Professional Documents
Culture Documents
Module Iii Refrigeration Cycle
Module Iii Refrigeration Cycle
1 ton 2000lb
1 ton of refrigeration=
24 hr( ton )( 144lbBTU )=12000 BTU
hr
1 ton 335 KJ hr
1 ton of refrigeration= ¿ )( )( )= 3.516KW
24 hr kg 3600 s
VAPOR COMPRESSION REFRIGERATION SYSTEM
The vapor-compression uses a circulating liquid refrigerant as the medium which absorbs and removes
heat from the space to be cooled and subsequently rejects that heat elsewhere. Figure depicts a typical,
single-stage vapor-compression system. All such systems have four components: a compressor,
a condenser, a thermal expansion valve (also called a throttle valve or metering device), and an
evaporator.
1. Circulating refrigerant enters the compressor in the thermodynamic state known as a saturated
vapor and is compressed to a higher pressure, resulting in a higher temperature as well. The hot,
compressed vapor is then in the thermodynamic state known as a superheated vapor and it is at
a temperature and pressure at which it can be condensed with either cooling water or cooling
air.
2. That hot vapor is routed through a condenser where it is cooled and condensed into a liquid by
flowing through a coil or tubes with cool water or cool air flowing across the coil or tubes. This is
where the circulating refrigerant
rejects heat from the system and
the rejected heat is carried away by
either the water or the air
(whichever may be the case).
1. Compressor
a. The job of the compressor is to suck vapour
from the evaporator and force it into the
condenser. The most common type is the
piston compressor, but other types have won
acceptance, e.g. centrifugal scroll and screw
compressors. The piston compressor covers a
very large capacity range, right from small
single cylinder modeIs for household
refrigerators up to 8 to 12 cylinder modeIs
with a large swept volume for industrial
applications. In the smallest applications the
hermetic compressor is used, where
compressor and motor are built together as
a complete hermetic unit. For medium sized
plants one of the most common compressors
is the larger sizes of hermetic compressors in
either piston or scroll versions. The
applications are both air conditioning,
general commercial refrigeration and chillers. For larger plants the most common is
the semihermetic compressor. The advantage here is that shaft glands can be
avoided; these are very difficult to replace when they begin to leak. However, the
design cannot be used on ammonia plants since this refrigerant attacks motor
windings. Still larger HFC compressors, and all ammonia compressors, are designed
as “open” compressors, i.e. with the motor outside the crankcase. Power
transmission can be direct to the crankshaft or through a V-belt drive. For quite
special applications there is the oil-free compressor. But lubrication of bearings and
cylinder walls with oil is normally always necessary. On large refrigeration
compressors oil is circulated by an oil pump.
2. Condenser
a. The purpose of the condenser is to remove the amount of heat that is equal to the
sum of the heat absorbed in the evaporator and the heat produced by compression.
There are many different kinds of condenser.
b. Shell and tube condenser. This type of condenser is used in applications where
sufficient cooling water is available. It consists of a horizontal cylinder with welded-
on flat end caps, which support the cooling tubes. End covers are bolted to the end
plates. The refrigerant condensate flows through the cylinder, the cooling water
through the tubes. The end covers are divided into sections by ribs. The sections act
as reversing chambers for the water so that it circulates several times through the
condenser. As a rule, the water becomes heated 5-10 °C when it has passed through
a condenser.
c. If it is desirable or necessary to cut down on the amount of water an evaporating
condenser can be used instead. This type of condenser consists of a housing in
which there is a condensing coil, water distribution tubes, deflection plates and
fans. The warm refrigerant vapour is led to the top of the condensing coil after
which it condenses and runs from the bottom of the coil as liquid.
Evaporating Condenser
3. Expansion Valve
a. The main purpose of the expansion valve is to ensure a sufficient pressure
differential between the high and low pressure sides of the plant. The simplest way
of doing this is to use a capillary tube inserted between the condenser and
evaporator. A regulating valve must be used for this process, the most usual being
the thermostatic expansion valve, which consists of a valve housing, capillary tube
and a bulb. The valve housing is fitted in the liquid line and the bulb is fitted on the
evaporator outlet.
