NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE

SUBSTRATE CLADDING PANELS HAVE TO BE SATISFIED.

FIXING

THERMOPAD FixU T, THICKNESS 5 mm


art.No 05.001.5

WASHER

THERMAL INSULATION LAYER

BRACKET FixU T, FIXED SUPPORT


art.No 02.ft.190

T PROFILE 110x60x2 mm
art.No 01.2.110602.6 RAINSCREEN SYSTEM

art.No 04.4.4812.1 QV2


CONCEALED FASTENING SYSTEM
HPL PANEL FUNDERMAX USING GLUING TECHNOLOGY

SikaTack-PANEL ADHESIVE CLADDING PANELS


art.No 07.001.1

SikaTack-PANEL FIXING TAPE FUNDERMAX MAX EXTERIOR


art.No 07.001.3
DRAWING

01 HORIZONTAL SECTION

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
art.No 04.4.4812.1
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


FIXING CLADDING PANELS HAVE TO BE SATISFIED.

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

T PROFILE 110x60x2 mm
art.No 01.2.110602.6

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVE
art.No 07.001.1

art.No 04.4.4812.1
RAINSCREEN SYSTEM
FIXING
QV2
BRACKET FixU T, FIXED SUPPORT
CONCEALED FASTENING SYSTEM
art.No 02.ft.190 USING GLUING TECHNOLOGY
THERMOPAD FixU T, THICKNESS 5 mm
art.No 05.001.5 CLADDING PANELS

FUNDERMAX MAX EXTERIOR

THERMAL INSULATION LAYER DRAWING

SUBSTRATE 02 VERTICAL SECTION

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.
SUBSTRATE
_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT
AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
THERMAL INSULATION LAYER
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

HPL PANEL FUNDERMAX _ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE
CLADDING PANELS HAVE TO BE SATISFIED.

SikaTack-PANEL FIXING TAPE


art.No 07.001.3
SikaTack-PANEL ADHESIVE
art.No 07.001.1

FIXING

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

WASHER

BRACKET FixU L, FLEXIBLE SUPPORT RAINSCREEN SYSTEM


art.No 02.fl.190

QV2
CONCEALED FASTENING SYSTEM
L PROFILE 60x40x2 mm
art.No 01.1.60402.6
USING GLUING TECHNOLOGY

CLADDING PANELS
art.No 04.4.4812.1

FUNDERMAX MAX EXTERIOR

DRAWING

03 EXTERNAL CORNER

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
FIXING
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.
THERMOPAD FixU T, THICKNESS 5 mm
art.No 05.001.5

WASHER

BRACKET FixU T, FIXED SUPPORT


art.No 02.ft.190

L PROFILE 60x40x2 mm
art.No 01.1.60402.6

art.No 04.4.4812.1

HPL PANEL FUNDERMAX RAINSCREEN SYSTEM

QV2
SikaTack-PANEL ADHESIVE CONCEALED FASTENING SYSTEM
art.No 07.001.1
SikaTack-PANEL FIXING TAPE USING GLUING TECHNOLOGY
art.No 07.001.3
CLADDING PANELS

FUNDERMAX MAX EXTERIOR


THERMAL INSULATION LAYER
DRAWING
SUBSTRATE
04 INTERNAL CORNER

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SUBSTRATE SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
THERMAL INSULATION LAYER
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

T PROFILE 110x60x2 mm
art.No 01.2.110602.6

art.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

HPL PANEL FUNDERMAX RAINSCREEN SYSTEM

SikaTack-PANEL ADHESIVE
art.No 07.001.1 QV2
CONCEALED FASTENING SYSTEM
USING GLUING TECHNOLOGY

CLADDING PANELS
PERFORATED ALUMINUIM SHEET

FUNDERMAX MAX EXTERIOR

SELF-DRILLING SCREW
DRAWING
L PROFILE 60x40x2 mm
art.No 01.1.60402.6
05 VERTICAL SECTION_FACADE BASE

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
ALUMINIUM SHEET
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
PERFORATED ALUMINIUM SHEET
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


L PROFILE 40x40x2 mm CLADDING PANELS HAVE TO BE SATISFIED.
art.No 01.1.40402.6

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVE
art.No 07.001.1

BRACKET FixU T, FIXED SUPPORT


art.No 02.ft.190

FIXING

art.No 04.4.4812.1

THERMOPAD FixU T, THICKNESS 5 mm


art.No 05.001.5 RAINSCREEN SYSTEM

QV2
T PROFILE 110x60x2 mm CONCEALED FASTENING SYSTEM
art.No 01.2.110602.6
USING GLUING TECHNOLOGY

CLADDING PANELS

FUNDERMAX MAX EXTERIOR

THERMAL INSULATION LAYER DRAWING

SUBSTRATE
06 VERTICAL SECTION_ROOFBORDER COVER

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

SELF-DRILLING SCREW

FIXING
THERMOPAD FixU L, THICKNESS 5 mm
art.No 05.001.1

WASHER

THERMAL INSULATION LAYER

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

RAINSCREEN SYSTEM

L PROFILE 60x40x2 mm
art.No 01.1.60402.6 QV2
CONCEALED FASTENING SYSTEM
HPL PANEL FUNDERMAX USING GLUING TECHNOLOGY

CLADDING PANELS
SikaTack-PANEL ADHESIVE
art.No 07.001.1
FUNDERMAX MAX EXTERIOR
SikaTack-PANEL FIXING TAPE
art.No 07.001.3
DRAWING

