5-Bo-Control Unit PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

BO

S LOA 24
N
SIEME

see pag
e BO.9
Control unit
BRAHMA................................BO.2

CEM ECEE..............................BO.3

DANFOSS...............................BO.5
> DANFOSS
DUNGS...................................BO.6 Control unit

ELESTA..................................BO.6
see page BO.6
HONEYWELL...........................BO.7

LANDIS & GYR - STAEFA -


SIEMENS.........................................BO.9

MAY & CHRISTE.....................BO.15

PACTROL................................BO.15

RIELLO...................................BO.16

RV.........................................BO.17

SATRONIC..............................BO.17

SIT.........................................BO.21

Insulation transformer.............BO.21

Micro ammeter.......................BO.21

Connector .............................BO.22

Ignition spark detector.............BO.24

RETURN
SUMMARY
Control unit
BO return to the
retour of
beginning sommaire
the chapter

BRAHMA CONTROL BOX GAS type


FUEL type
Control unit

1 2 3
Type Pre Purge Safety Time Detection Mark Ref
Fuel burners compatible with a fuel flow less than 30 kg/hour. AT5 15 5 Io 1 504031
Type Pre Purge Safety Time Detection Ref AT5/TR1 15 10 Io 1 504030
Characteristic : 1 firing rate CM11 20 10 Io 2 504036
G33/03 15 10 Cell 504006
Characteristic : 1 firing rate
CM11F 15 5 Io 2 504050
G22/03 only one 15 10 Cell 504019 Characteristic : BPS
G22/09 only CM31 30 10 - 2 504039
one *
10 10 Cell 504023
Characteristic : 2 firing rates
CM31 30 5 - 2 504040
GF2/03 only one 15 5 Cell 504018 Characteristic : FRISQUET
GF3/03 only one 20 5 Cell 504004 CM31 15 5 Io 2 40030
Characteristic : for FERROLI
Characteristic : SEET
FR1 10 10 Cell 504044
Characteristic : for BALTUR CM31F 10 5 - 1 504005
OR3/B 20 5 Cell 431131 CM32 30 15 lo 2 504002
TEC3 10 10 Cell 431260 CM32 20 10 Io 2 504037
Characteristic : for ELCO
see Characteristic : SLCF
ER1 10 5 Cell
402023 CM32 5 5 - 2 504038
see
ER1H 15 5 Cell
402023 CM32 30 10 - 2 504051
** replaces models G22/05, G22/06 and G22/07 Characteristic : SLCF
CM32 - - - 2 504052
NOTE : CM 191.1 - - Io 1 504003
CM191.2/T1.5 15 10 Io 1 504049
Application Ref
ECOFLAM - FRANCO BELGE - FBR - THERMITAL
see CM391.2 15 5 lo 1 504034
504006
JOANNES - BALTUR - BIASI - FINTERM - THERMOMATIC - CGA CM391.2 * 15 10 Io 1 504035
FRANCO BELGE - ECOFLAM - DREIZLER - CHAUFFAGE Characteristic : GAZ INDUSTRIE gas relay 20s
FRANÇAIS - IDÉAL CLIMA - JUHATHERM - TERMONAFTA - 504019
MAZECO - SLCF - SANT ANDRÉA - BLOWTHERM - THERMOMEC DM 32 - - - - 504054
BALTUR - HS FRANCE- FIM - CTC - THERMOMATIC - RADIANT 1 504027
ECOFLAM - FRANCO BELGE - FONDITAL - PORCHER - CTC - CGA 504023 M300/02 30 2 Io/UV
JOANNES - THERMOMEC - FINTERM - THERMOMATIC -
504018
MF2/02 30 2 Io/UV 1 504033
DREIZLER - JUHATHERM - TERMONAFTA -BLOWTHERM
SM11 1.5 5 Io 2 504024
FER-FERROLI 504044
BALTUR 431131 SM152.2 30 10 lo 1 504001
BALTUR 431260 Characteristic : EMAT
SM191.2 20 10 Io 1 504048
Characteristic : CHAFFOTEAUX
CELL SM192.2 - - - 1 504053
SR3/TR01 30 3 Io/UV 1 504029
SR3/02 30 3 Io 1 504028
Characteristic : SLCF
1 2 3 See
Description Mark Ref SR3/TR 30 3 - 1 504029
FC7/R side shot 1 504207 SR3/TR15 15 3 Io/UV 1 504026
FC8/R frontal shot 2 504210 Characteristic : COUSSEMENT
TEC3 blue frontal and side shot 3 431259 SR3V 20 3 Io 1 504047
FC13 red frontal and side shot 3 431141 TM11-
15 10 Io - 504042
FC13AL ELCO pluggable - 402002 37059010
TM31-
37065010
15 10 Io - 504043
VE3-2/05 30 2 Io 1 504025
BASE
Characteristic : FRISQUET
XM11F 15 5 Io 2 40054
Characteristic : ELCO
EM41
Description Ref 37201031
30 3 Io 3 402010
2
G22 - GF2 - G22Z 504015
* Hydromotrix
BO
Control unit
return to the
beginning of the chapter

