Professional Documents
Culture Documents
A New Approach To Fast Inrush Current Discrimination Based On Transformer Magtetizing Characteristics PDF
A New Approach To Fast Inrush Current Discrimination Based On Transformer Magtetizing Characteristics PDF
Abstract - This paper investigates the necessity of pro- nent in the current waveform is commonly used. However,
tection devices that implement fast relaying algorithms for this method requires a longer time to determine the sec-
distribution systems to meet the demands for high reliabil- ond or higher harmonic components in a transient current
ity from the viewpoint of power quality. In designing high waveform, and cannot detect inrush current within the one
speed protection systems, the fast discrimination of magne- short cycle. Therefore, the authors examined a discrimi-
tizing inrush current is also indispensable to prevent the false nating method using the magnetization characteristics of
tripping of relays. The conventional method of inrush cur- the transformer core to detect an inrush current within one
rent detection for transformer protection recognizes the ra- cycle[3].
tio of the second harmonic component of the differential cur- A considerable number of studies of detecting in-
rent. The authors propose a new approach to detecting the rush currents have been made and a method using the
inrush current based on the transformer magnetizing char- equivalent circuit of the transformer[4], a method observ-
acteristics. An inrush current occurs when the transformer ing the active power flowing into the transformer[5], a
core becomes saturated. The proposesd method estimates the method using artificial neural networks[6], a multi-criteria
transformer core saturation by the linear relation between approach[7], a method using the similarity between the
the differential current and the integral of voltage. Experi- waveforms of current and voltage[8], and a method using
mental results obtained on a single-phase transformer and a wavelet transformation[9] have been proposed. Another
three-phase transformer are presented. method similar to the proposed method of detecting an in-
rush current based on the magnetization characteristics of
Keywords - distribution system, protective relay, fast the transformer core has been proposed[10]. These meth-
fault detection, transformer, inrush current, magnetizing ods have been proposed as more reliable methods than
characteristics the conventional method using the second harmonic com-
ponent. The authors examined a method aiming princi-
1 INTRODUCTION pally at fast discrimination because they intend to apply
the method to a fast protection system for distribution sys-
Recently, more and more large-scale industrial plants tems.
and commercial facilities have introduced on-site gener-
ators, such as cogeneration systems, to increase electric
2 FAST FAULT DETECTION IN DISTRIBUTION
power reliability. Critical or sensitive customer loads suf-
SYSTEMS
fer from power quality related problems caused by volt-
age sags caused by faults on the utility system. The ITIC In Japan, the reliability of power supply is remarkably
(Information Technology Industry Council) curve is well- high because of the large investment in power transmis-
known for power acceptability[1]. To avoid the influence sion and distribution equipment as compared to the relia-
of faults on sensitive loads, the on-site generator is sep- bility in foreign countries. However, some users, such as
arate from the utility system, and power is supplied to semiconductor manufacturing plants, require considerably
the sensitive loads from the on-site generator, so that con- high quality of power, and instantaneous voltage sags ow-
tinuous operation of sensitive loads is enabled. Also in ing to a fault, such as lightning, in the utility system can
FRIENDS (Flexible, Reliable and Intelligent Electric eN- result in serious damage in these plants. Figure 1 shows a
ergy Delivery System), a new concept of distribution sys- power supply system with an on-site generator and a high-
tem, a fault must be quickly detected and removed the speed circuit breaker on the plant bus. Sensitive loads are
fault, and a high-speed switching system is also being arranged on the on-site generator side of the plant bus sep-
investigated[2]. arate from the non-sensitive loads. When a fault occurs in
As stated above, there are demands for the improve- the utility system, the fault is detected based on the cur-
ment of reliability of power supply of distribution sys- rent and voltage values on the plant bus, and the fast cir-
tems from various viewpoints. To decrease the duration cuit breaker isolates the on-site generator from the utility
of voltage sags when a fault occurs, fast fault detection system to protect the sensitive loads. In some other plants,
is necessary. For transformer primary protective relays, a fast power switching system (SSTS: Solid-State Trans-
to prevent false tripping due to an inrush current, a tech- fer Switch) has been used. This system receives power
nique using the content of the second harmonic compo- through two sources, and enables the seamless transfer
14th PSCC, Sevilla, 24-28 June 2002 Session 42, Paper 2, Page 2
of energy from a primary source to an alternative source of the transformer protection relay due to an inrush cur-
when a fault occurs in the utility system[11]. rent is normally a function specific to the transformer pri-
For another example, since the needs of consumers mary protective relay. However, to design a fast protection
will vary because of the recent tendency toward elec- method for distribution systems, it will be required to im-
tric utility deregulation, a flexible, reliable and intelligent plement the inrush detection algorithm to protective relays
electric energy delivery system (FRIENDS) has been pro- other than the transformer primary protective relay, such
posed. This system has power quality improvement cen- as overcurrent devices.