07.1 HORIZONTAL SECTION_WINDOW REVEAL

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

SELF-DRILLING SCREW

FIXING
THERMOPAD FixU L, THICKNESS 5 mm
art.No 05.001.1

WASHER

THERMAL INSULATION LAYER

ALUMINIUM SHEET

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

RAINSCREEN SYSTEM

L PROFILE 60x40x2 mm
art.No 01.1.60402.6 QV2
CONCEALED FASTENING SYSTEM
art.No 04.4.4812.1 USING GLUING TECHNOLOGY

HPL PANEL FUNDERMAX CLADDING PANELS

SikaTack-PANEL ADHESIVE FUNDERMAX MAX EXTERIOR


art.No 07.001.1

SikaTack-PANEL FIXING TAPE DRAWING


art.No 07.001.3

07.2 HORIZONTAL SECTION_WINDOW REVEAL

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


SUBSTRATE
AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
THERMAL INSULATION LAYER
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


T PROFILE 110x60x2 mm CLADDING PANELS HAVE TO BE SATISFIED.
art.No 01.2.110602.6

art.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVE
art.No 07.001.1

L PROFILE 40x40x2 mm
art.No 01.1.40402.6 RAINSCREEN SYSTEM

PERFORATED ALUMINIUM SHEET


QV2
CONCEALED FASTENING SYSTEM
SikaTack-PANEL ADHESIVE USING GLUING TECHNOLOGY
art.No 07.001.1

SikaTack-PANEL FIXING TAPE CLADDING PANELS


art.No 07.001.3

FUNDERMAX MAX EXTERIOR

DRAWING

08.1 VERTICAL SECTION_WINDOW LINTEL

EDITION

JANUARY 2015
8.1 SUBSTRATE
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
THERMAL INSULATION LAYER
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


T PROFILE 110x60x2 mm CLADDING PANELS HAVE TO BE SATISFIED.
art.No 01.2.110602.6

art.No 04.4.4812.1

FIXING

BRACKET FixU L, FLEXIBLE SUPPORT


art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVE
art.No 07.001.1

L PROFILE 40x40x2 mm RAINSCREEN SYSTEM


art.No 01.1.40402.6

ALUMINIUM SHEET QV2


CONCEALED FASTENING SYSTEM
SELF-DRILLING SCREW USING GLUING TECHNOLOGY

CLADDING PANELS

FUNDERMAX MAX EXTERIOR

DRAWING

08.2 VERTICAL SECTION_WINDOW LINTEL

EDITION

JANUARY 2015
8.2 NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
art.No 04.4.4812.1
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
FIXING OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


BRACKET FixU L, FLEXIBLE SUPPORT CLADDING PANELS HAVE TO BE SATISFIED.
art.No 02.fl.190

THERMOPAD FixU L, THICKNESS 5 mm


art.No 05.001.1

T PROFILE 110x60x2 mm
art.No 01.2.110602.6

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVE
art.No 07.001.1

RAINSCREEN SYSTEM

L PROFILE 60x40x2 mm
art.No 01.1.60402.6 QV2
CONCEALED FASTENING SYSTEM
ALUMINIUM SHEET USING GLUING TECHNOLOGY

CLADDING PANELS

FUNDERMAX MAX EXTERIOR

DRAWING

08.3 VERTICAL SECTION_WINDOW LINTEL

EDITION

JANUARY 2015
NOTES

_ THE SPECIFICATION OF THE PROFILES, ACCESSORIES AND THEIR


POSITIONING, HAS TO BE AGREED UPON STATIC ANALYSIS.

_ THE STATIC ANALYSIS MUST BE APPLIED FOR EACH PROJECT


AND HAS TO RESPECT THE INDIVIDUALITY OF THE PROJECT,
SPECIFIC CONDITIONS AND LOCAL REGULATIONS. IT PROVIDES
SAFETY CHECK, VERIFICATION OF THE COMPONENTS AND
OPTIMIZATION.

_ ALL TECHNICAL REQUIREMENTS GIVEN BY THE SUPPLIER OF THE


CLADDING PANELS HAVE TO BE SATISFIED.

SELF-DRILLING SCREW

ALUMINIUM SHEET

PERFORATED ALUMINIUM SHEET

L PROFILE 40x40x2 mm
art.No 01.1.40402.6

HPL PANEL FUNDERMAX

SikaTack-PANEL ADHESIVE
art.No 07.001.1

T PROFILE 110x60x2 mm
art.No 01.2.110602.6 RAINSCREEN SYSTEM

FIXING
QV2
CONCEALED FASTENING SYSTEM
art.No 04.4.4812.1
USING GLUING TECHNOLOGY
BRACKET FixU T, FIXED SUPPORT
art.No 02.ft.190 CLADDING PANELS

THERMOPAD FixU T, THICKNESS 5 mm


art.No 05.001.5 FUNDERMAX MAX EXTERIOR

DRAWING

THERMAL INSULATION LAYER


09 VERTICAL SECTION_WINDOW SILL
SUBSTRATE
EDITION

JANUARY 2015