4.
Evaporator
a. Evaporator acts as a heat conductor between product and refrigerant. It absorbs the
heat from the load in the refrigerated space.
Qa = T1( S1-S4)
Qr = T2(S2-S3)
= T2(S1-S4)
W = Qa- Qr
=T1(S1-S4)-T2(S1-S4)
=(T1-T2)(S1-S4)
W (T 1−T 2)(S 1−S 4)
E= Q = T 1(S 1−S 4)
(T 1−T 2)
E=
T1
Where:
Qa=T1(S1-S4)
Qr =T2(S2-S3)
=T2(S1-S4)
W = Qr-Qa
=T2(S1-S4)-T1(S1-S4)
=(T2-T1)(S1-S4)
Qa T 1(S 1−S 4) T1
COP = = =
W (T 2−T 1)(S 1−S 4) T 2−T 1
Where
Exercise Problem:
1. A certain refrigeration system maintains the cold room at -18C and can reject heat to the
atmosphere at 35C. If the refrigerating capacity is 100 Kw,
a. What is the COP of the system of refrigeration?
b. Determine the performance factor
c. What is the UA value in KW/K at ∆T= 5K?
2. A refrigerating system operates on the reversed Carnot Cycle. The higher temperature of
the refrigerant in the system is 120F and the lower is 10F. The capacity is 20 tons. Neglect
losses. Determine:
a. Coefficient of Performance
b. Heat Rejected from the system in BTU/min
c. Net work in BTU/min
d. Horsepower
3. A refrigeration system operates on the reversed Carnot cycle. The minimum and maximum
temperatures are -25C and 72C respectively. If the heat rejected at the condenser is
6000Kj/min, draw the TS diagram and find,
a. The power input required
b. Tons of refrigeration developed
WET COMPRESSION
saturated vapor and thus should be free from liquid such is not the actual case. During
compression, the droplets of liquid are vaporized by an internal heat transfer process which
requires a finite amount of time. High speed compressors are susceptible to damage by liquid
because of the short time available for heat transfer. In a compressor that has a rotative speed
of 30r/s, for example, the compression takes place in 1/60s. At the end of compression, point 2
on the saturated vapor line represents only average conditions of a mixture of superheated
vapor and liquid. Another possible danger of wet compression is that droplets of liquid may
wash the lubricating oil from the walls of the cylinder, accelerating wear. Because of this
disadvantages, dry compression, which takes place with no droplets of liquid present, is
preferable to wet compression. If the refrigerant entering the compressor is saturated vapor, as
in figure, the compression from point 1 to 2 is called dry compression .
DRY
COMPRESSION
With dry compression the cycle loses the rectangular shape of the Carnot cycle. Compression of
a dry vapor results is a temperature at point 2 which is higher than the condensing
temperature. The refrigerant therefore leaves the compressor superheated. The area of the
cycle which is above the condensing temperature is sometimes called the superheat horn. On
the temperature entropy diagram it represents the additional work required for dry
compression.
refrigerant flows at constant pressure through the two heat exchangers (evaporator and
condenser)
Sample Problem:
A R-12 simple saturated refrigerating cycle operates at an evaporating temperature of -10C and
a condensing temperature of 40C. Show the effects of increasing the vaporizing temperature to
5C.
Sample Problem:
A simple saturated refrigerating cycle using R-12 as the refrigerant, operates at a condensing
temperature of 40C and an evaporating temperature of -10C. Show the effects of increasing the
condensing temperature to 50C.
SAMPLE PROBLEM:
A simple saturated refrigerating cycle for R-12 system operates at an evaporating
temperature of -5C and a condensing temperature of 40C. Show the effects of
superheating the suction vapor from -5C to 15C.
Sample Problem:
A simple saturated refrigerating cycle using R-12 as the refrigerant operates at an evaporating
temperature of -5C and a condensing temperature of 40C. Show the effects of subcooling from
40C to 30C before reaching the expansion valve.