Temperature
Charger Fail Bypass Fail
Fan Fail Fuse Fail Input
Inverter Fail Replace Battery Shutdown UPS
UPS Disconnect Battery Discharging
On Boost On Buck
On Manual Bypass Test Fail
Delta Confidential
Modbus Card
Technical Spec:
Size 130 x 60 mm
Weight 150 g
Operating Temperature 0 ~ 40° C
Operating Humidity 10 ~ 80 %
Power Input 8 ~ 20V DC
Power Consumption 1 Watt

I/O Pinout: Features:


GND Ground for RS232 Translate UPS RS232 protocol into another
RS232-Tx Tx to PC
RS232 and RS422/485 Modbus protocol.
RS232-Rx Rx from PC
RS422-T+ T+ for RS422
Device ID is adjustable by 8 dip switches, the
RS485-D+ D+ for RS485
value is from 0 to 255.
RS422-T- T- for RS422
RS485-D- D- for RS485 RS422/485 terminal resistor is selectable by
RS422-R+ R+ for RS422
dip-switch, easy to installation.
RS422-R- R- for RS422
Baud rate and parity options are also adjustable
by dip switches.
2 LEDs to indicate communication status.
Delta Confidential
Modbus Card Application

8 7 6 5 4 3 2 1

UPS

Pin Function

1 T+(D+) RS422 (RS485)


2 T-(D-) RS422 (RS485)
PLC Power Sensor
3 R+ RS422 Meter Display
4 R- RS422
5
6 Card TxD – transfer data to
PC -> RS232 pin2 RS485
7 Card RxD – receive data from
PC -> RS232 pin3 MOXA TCC 80
8 GND – (485-232)
PC -> RS232 pin5 Monitor Center
(Customer System)

Delta Confidential
Mini Card Products

TVSS Card Relay Card

SNMP Card USB Card


Delta Confidential
Mini-SNMP Card
Technical Spec:

Network Connection RJ-45 jack connector


Operating Temperature 0 ~ 40° C
Operating Humidity 10 ~ 80 %
Power Input 3.3V DC
Power Consumption 1 Watt Maximum
Size 60.5 mm x 40 mm (L x W)
Weight 30 g

Pin 1 GND Pin 2 DC (3.3V)


Pin 3 Txd→UPS Pin 4 Rxd←UPS
Pin 5 NC Pin 6 NC
Pin 7 NC Pin 8 NC
Pin 9 NC Pin 10 NC

Delta Confidential
Mini SNMP Card
Features:
SNMP agent and web server implemented for UPS
Support the following protocols: ARP, IP, ICMP, SNMPv1, SNMPv3 USM, UDP,
TCP, HTTP, FTP, TFTP, SMTP, BOOTP, SNTP, DN and Telnet
Security login by MD5
Users level management
Firmware upgrade for new features through TFTP
Batch configuration through FTP
Save UPS event log and history values in EEPROM
Schedule shutdown, restart and test UPS
Wake On LAN packet to wakeup PC
Send e-mail and SNMP trap to notify users
Provide InsightPower Client software to protect public operating systems
Provide InsightPower Manager to monitor all of the UPS information in the
network
Provide InsightPower EzSetting software to easily configure at the first time and
upgrade firmware
Delta Confidential
Mini USB Card
Features:
Communication Protocol
SCI: Delta Regular v1.51
USB: Delta HID Protocol v3.4
Support HID (Human Interface Device)
protocol.
The UPS can communicate with Windows
2000/XP/Vista/2003 without monitoring
software
• Compatible with Delta UPS standard software:
UPSentry Smart 2000

Delta Confidential
Mini Dry Contact Card
Features:
SNMP agent and web server implemented for UPS
UPS status information presented as 3 contact
closures
Configurable the input signal as shutdown UPS or
battery test
Programmable output contacts, monitors the UPS
events that users really concern in different
application practices
Configurable UPS shutdown delay time
Has the ability to protect up to 3 computers
unattended shutdown gracefully

Delta Confidential
Mini TVSS Card
Features:
This connection is optional but highly suggested as
network lines often carry dangerous surges and
spikes

Connect the Network Protection Lines


Connect the network line form the wall to the
connector marked "IN", then connect the
device(Ethernet card) to be protected to the connector
marker "OUT"

Delta Confidential
Thank You!

Delta Confidential