NOTE : Type Cell Pre Purge


Pre Post- Safety
Ref
Application Ref Ignition Ignition Time
Characteristic : 220V

Control unit
JOANNES - FINTERM 504031
EMAT 504036 MA 610-1 8205 10“ 10“ 6“ 10“ 501020
Characteristic : 220V replaced by MA 610
GEMINOX - PENSOTTI 504050
EMAT - BPS - WESPER 504039 MA 710 8205 - - 6“ 10“ 501020
Characteristic : Mono 110/220V
EMAT- ACCORRONI - NALSON - WESPER 504040
EMAT- CHAUFFAGE FRANÇAIS 504037 MA 800 8205 - - - 10“ 501040
AERMAX- APEN GROUP - GENERFEU - SOLYGAZ - THERMOVUR Characteristic : Tri 220/380V
CHAUFFAGE FRANÇAIS 504038 MA 803 8205 - - - 10“ 501050
AERMAX 504051 Characteristic : Mono 220V
ABIG - PENSOTTI - IMMERGAS 504049 MA 810 8205 - - - 10“ 501060
EMAT - BALTUR FRISQUET - CHAUFFAGE FRANÇAIS 504035 Characteristic : Replaced by MA610
EMAT 504048 MA 910 8205 10“ 10“ - 10“ 501020
CHAUFFAGE FRANÇAIS 504029 Characteristic :
MA 152.01 8205 24“ 24“ 18“ 5“/8“ on request
CHAUFFAGE FRANÇAIS - ACCORRONI - WESPER 504026
JOANNES 504042
JOANNES 504043
FRISQUET 504046 REPLACEMENT INDEX
FRANCO BELGE-JOANNES-MAZECO-ECOFLAM - FINTERM OLD BOX NEX MODEL Notes
CHAUFFAGE FRANÇAIS 504027
MA 22 MA 26 BASE without replacement
WESPER-ACCORRONI-EMAT-JOANNES - FINTERM 504033 MA 25 MA 26 Cell Replaced by 8206
UNIGAS - WESPER - ACCORRONI - BALTUR - ECOFLAM - EMAT-
EUROWARM - FRANCO BELGE - AERMAX - APEN GROUP MA 86-02 MA 86-05 BASE without replacement
GENERFEU - SOLYGAS - THERMOVUR - CGA - COLLARD MA 87-02 MA 86-05 Cell without replacement
504028
TROLART - PORCHER - LAMBORGHINI - SANT ANDRÉA
ECOFLAM-JOANNES-BALTUR - PORCHER - CHAUFFAGE
FRANÇAIS 504025
20 type
CELL

1 2
Description Mark Ref Pull out equipment. Use with Fuel-oil burner
UV 1 Ø22 mm 1 504218 Type Cell Pre Purge
Pre Post- Safety
Ref
Ignition Ignition Time
FC11 Ø8 mm frontal shot 2 504215
Characteristic : 2 firing rates
MA 23 8208 15“ 12“ 2“ 10“ 501360
BASE Characteristic : replaced by MA 26
MA 25 8208 15“ 15“ 2“ 10“
Characteristic : Cell 8210/8211
MA 26 8206 10“ 10“ 5“ 10“ 501300
MA 28 8206 - - - 10“ 501310
MA 29 8206 10“ 10“ - 10“ 501320
Description Ref
for MF2 504013
for AT5 / TR-CM391 504014 PROTECTOBLOC type
for AT5 / SR302 / M300 / VE3-2 504016
for SR3 / TR / CM191 504017

