Professional Documents
Culture Documents
Neutral Earthing#1
Neutral Earthing#1
NEUTRAL EARTHING
NEUTRAL
EARTHING www.cressall.com
Cressall neutral earthing resistors (NERs) are The rating of an NER is chosen to meet the
employed in AC distribution networks to limit requirements of the system protection scheme;
the current that would flow through the neutral this will include consideration of maximum
point of a transformer or generator in the event acceptable fault current, earth potential levels,
of an earth fault. and preventing damage caused by the fault.
6
CHS Controls AB
Florettgatan 33
SE-254 67 Helsingborg, Sweden
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se
www.chscontrols.se
www.cressall.com
Neutral Earthing
CRESSALL NERS HAVE NUMEROUS BENEFITS:
Choice Stability and predictability Earth Fault Detection 11
An extensive range of metal resistor elements The resistance value is set at the manufacturing
allows selection of the most efficient and cost stage and remains constant throughout the life Dynamic Braking 12
effective solution for any required duty. Cressall of the NER. Unlike liquid resistors, changes in
can manufacture NERs for any system voltage resistance value due to the fluctuations in ambi- Harmonic Filters 18
and initial current with rated times from a few ent temperature are negligible. This means that
seconds to continuous. protection levels can be accurately pre-deter- Portable Load Units 20
mined.
Ease of installation
Cressall NERs are compact and do not require
site calibration or auxiliary power supplies.
Reliability
NERs may only be called upon to operate a few
times in their service life, which may be 25 years
or more. Cressall NERs have been proven reli-
able in numerous installations and under severe
climatic conditions world-wide.
7
CHS Controls AB
Florettgatan 33
SE-254 67 Helsingborg, Sweden
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se
www.chscontrols.se
NEUTRAL
EARTHING www.cressall.com
Construction
Standards
At present the only standard for NERs is ANSI/ The tie-rods are supported between galvanised
IEEE Std 32, 1972. Cressall NERs can be designed end-plates to form banks. These banks can be
and tested to comply with this standard, or with mounted on top of each other with intermediate
individual client specifications. insulators to form a complete self-supporting
stack.
Resistor elements
Interconnections between coils are copper,
For the majority of ratings the most suitable
using two bolts per joint.
element is the type RP oval edge-wound coil.
8
CHS Controls AB
Florettgatan 33
SE-254 67 Helsingborg, Sweden
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se
www.chscontrols.se
www.cressall.com
Neutral Earthing
tor earth connection. Where required this can accidental contact. Suitable steel plinths can be
Portable Load Units 20
also be enclosed in a cable box. Earthing of the supplied.
enclosure is via two separate stud type termi- Static Load Banks 22
nals, fitted diagonally opposite each other.
Expanded Mesh 24
Edgewound 26
Standard
enclosure to
IP23 or IP54
Stainless steel
type RP resistor
elements
All primary
and secondary
insulators are
ceramic
Undrilled
gland plate
Double bolted
interconnections Separate
enclosure earth
LV earth
connection
Standard enclosure either unpainted
stainless steel or polyester powder
coated mild steel
9
CHS Controls AB
Florettgatan 33
SE-254 67 Helsingborg, Sweden
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se
www.chscontrols.se
NEUTRAL
EARTHING www.cressall.com
Other equipment
Where required cable boxes can house current
transformers, isolators, vacuum contactors or
other ancillary equipment.
Standard tests
As standard, NERs are tested to the requirements
of ANSI/IEEE Std 32, 1972.
10
CHS Controls AB
Florettgatan 33
SE-254 67 Helsingborg, Sweden
Tel +46 42 38 61 00, Fax +46 42 38 61 29
chs@chscontrols.se
www.chscontrols.se
www.cressall.com
Neutral Earthing 6
Dynamic Braking 12
Harmonic Filters 18
Expanded Mesh 24
Edgewound 26
Service Grids 31
Wirewound 32
• Options for indication, metering, and earth. In the event of an earth fault the resistor
pulsing and auxiliary resistance circuits will limit the fault current to a few amps (typically
3-5). Control equipment continuously monitors this
In low voltage three phase distribution networks
earth current and provides indication when it exceeds
where continuity of supply is a priority, high
a predetermined level.
resistance earthing reduces the risk of service
interruptions caused by an earth fault while main- Units can be supplied with a range of features:
taining the integrity of the system. • Earth fault protection and monitoring
Where their use is permitted, Cressall earth fault • Pulsed earth fault protection and hand held
detection resistors are ideal for sensing and sensor for easy fault finding
locating earth faults quickly, minimising plant • Double resistor paths with continuous
down time in industrial applications. monitoring for fail safe protection
11