Professional Documents
Culture Documents
Chap10 Consideration PDF
Chap10 Consideration PDF
CHAPTER 10
GROUNDING
10-1. Basic principles of grounding. (1) Water tab1 es are gradually falling in many
Grounding is provided to limit potential (voltage) areas.
differences to values that will not cause undue haz- (2) There are more underground installations
ards to personnel and equipment. A ground system of nonmetallic pipes and conduits, which do not
which provides adequate current-carrying capacity provide low-resistance ground connections.
and a low-resistance path to an earthing connection (3) Electric systems are continually expanding
will dissipate, isolate, or disconnect overpotential with an associated fault current increase which may
areas resulting from fault overcurrents or surge require a decrease in grounding resistance.
overvoltages. A ground path can consist of single or
(4) Corroded connections may increase the re-
multiple conductors whose connection provides ad-
sistance.
equate thermal and conductance capacities. The
earthing connection is generally a metallic electrode
1O-2. Grounding provisions.
such as a rod, a water pipe, a counterpoise, or a
ground grid system installed below grade. Maintenance personnel deal with two types of
a. Electrode resistance. The resistance of a grounding systems: permanent and temporary.
ground electrode is primarily determined by the a. Permanent grounding systems. Permanent
earth surrounding the electrode. Test data given in grounding is provided for the efficient, effective,
IEEE 142 indicate that about 90 percent of the total safe operation of electrical power systems.
resistance of a ground lies within 6 to 10 feet (1.8 to
(1) Safety. Equipment grounding, which is the
3 meters) from the electrode. The diameter of the
grounding of all exposed or accessible noncurrent-
rod has only a negligible effect on the resistance of a
- carrying parts of electrical devices and equipment,
ground. The resistance of the soil is dependent upon
reduces the hazards of contact by personnel.
the type of soil and its moisture content. Electrodes
should be long enough to penetrate a relatively per- (2) System operation. System grounding, which
manent moisture level and should extend well be- is the grounding of one conductor point on an elec-
low the frost line. trical circuit, stabilizes the voltages to protect the
b. Factors which can degrade initial good equipment and provides a basis for adequate protec-
grounds. Tests should always be made at times tive relaying.
when the surrounding soil can be expected to have b. Temporary grounding. Temporary grounding is
the least moisture. The following factors indicate the personal protective grounding, which is pro-
the importance of continuous periodic testing of vided to protect persons engaged in de-energized
grounding systems. electric line maintenance.
Section II-MAINTENANCE
1O-3. Grounding maintenance safety. 10-4. Visual inspection of grounds.
Extreme care must be exercised in inspecting, Visual inspection of ground connections to equip-
maintaining and testing grounds and ground sys- ment, equipment enclosures, structural members,
terns. Never open a grounding connection unless the fencing, and system neutrals should be made at
connected equipment is deenergized, or an adequate least every 2 years. More frequent inspections
safety bypass is provided. Always wear rubber should be made where appropriate to the system’s
gloves and follow facility safety manual procedures. size and importance. Loose, broken, or missing con-
This applies equally to grounds installed on struc- nections should be repaired or replaced as required.
tural or supporting members, ground connections to Connections or connectors showing signs of over-
equipment enclosures, and neutral grounds of pri- heating, as evidenced by discolorations, should be
mary or secondary systems. The life and safety of reported, as this may be the result of an improper
those in the vicinity of electrical facilities depend on application or installation. If connections are found
L how carefully and completely inspections and main- to be corroded or rusted, they should be cleaned and
tenance of grounds and grounding systems are per- corrective measures should be taken to prevent a
formed. recurrence of this situation. Excessive amounts of
10-l
TM 5-684/NAVFAC MO-200/AFJMAN 32-1082
corrosion should be reported, as this may indicate a. Stainless steel ground rods. Do not use stain-
the need for cathodic protection in the area. less steel ground rods. Their performance can be
unpredictable because of their tendency toward lo- -
10-5. Galvanic corrosion of grounds.
calized corrosion.