CEM ECEE FUEL CONTROL UNIT


OLD FUEL MODEL
Pull out equipment. Use with CEM motor and protectobloc transformer
Pre Post- Safety
Type Cell Pre Purge Ref
Ignition Ignition Time
Characteristic : motor 90W
MA 72 8205 5“ 5“ - 10“ 501330
Characteristic : motor 150W
Fuel burners compatible with a fuel flow less than 30 kg/hour. MA 73 8205 5“ 5“ - 10“ 501340
Characteristic :
Pre Post- Safety
Type Cell Pre Purge
Ignition Ignition Time
Ref MA 52 8209 12/7“ 2“ 2“ 10“ 501375
Characteristic :
Characteristic : 2 firing rates 220V
MA 310-1 8205 30“ 30“ 20“ 5“ or 10“ 501100
MA 53 8207 10“ 10“ - 10“ 501374
Characteristic : replaced by MA 86-05
Characteristic : 2 firing rates 380V
MA 310-1 8205 30“ 30“ 20“ 5“ or 10“ 501099
MA 86-02 8212 7“ 10“ - 10“ 501391
Characteristic : replaced by MA 510-1
MA 86-04 8212 7“ 5“ 1“ 10“ 501391
Characteristic :
MA 410-1 8205 30“ 5“ 15“ 5“ or 10“ 501010
Characteristic : 220V
MA 86-05B 8212 5/7“ 5/7“ 0,5“ 10“ 501391
Characteristic :
MA 510-1 8205 30“ 30“ 15“ 5“ or 10“ 501010
Characteristic : 380V
MA 86-11 8212 5/7“ 5/7“ 0,5“ 10“ 501392
Characteristic : replaced by MA 86-05
MA 510-1 8205 30“ 30“ 15“ 5“ or 10“ 501009 MA 87-02 8212 - - 12“ 10“ 501391 3
Control unit
BO return to the
retour of
beginning sommaire
the chapter

CEM ECEE FUEL CONTROL UNIT CEM ECEE CONTROL UNIT


41/43/45/46/ 55 type GAS FLAME
Control unit

Pull out equipment - Transistor amplifier detects gas flame with a ionization
electrode.
Pre Post- Safety
Type Cell Pre Purge Ref
Ignition Ignition Time FEATURES :
Characteristic : 2 firing rates  Monophased voltage : 220V +10% +15% 50Hz
MA 41 8212 15“ 15“ 40“ 5“ 501370  Contact of flame relay : 220V 2A
MA 43 8212 10“ 10“ 15“ 10“ 501350  Current of flame ensuring a correct operation: between 5 and 120
Characteristic : Security on stray light micro amps
 Consumption : 3VA
MA 45 8212 10“ 10“ 3“ 10“ 501380  Ambiant temperature : 50°C maxi
MA 46 8212 10“ 10“ 3“ 10“ 501385  Response time of the flame relay : lower than 0,5 second with the
Characteristic :- appearance and the extinction of the flame.
MA 55 8209 10“ 10“ 3“ 10“ 501376
Characteristic : Used with preheater Description Ref
MA 55H 8209 10“ 10“ 3“ 10“ 501377 AE 25 ionization detector 501900
Characteristic : maintains the tension even if the klixon heater
breaks
8207/
MA 55R 10“ 10“ 3“ 10“ 501378
8209 GA / GB / GE type
Characteristic : ionization
MA 55E - 10“ 10“ 3“ 10“ 501379
Characteristic : Remote control
8207/
MA 55D
8209
10“ 10“ 3“ 10“ 501373