ters (QCC: Quality Control Center) that implements dis-
tributed power sources and power storage equipment be- 3 BASIC PRINCIPLE AND ALGORITHM
tween distribution substations and consumers, and uses an
information network to realize highly reliable power sup- 3.1 Theoretical Background
ply, energy conservation and high-quality customer ser- The magnetizing characteristics of a transformer core
vice. When a fault occurs on such a system, it is necessary are indicated by the B–H curve as shown in Figure 2. The
to detect the fault in a short time. A system switching magnetic field intensity H is in proportion to the current
method using thyristors has been proposed[2]. value i, and the change in magnetic flux density B from
Utility System On-site Generator residual magnetic flux density Br is in proportion to the
Fast Protective Relay G
integral of voltage v. The B–H curve inherent to each
transformer can be divided into two linear segments, one
VT is segment A–D, the condition in which the transformer
Trip Signal core is not saturated and the others are segments A–B and
C–D, the condition in which the transformer core is satu-
CT rated because the magnetizing current in the non-saturated
Plant Bus-Tie Breaker condition is negligible small.
(High-speed Mechanical
Switch)
Integral of voltage
Non-sensitve Loads Sensitive Loads Saturation flux B
Figure 1: Example of sensitive load protection system.
of current of each winding and examining whether the inrush when the secondary side was open and the other a
plotted (H, B) locus crosses the zones according to the pre- short-circuit fault when the circuit on the secondary side
defined zones[10]. The method proposed in this study dis- was shorted to simulate an transformer internal fault, and
criminates an inrush current by predicting the segment of the integral values of the voltage and current values were
the magnetization curve. Since the transformer becomes plotted using these waveform data.
equivalent to an air core condition when the magnetic
flux density B(t) exceeds the saturated magnetic flux den- 6000
Voltage[V]
sity, the reactance looks to be apparently almost constant. Current[A]
Therefore, if the ratio of the current value to the voltage 4000
6000 10
Voltage[V]
Current[A] 5
4000
0
2000
-5
0
-10
-2000 -15
-3000 -2000 -1000 0 1000 2000 3000 4000
Current[A]
-4000
(b) Current vs. integral of voltage
Figure 4: Measured waveform of voltage and short-circuit current, and
-6000
0 10 20 30 40 50 60 the locus by the proposed method.
Time[ms]
(a) Voltage and current
Figure 3 shows the waveforms obtained when an in-
20 rush occurred, and Figure 4 shows the waveforms obtained
15
when a short-circuit fault occurred. As is evident from
these figures, the locus obtained when an inrush occurred
10 is similar to the magnetization curve, while the locus ob-
Integral of Voltage[Wb]
When inrushes occur in phases B and C, and phases A and values determined by the equations from (16) to (21) us-
C they are considered in the same manner. The current ing the measured current values and the integral values of
values to be used for discrimination ima1 , ima2 , imb1 , imb2 , voltage in each phase. There are six combinations of de-
imc1 and imc2 are defined as follows. termined current value and voltage in each phase as shown
above. Figure 7 shows only two combinations in which an
ima1 ≡ i1a − i1b − i2b (16) inrush was discriminated. In this case, inrushes occur in
phases A and B. It is possible to observe an inrush on the
phase A winding from the relationship between the inte-
ima2 ≡ i1a − i1c + i2a (17)
gral value of vma and the current ima2 and an inrush on the
phase B winding from the relationship between the inte-
imb1 ≡ i1b − i1c − i2c (18) gral value of vmb and the current imb1 . With the applica-
tion of (3), inrushes on the phase A winding and phase B
winding were detected at 1.8 ms and 3.8 ms after the cur-
imb2 ≡ −i1a + i1b + i2b (= −ima1 ) (19) rent became larger than the given threshold respectively,
before the current value reached the peak. This means that
imc1 ≡ −i1a + i1c − i2a (= −ima2 ) (20) the proposed method is effective even for inrushes in two
phases.