The use of dissimilar metals embedded in the earth b. Underground pipe lines. The bonding of inte-
in and around generating stations and substations rior metallic pipelines to an electrical system’s
results in the formation of a huge galvanic cell. ground provisions of copper (which is required by
Steel or galvanized structures, including conduits,
code) if done incorrectly, can result in galvanic cor-
cable sheaths, pipes, and structural footings, where
rosion of the underground pipeline. Installation of a
used either purposely or inadvertently in the
dielectrically-insulated fitting on the pipe above
ground system, are subject to galvanic corrosion.
ground, and before the copper ground connection,
Attention should be given to the necessity of provid-
will eliminate the earth’s electrolytic coupling be-
ing corrosion mitigation measures under such cir-
cumstances. tween the underground cable and the ground wire.
Section III-TESTING
sary. Auxiliary reference grounds and test instru- This arrangement is shown in figure 10-3. The
ments are necessary for ANSI/IEEE 80 and ground rods should be driven 8 to 10 feet (2.5 to 3
- ANSI/IEEE 81 methods. meters) into the earth and spaced not less than 50
a. Minor grounding installations. The following feet (15 meters) apart. Three separate tests are
methods are suitable for measuring the resistance made to determine the resistance of each of the
of isolated ground rods or small grounding installa- series circuits when composed of only two grounds.
tions. Precision in measurements is difficult to ob- The unknown resistance may then be calculated as
tain. Normally an accuracy of 25 percent is suffi- follows by equation 10-l.
cient, since the surrounding soil will not have R, + R, - R,
consistent values of temperature, moisture, and R, = (eq. 10-l)
depth. 2
(1) Portable ground testing instruments. A Actual resistances may be determined by using one
usual way to measure the ground resistance is with of the following methods.
a low-range, self-contained, portable earth-tester in- (a) AC voltmeter-ammeter method. The con-
strument such as the “Megger” Ground Tester or nections for the ac voltmeter-ammeter test are
Ground Ohmer. The manufacturers’ instructions shown in figure 10-3. The resistances of the ground
should be followed in the use of this instrument. circuits are determined from the meter readings
The two most common methods of measuring the and these values are then used in calculating R,.
ground resistance with this type of instrument are Stray alternating currents of the same frequency as
the direct-reference or two-point method shown in the test current, if present, will introduce some er-
figure 10-l and the auxiliary ground method shown ror in measurements.
in figure 10-2. (b) DC voltmeter-ammeter method. A dc
(2) Three-point method. The three-point voltmeter-ammeter method may also be used to de-
method of measuring ground resistance requires termine the resistance of each pair of grounds in
two auxiliary grounds, similar to those required series. Like the ac method, it is limited to locations
with portable ground testing equipment, except where power is available or where a battery source
that each auxiliary ground should have a resistance may be used with the regulating apparatus re-
approximately equal to the ground being tested. quired to control the current flow. The line supply-
-
------_-- 1
I
r-PORTABLE GROUND
RESISTANCE MEASURING
INSTRUMENT
GROUND TO - W A T E R
B E TESTEDd SYSTEM
I_ 5 (LOW RESISTANCE)
I I
t--PORTABLE GROUND
RESISTANCE MEASURING
INSTRUMENT
GROUND TO
BE TESTED C
=
_I
fT( 15M) M I N I M U M 50 fT( 15M) MAXIMUM ’
10-3
TM 5-684/NAVFAC MO-200/AFJMAN 32-1082
ing the current must be free from grounds to mini- tion of these methods may be necessary. Also see
mize the effect of cross-currents. To compensate for IEEE 142 for additional information on the effect of
the effect of stray dc voltage currents in the area, these changes.
readings should be made at both polarities. a. Adding rods. An easy and preferable method of
b. Major grounding installations. Where accurate reducing the resistance is to provide more rods. For
measurements of extensive low-resistance ground- example, two ground rods, properly spaced and con-
ing systems are required, more elaborate test meth- nected in parallel, should have a combined resis-
ods and equipment are needed using considerably tance on the order of 60 percent of the resistance of
larger separation distances between test electrodes. one rod; and for three rods, 40 percent of that resis-
Normally large facility substations are tested with tance. In general, proper spacing of rods means
the fall-of-potential method in accordance with placing rods at least one rod length apart.