CELL
Pre Post- Safety
Type Pre Purge Ref
Ignition Ignition Time
Characteristic : Blown air burner
1 2 3 5 GA 2410 30“ - - 5“ 501615
Characteristic : atmospheric burner
GA 2510 5“/10“ - - 5“ 501620
Characteristic : Used absolutely with an air pressure switch
4 6 7 Relay GB 650 replaces completely GE 650 subject to short
circuit of the terminals 12 and 13 which do not exist on the GE
Description Mark Ref 650.
8205 for MA 800/72/73/152-01 types (supplied
without flange)
1 501220 GB 650 0“ - - 4“ 501656
Characteristic : ionization sensor
8206 use with MA 26/28/29 (side and frontal shots) 2 501260
8207 use with MA 55R - no flange 3 501261 GB 650.1 0“ - - 4“ 501622
8208 use with MA 23 and 25 5 501290 Characteristic : blown air burner
8209 use with MA 23 / 25 / 52 / 55 4 501500 GE 143 20“ - - 5“ 501600
8210 use with MA 26/28/29 (side Ø17 shots) 2 see 501260 Characteristic : atmospheric burner
8211 use with MA 26/28/29 (side Ø14 shots) 7 501510 GE 145 10“ - - 5“ 501605
8212 use with MA 86/ 41/43/45/46 6 501520 Characteristic : not recyclic blown air burner
8212 RR same model extended for GIANOLA 6 501530 GE 218.23-03M 30“ - - 3“ 501625
GE 218.02
Characteristic : atmospheric burner
BASE GE 230.01 3“ 1“ 4“ 4“ 501644
Characteristic : atmospheric burner
semi permanent pilot flame
GE 232-01 20“ 1“ - 4,5“ 501645
Characteristic : monotube blown air burner
1 2 3 GE 236-01 60“ 3“ 3“ 2“ 501650
Description Mark Ref Characteristic : -
S801 for MA 800/803/810 1 501200 GE 296 - - - - 501601
S802 for MA 310 and gas box GA 2140/2510 1 501201 Characteristic : not recyclic
SP06 for MA 152.01 - GE 232/236 3 501202 GE 633 3“ - 3“ - 501630
S20 for all MA 20 types 2 501250 Characteristic : can function with shunt on air manostat
S401 for MA 40 and 55 types 2 501252 GE 650 10“ - - 8“ 501656
S72 for MA 72 2 501255 Characteristic : 2 firing rates
S73 for MA 73 - 501256 GE 733 30“ - 2“ 2,5“ 501631
S407 for MA 52 2 501257 GE 735 30“ - 40“ 4,5“ 501632
S861 for MA 86.11 2 501259
4 S803 for MA 803 exclusively 1 501410
BO
Control unit
return to the
beginning of the chapter

GU (UV) type DANFOSS CONTROL BOX


REPLACEMENT INDEX

Control unit
REPLACEMENT kit INCLUDES :
Superior level with 12 terminals Adapter BHA 11/12
Ref 505410

Control and security equipment with flame monitoring by UV sensitive cell.


Seat with 9 terminals
Pre Post-
Type Pre Purge Safety Time Ref
Ignition Ignition
Characteristic : ignition spark control
GU 336-01 60“ - 2“ 4“ 501655 OLD RELAY ADAPTATION KIT COMPOSITION
 DANFOSS  New DANFOSS  New Ref
Type  Adapter 
Reference   Relay  Reference  Cell 
BHO 03 3018/3118 BHO64.1 7037(1) BHA 7020 LD7020 505053
(1) Landis & Gyr switch position
Important : Always place cell with control box

CELL
BHO 62/64/72/74 type

1 2 3
Description Mark Ref
8300 UV Detector 1 501690
8301 UV Detector industrial model 2 501691
SYLVANIA UV P607.88 - Ø22 mm - 4 pin plugs 3 502312 Pre Post- Safety
Type Pre Purge Ref
Ignition Ignition Time
Characteristic : Landis & Gyr switch position
Replaced by 505154 after exhaustion of stocks
see
BHO 62 - 7034/7234 13“ 13“ 15“ 10“ 505156
Characteristic : Landis & Gyr switch position
BASE BHO 64.1 - 7037 6“ 6“ 20“ 10“ see 505157
Characteristic : Danfoss switch position
BHO 62D-7035/7235 13“ 13“ 15“ 10“ see 505156
Characteristic : Landis & Gyr switch position
BHO 64 - 7036/7236 13“ 13“ 15“ 10“ see 505156
Characteristic : electronic box to diagnostic blinking light
1 2 3 replaces BHO64
Description Mark Ref BHO 72.10 57H6102 13“ 15“ 15“ 10“ 505156
SP06 for GE 218/230/232/236/650/GB650/ Characteristic : electronic box to diagnostic blinking light
GU330/336 - MA 152.01
1 501202 replaces BHO64.1
S406 for GE 633 2 501203 BHO 72.11 57H6103 16“ 20“ 20“ 10“ 505157
Characteristic : electronic box to diagnostic blinking light
S402 for GE 143 / 145 3 501204 replaces BHO64A
S802 for GA 2H40/ 2510 /810 3 501201 BHO 73.10 57H6104 13“ 2“ 15“ 10“ 505158
Characteristic : electronic box to diagnostic blinking light
S412 for GE 733 / 735 2 501205 equivalent LMO44
BHO 74.10 57H6105 25“ 2“ 5“ 5“ 505159