imc2 ≡ −i1b + i1c + i2c (= −imb1 ) (21) 250
These defined values can be obtained from the mea- 200 ia
sured current values. The voltage in each phase is as 150
Primary Current [A]
shown below. 100
di1a 50 ic
vma = v1a − R1a i1a − L1a (22) 0
dt
-50
di1b
vmb = v1b − R1b i1b − L1b (23) -100
dt
-150 ib
di1c -200
vmc = v1c − R1c i1c − L1c (24)
dt -250
0 5 10 15 20 25 30 35 40 45 50
The relationship between combination of voltage and Time [ms]
defined current values to which this proposed method is Figure 6: Waveform of current during inrush.
applied and the phase in which an inrush is discriminated
is shown below: The relationship between combination of 25
voltage and defined current values to which this proposed 20 (va, ima2)
method is applied and the phase in which an inrush is dis- 15
Integral of Voltage [Wb]
400 20
ic (vmc, imc2)
300 15
Integral of Voltage[Wb]
200 ia 10
Primary Current [A]
100 5
0 0
-100 -5
-200 -10
-300 ib -15
fault+inrush
-400 -20
0 5 10 15 20 25 30 35 40 45 50 -800 -600 -400 -200 0 200 400
Time [ms] Current[A]
Figure 8: Waveform of current during internal fault. Figure 10: Example of inrush during short-circuit fault.
25
5 DISCUSSION
20 5.1 Relationship between residual magnetic flux density
(va, ima1)
15 and inrush
Integral of Voltage [Wb]
which the condition of |ima1 (= −imb2 )| > imin has lasted -25
for a determined time, tmin , if the conditions of (vma , ima1 )
-30
and (vmb , imb2 ) are not discriminated the inrush, i.e. there -800 -600 -400 -200 0 200 400
is a strong possibility that an inrush has not occurred in Current[A]
phase A or phase B, and it is considered that a short- Figure 11: Example of failure to detect an inrush.
circuit fault may have occurred. Also imb1 (= −imc2 ) and
imc1 (= −ima2 ) are evaluated in the same manner, and, If the residual magnetic flux is obtained when a trans-
when the short-circuit fault is observed in at least two of former stops, the occurrence of an inrush current can be
these three conditions, it is considered that a short-circuit prevented by synchronous controlled switching suitable
fault has occurred. The condition of detecting a short- for each of three phases. However, in the transformers
circuit fault is as follows: used on plant facilities of customers, it is generally diffi-
cult to obtain the residual magnetic flux before the trans-
formers energize. Therefore, it is considered to be diffi-
if at least two of the following three conditions: cult to prevent an inrush by optimal controlled switching
if {|ima1 (= −imb2 ) > imin |} and in plant facilities of customers.
{(vma , ima1 ) and (vmb , imb2 ) not inrush}
if {|imb1 (= −imc2 ) > imin |} and 5.2 CT saturation
{(vmb , imb1 ) and (vmc , imc2 ) not inrush} Since the proposed method is based on the magneti-
if {|imc1 (= −ima2 ) > imin |} and zation characteristics of the transformer core, its discrim-
{(vmc , imc1 ) and (vma , ima2 ) not inrush} inating performance may degrade when CT is saturated if
then short-circuit fault the voltage sag is small, because the CT saturation affects
14th PSCC, Sevilla, 24-28 June 2002 Session 42, Paper 2, Page 7
the secondary sigals and the saturation characteristics of [3] M. Kitayama and M. Nakabayashi, “A Fast Dis-
the transformer core cannot be estimated correctly by the crimination Method of Inrush Current based on
distorted signals. However, measuring devices, such as Transformer Magnetizing Characteristics”, Trans.
