The document discusses earth fault detection logic for a 380 kV overhead transmission line. It explains that the zero sequence current pickup is stabilized to avoid false detection during conditions like unbalanced phases or CT saturation that could cause zero sequence current flow even without a fault. It recommends using a combination of zero sequence current and voltage to reliably detect earth faults in earthed systems.
The document discusses earth fault detection logic for a 380 kV overhead transmission line. It explains that the zero sequence current pickup is stabilized to avoid false detection during conditions like unbalanced phases or CT saturation that could cause zero sequence current flow even without a fault. It recommends using a combination of zero sequence current and voltage to reliably detect earth faults in earthed systems.
The document discusses earth fault detection logic for a 380 kV overhead transmission line. It explains that the zero sequence current pickup is stabilized to avoid false detection during conditions like unbalanced phases or CT saturation that could cause zero sequence current flow even without a fault. It recommends using a combination of zero sequence current and voltage to reliably detect earth faults in earthed systems.
The document discusses earth fault detection logic for a 380 kV overhead transmission line. It explains that the zero sequence current pickup is stabilized to avoid false detection during conditions like unbalanced phases or CT saturation that could cause zero sequence current flow even without a fault. It recommends using a combination of zero sequence current and voltage to reliably detect earth faults in earthed systems.
1207A 3I0 pickup stabilisation (3I0>/Iphmax): In the event of large phase currents, system unbalance (e.g. non-transposed lines) and CT errors (e.g. saturation) zero sequence current flow via the measuring circuit of the relay is possible although no earth fault is present. To avoid earth fault detection under these conditions, the zero sequence current pickup is stabilised by this set factor.
Figure 19: Stabilised zero sequence pickup threshold
Unless extreme system unbalance or exceptionally large CT errors are expected, the default setting of 10% i.e. 0.10 can be maintained, as is done for this example. 1209A criterion for earth fault recognition: For the settings 1203 and 1204 above, and in Figure 18, the method and logic of the earth fault detection were explained. With this setting the user has the means to influence the earth fault detection logic. In earthed systems it is recommended to use the very reliable OR combination of zero sequence current and voltage for the earth