CELL
SPARK DETECTOR
Linked to a flame detector circuit that uses ionization
electrode, the system detects a flame signaling a spark.
It replaces the UV cell for ignition spark detection when
the use is compromized.
Description Ref
Description Ref LD (6 LUX) 057H 7079 - with length 780 mm 505260
DA 51 pour GE 633/ 733 501660 LD (6 LUX) lg 65,5mm 057H 7079/7279 - with length
505263
780 mm
SEE THE INSTALLATION DRAFT AT THE END OF THIS CHAPTER LDS (2 LUX) 057H 7085 - with length 500 mm 505261
LDS longue 057H 7091 for BENTONE - DEVILLE - HS FRANCE 505262 5
Control unit
BO return to the
retour of
beginning sommaire
the chapter

DANFOSS CONTROL UNIT DUNGS CONTROL BOX


VDK / VPS / W-F
Control unit

ADAPTER

Description Ref 1 2 3
ADAPTER ONLY BHA for BHO 11/12 transformation 505410

BASE
4
Pre Post- Safety
Type Pre Purge Mark Ref
Ignition Ignition Time
VDK200A 02
type
- - - - 1 509001
Description Ref
VPS504 02 type - - - - 2 509003
Base 057H 7010 - 057H 7011 for BHO 61/62/62D/64.1 505401 VPS504 04 type - - - - 3 509004
W-FM20 V3.02
502
- - - 2/5 4 407103
FRA / FRU type
Flame control relay used for flame control on semi-automatic
installations .

ELESTA CONTROL BOX ACCESSORY


FFW type for FRA / FRU replace-
ment
Cell of replacement

Description Ref
8209 Fuel oil flame control cell /all types of control boxes 501500
For fuel or gas, atmospheric or ventilated burner.
For semi-automatic installation.
 Ionization monitoring or cell UVZ or infrared IRD 1020 detector
Description Ref
FFW FUEL - GAS 507320
HONEYWELL CONTROL BOX
BASE 507300
ZT 870 Transformer 805913
S4565 GAS type
AZ5 Pilot burner 708790

DUNGS CONTROL BOX


Pre Pre Post- Safety
DGAI 19 type Type
Purge Ignition Ignition Time
Ref
Relay used by GEMINOX
S4565 A 1001 - -- - 508015
S4565 A 2027 - - - - 508003
Relay used by DE DIETRICH - RADIANT
S4565 A 2019 - - - - 508026
Relay used by DE DIETRICH - ZAEGEL HELD- ST ROCH -COUVIN
S4565 A 2035 - - - - 508050
Relay used by CHAFFOTEAUX - ZAEGEL HELD
DGAI 19.2 control box for atmospheric gas burner, 220VA - 600 Kw, ionization S4565 A 2050 - - - 5“ 508021
electrode detection. Relay used by ACV

Type Pre Purge


Pre Post- Safety Characte-
Ref
S4565 A 2068 - - - - 508053
Ignition Ignition Time ristic S4565 AD 2080 - - - - 508079
DGAI 19.2 4“ 5“ 4“ 13“/8“ - 509000 Relay used by ROCA
6 DGAI 69 50“ 1“ 0“ - - 509005 S4565 A 2076 - - - - 508082
BO
Control unit
return to the
beginning of the chapter

S4565 GAS type (contd...) S4565 GAS (contd...)