Rogowski coils and optical CTs, will be mainly used in on Electrical Engineering in Japan, Vol.121, No.8,
distribution systems. Although Rogowski coils have some pp.982–989, 2001
problems, such as a problem of noise removal, because of
their low sensitivity, recently, those on the practical use [4] K. Inagaki, M. Higaki, Y. Matsui, K. Kurita,
level have been developed[13]. Optical CTs are character- M. Suzuki, K. Yoshida and T. Maeda, “Digital Pro-
ized by their compact sensor blocks, ease of ensuring elec- tection Method for Power Transformers Based on
trical insulation and resistance to external noises because an Equivalent Circuit Composed of Inverse Induc-
they obtain measurements based on the optical Faraday ef- tance”, IEEE Trans. on Power Delivery, Vol.3, No.4,
fect. The use of such CTs without a core will decrease the pp.1501–1510, 1988
problems of CT saturation. [5] K. Yabe,”Power Differential Method for Discrimina-
tion between Fault and Magnetizing Inrush Current
6 CONCLUSION in Transformers”, IEEE Trans. on Power Delivery,
Vol.12, No.3, pp.1109–1118, 1997
This paper proposed a new fast discriminating method
of magnetizing inrush in energizing transformers in distri- [6] B. Grčar, G. Štumberger and J. Pihler, “Trans-
bution systems. former Protection based on the New Theoretical
Distribution systems require fast fault detection from Background and with Improved Inrush Recogni-
the viewpoint of power quality. Therefore, discriminating tion”, Proc. of 12th PSCC, pp.101–106, 1996
an inrush to meet the demand for increased reliability is
also indispensable. Formerly, the function of detecting an [7] B. Kasztenny, E. Rosolowski, M. M.Saha and
inrush was a function specific to the transformer primary B. Hillstrom, “A Comparative Analysis of Protection
protective relay. However, it will be required to provide Principles for Multi-criteria Power Transformer Re-
overcurrent relays with this function on distribution sys- laying”, Proc. of 12th PSCC, pp.107–113, 1996
tems. [8] S. Guocai and Y. Dachan, “Identifying Inter-
Therefore, an new method of discriminating inrush nal Faults of Transformers through the Similar-
current that predicts the magnetization characteristics of ity Degree between Voltage and Current”, Proc.
the transformer core based on the relationship between in- of IEEE/PES 2000 Winter Meeting, pp.1151–1156,
tegral values of voltage and current values was proposed. 2000
To apply this method to a three-phase transformer, it is
necessary to use the single-phase inrush current values de- [9] Moisés Gómez-Morante and Denise W.Nicoletti,
termined in consideration of the helping effect. “A Wavelet-based Differential Transformer Protec-
The authors validated the proposed method using tion”, IEEE Trans. on Power Delivery, Vol.14, No.4,
test data obtained with the transformer of actual equip- pp.1351–1358, 1999
ment. The proposed method could detect an inrush current
[10] J. Koda and K. Yabe,”Dynamic Estimation of Mag-
within a half cycle, 4 to 5 ms, and proved to be effective.
netizing Curve for Transformer Protection Relay”,
The authors will examine the discriminating algorithm Proc. of the ICEE, E02, pp.94–97, 1997
in more detail based on the results of the experiments,
the hardware architecture to which the algorithm will be [11] M. Takeda, H. Yamamoto, T. Aritsuka, I. Kamiyama
implemented, and the fast protection system using this and G. F. Reed, “Development of a Novel Switch
method on distribution systems. Device and Application to a Solid-State Transfer
IEEE Power Engineering Education Committee, Ad- Switch”, Proc. of IEEE/PES 1999 Winter Meeting,
vancements in Microprosessor Based Protection and pp.1151–1156, 1999
Communication, IEEE Tutorial Course, 97TP120-0, 1997
[12] W. K. Sonnemann, C. L. Wagner and G. D. Rock-
efeller, “Magnetizing Inrush Phenomena in Trans-
REFERENCES former Banks”, AIEE Transactions, Vol.77, part.III,
[1] G. T. Heydt, R. Ayyanar and R. Thallam, “Power pp.884–892, Oct.1958
Acceptability”, IEEE Power Engineering Review, [13] L. Kojovic, “Rogowski Coils Suit Relay Protection
Vol.21, No.10, pp.12–15, 2001 and Measurement”, IEEE Computer Applications in
Power, Vol.10, No.3, pp.47–52, 1997
[2] R. Hara, T. Suzuki, H. Kita, E. Tanaka, J. Hasegawa
and I. Iyoda, “The Effects of the Transfer Switching [14] IEEE Power Engineering Education Committee, Ad-
on the Low Voltage Side of Quality Control Center vancements in Microprosessor Based Protection and
in FRIENDS”, Proc. of POWERCON 2000, pp.667– Communication, IEEE Tutorial Course, 97TP120-0,
671, 2000 1997