ANSI/IEEE 81 requirements. Figure 10-4 shows a b. Increased rod length. Providing longer rods is
field setup for this method and the ground resis- particularly effective where low-resistance soils are
tance curve. The resistance shown on the flat part of too far below the surface to be reached with the
the curve is taken as the resistance of the ground. normal rod lengths of 8 to 10 feet (2.5 to 3 meters).
The self-contained earth tester instrument shown The amount of improvement from longer rods de-
should be used rather than a voltmeter-ammeter pends on the depth of the low-resistance soils. A
combination, as the earth tester is designed to rather sharp decrease in the measured resistance is
eliminate the effects of stray currents. The primary usually noticed where the rod has been driven to a
advantage of this method is that potential and cur- low-resistance soil level. Soil resistivity usually (but
rent electrodes (probes) may have substantially not always) decreases with depth because there is
higher resistance than the ground system being normally an increased moisture content.
tested without significantly affecting the accuracy c. Soil treatment. A method called salting has tra-
of the measurement. ditionally been used to treat the soil around ground
(1) Major substations. To allow for seasonal rods.
variations it is recommended that tests be made at (1) Sodium chloride, calcium chloride, magne-
the same time each year or for each season of the sium, and copper sulfate are all used as treatment.
year to allow for accurate comparison. Bentonite, a natural clay, works well, except in a
(2) Procedures. Tests should be performed in very dry environment. A pre-packaged mixture of 75
accordance with written procedures. Provide ad- percent gypsum, 20 percent bentonite, a 5 percent
equate safety precautions as all electrical conduct- sodium sulfate. is recommended. Ground rods can
ing paths for overvoltage and fault currents are also be encapsulated in concrete rather than using a
connected to the substation grid. soil treatment.
(2) Soil treatment is a reliable and effective
10-9. Method of reducing ground resistances. method for reducing ground resistance and is par-
Ground tests may indicate that the ground resis- ticularly suitable for improving a high-resistance
tance exceeds safety requirements. Adding rods, in- soil. The treatment is advantageous where long
creasing rod lengths, soil treatment, or a combina- rods are impractical because of rock strata or other
10-4
TM 5-684/NAVFAC MO-200/AFJMAN 32-1082
Station f e n c e p e r i m e t e r
f
00
-7
/////////r////f//
Fixed C u r r e n t
LA-..aLI-
IvIuvuulc “7tentiol
l-c
Probe C
Probe: j ?
--ANSI/IEEE 8 1 Distances
obstructions to deep driving. There are two practi- grounding system that uses a 2-inch (50-millime-
cal ways of accomplishing this as shown in figure ter) copper tube filled with metallic salts and avail-
10-5. Where space is limited, a length of tile pipe is able in various lengths. Since this method uses me-
sunk into the ground a few inches (millimeters) tallic salts it is not recommended except as a last
from the ground rod and filled to within approxi- resort. The tube is also available as a straight unit,
mately 1 foot (0.3 meters) of the ground level with or in an L-shaped configuration which allows the
the treating chemical. The second method is appli- tube to be installed on its side in a shallow trench.
cable where a circular or semicircular trench can be Changes in atmospheric pressure “pump” air
dug around the ground rod to hold the chemical. through the breather holes at the top of the tube.
The chemical must be kept several inches (millime-
Moisture in the air condenses inside the tube to
ters) away from direct contact with the ground rod
move slowly down through the bed of metallic salts,
to avoid corrosion of the rod. The first treatment
providing a self-maintaining low-resistance system
usually requires 50 to 100 pounds (22 to 45 kilo-
with a much greater life expectancy than conven-
grams) of material and will retain its effectiveness
for 2 to 3 years. Each replenishment of the chemical tional ground rods.
extends its effectiveness for a longer period, thus e. Combination methods. A combination of meth-
increasing treatment intervals. To start the action ods may be advantageous and necessary to provide
promptly, the first treatment of chemical should be the desired ground resistance. Adding specialized
flooded. rods or a combination of multiple rods and soil
d. Specialized rods. In lieu of adding additional treatment may be effective. Multiple of longer rods
rods or lengthening rods, a copper tubing grounding are effective where conditions permit this type of
system can be used. There is an Underwriters-listed installation.
10-5
TM 5-684/NAVFAC MO-200/AFJMAN 32-1082
/-CROWD ROD -/
901L TREATMENT
10-6