Pre Post- Safety
Type Pre Purge Ref

Control unit
Ignition Ignition Time
Relay used by DE DIETRICH - OERTLI - ROCA
S4565 BF 1112 - - - - 508043
S4565 BF 1161 - - - - 508071
Pre Pre Post- Safety Relay used by FERROLI - SAUNIER DUVAL
Type Ref S4565 CD 1005 - - - 10“ 508014
Purge Ignition Ignition Time
Relay used by UNICAL
Relay used by RIELLO - BERETTA S4565 CD 1021 - - - - 508076
S4565 B 2066 replace S4565 DF 1050 - - - - 508078
S4565 B 2017
- - - - 404049 Relay used by BIASI - MANAUT - RIELLO - ALLIANCE
S4565 DD 1003 - - - - 508081
Relay used by RIELLO - SIME - CALORTECNICA Relay used by UNICAL - APEN GROUP
S4565 CF 1052 - - - - 508063 S4565 DM 1029 - - - - 508064
Relay used by GAS ICI - SAVIO
Relay used by RIELLO S4565 CF 1003 - - - - 508045
Relay used by RIELLO - DOMUS- HERMAN
S4565 RF 1000 - - - - 508077 S4565 CF 1045 - - - - 508001
Relay used by DE DIETRICH - CICH - IDEAL STANDARD - APEN Relay used by DEVILLE-ZAEGEL HELD- ST ROCH COUVIN
GROUP CALORTECNICA - THERMITAL S4565 CF 1060 - - - - 508046
Relay used by BALTUR - HERMANN
S4565 C 1025 - - - - 508058 S4565 DD 1045 - - - 10“ 431171
Relay used by VIESSMANN Relay used by BERETTA
S4565 QM 1012 - - - - 508065
S4565 C 1132 - - - - 508075
Relay used by ACTI - SOLARONICS-GUILLOT-GAZ INDUSTRIE
S4560 / S4561 /S4562 /S4570 GAS type
S4565 D 1007 - - - - 508047
Relay used by GEMINOX
S4565 AD 2027 - - - - 508070
S4565 AD 2072 - - - - 508004
Pre Post- Safety
Type Pre Purge Ref
S4565 BM 1080 - - - - 508072 Ignition Ignition Time
S4565 DM 1045 Relay used by ACV - INOX G-GE
replaced by S4565 DM - - - - 508048 S4560 A 1024 - 4“ 2,5“ 5“ 508019
1086
Relay used by FRANCO BELGE - BONGIOANNI
Relay used by RADIANT SPACE RAY S4560 A 1032 - 4“ 2,5“ 10“ 508035
S4565 P 2024 - - - - 508008 Relay used by ROCA
S4560 B 1006 - 4“ 2,5“ 10“ 508057
Relay used by FERROLI
Relay used by NESTOR MARTIN - GUILLOT - ATLANTIC
S4565 AD 2056 - - - - 508016 S4560 B 1022 - 4“ 2,5“ 5“ 508028
Relay used by BUREX
S4565 CD 2029 - - - 10“ 508002
S4560 B 1048 - - - - 508009
Relay used by SIME - UNICAL - SAUNIER DUVAL (THELIA 30E) Relay used by SOLARONICS - GUILLOT
S4565 AF 1007 - - - - 508054 S4560 B 1063 - 4“ 10“ 25“ 508036
-
Relay used by CHAUFFAGE FRANÇAIS
S4560 C 1004 - - - - 508062
S4565 AF 1064 - - - - 508060 Characteristic : AIRCALO
Relay used by FRANCO BELGE S4560 C 1012 8“ 4“ - 10“ 508037
Characteristic : DEVILLE
S4565 BD 2021 - - - - 508073 S4560 C 1038 8“ 4“ -- 5“ 508024
Relay used by DE DIETRICH - IDEAL CLIMA Characteristic : UNICAL - ACCORRONI - AO SMITH - ATI -
BOSCHETTI - ICI
S4565 BF 1005 - - - - 508052 S4560 C 1053 24“ 4“ - 10“ 508038
Relay used by DE DIETRICH Characteristic : burner with fan GEMINOX ground boiler
w/burner (replaces S4560 D 1028)
S4565 BF 1025 - - - - 508017 S4560 D 1077 10“ 35“ - 5“ 508020
Characteristic : ACTI
S4565 SD 2005 - - - - 508069
S4560 D 1069 24“ 4“ - 25“ 508032
Relay used by SOLARONICS Characteristic : ACTI
S4565 BF 1047 - - - - 508051 Characteristic : ACTI - SOLARONICS - INTERCAL

Relay used by THERMITAL - VIESMANN


S4560 D 1135 24“ 4“ - 25“ 508039
Characteristic : CHAPPEE
S4565 BF 1054 - - - - 508074 S4560 D 1143 16“ 4“ - 25“ 508034
Relay used by IDEAL CLIMA- AO SMITH - CHAPPEE -IDEAL Characteristic : -
STANDARD- THERMITAL S4560 D 1150 - - - - 508059
S4565 BF 1062 - - - - 508029 Characteristic : GEMINOX
S4560 M 1036 - - - - 508025 7
Control unit
BO return to the
retour of
beginning sommaire
the chapter

HONEYWELL CONTROL UNIT PROGRAMMER


S4560/S4561/S4562/S4570 GAS type (contd...)
Control unit

Universal programmer pluggable to Q 7800 base


APAVE D 15/97 -43.2 approved
Pre Post- Safety Description Ref
Type Pre Purge Ref
Ignition Ignition Time
EC7850A1072 - 230Vac - post purge : 2s 508227
Characteristic : NESTOR MARTIN
S4560 CB 1022 - - - - 508012
Characteristic : UNICAL - SANT ANDREA - FER - FERROLI BASE
S4561 A 1007 - - - - 508056
Characteristic : FER - FERROLI
S4561 A 1015 - - - - 508040
Characteristic : FER - FERROLI - VAILLANT
S4561 B 1013 - - - - 508042 For 7800 type
Characteristic : IDEAL CLIMA - BALTUR
S4561 B 1005 - - - - 508041 Description Ref
Characteristic : CHAUFFE FRANÇAIS - FERROLI Q7800A1005 plastic version 508208
S4561 B 1039 - - - - 508007
Characteristic : WOLF
S4562 A 1014 - - - - 508013 PRE-VENTILATION CARD
Characteristic : FERROLI
S4562 A 1055 - - - - 508005
S4562 C 1069 - - - - 508006
Old Ref Range of purge timer
450002
S4562 DM 1006 - - - - New Description Ref
40503
Characteristic : AUER ST7800A1013 - 7s 508224
S4570 AS 1012 - - - - 508030 ST7800A1039 - 30s 508225
Characteristic : -
S4570 AS 1028 - - - - 508049
Characteristic : DE DIETRICH AMPLIFIER
S4570 BS 1002 - 17“ 1“ 10“ 508011
S4570 BS 1036 - 17“ 3“ 10“ 508031
S4570 LS 1026 - - - - 508066
Characteristic : SOLARONICS - GUILLOT
S4570 BS 1010 - - - - 508027 For UV : R7824/47/49/61/86 - Pluggable - additional modules
Characteristic : FRANCO BELGE
S4570 BS 1028 - - - - 508067 Description Ref
Characteristic : SOLARONICS - GUILLOT R7849A1023 standard - 2s - for detector C7027/35/44 508219
S4570 LS 1000 30“ 35“ 1“ 5“ 508033
Characteristic : REZNOR-GAZ INDUSTRIE-SOLARONICS
R7849A1034 standard - 2s - for detector C7027/35/44 508228
S4570 LS 1059 15“ - - 5“ 454064 R7861A1026 Auto-verifying - 2s - for detector C7061
APAVE D 15/97 -43.2 approved
508220
CONTROL and FLAME SECURITY
for HONEYWELL INDUSTRIAL BURNERS
CELL
For flame electrode : R7847A/B - Pluggable - additional modules

2 Description Ref
1
R7847A1033 standard - 2s - for detector C7012A/G 508217
R7847B1031 Auto-verifying - 2s - electrodes detector
APAVE D 15/97 -43.2 approved
508218
3

Description Mark Ref


DISPLAY
Cell UV C7027A1049 Monoblock tube frontal shot IP677
Fixing 1/2“ NPT - Cable 2,4m - Temperature 1 508202
-18 to +102°C
Cell UV C7027A1056 Monoblock tube frontal shot IP677
Fixing 1/2“ NPT - Cable 2,4m - Temperature 1 508203
-18 to +102°C
Cell UV C7027A1064 Monoblock tube frontal shot IP677 Pluggable with EC/RM7800 type - Communication and remote reset functions
Fixing 1/2“ NPT - Cable 7m - Temperature 1 508204 included
-18 to +102°C
Cell UV C7027A1023 Monoblock tube frontal shot IP677 Description Ref
Fixing 1“ NPT - Cable 1,8m - Temperature 2 508205
-18 to +121°C S7800A1035 508221
8 Cell UV C7061A1020-ST001 IP677 - Temperature
3 508206
-40 to +80°C with amplifier lens
BO
Control unit
return to the
beginning of the chapter

MANUAL REMOTE RESET MODULE SEAL CONTROL PROGRAMMER

Control unit
Air pressure control -
Description Ref LED display

S7820A1007 only remote reset 508222 Description Ref


A4021A1002 230 Vac 508201
RELAY
BASE

Primary relay with reversing switch Description Ref

Description Ref ZL030001 Seal control base 508226


R4343D1041-ST005 Standard amplifier incorporated - Ioniza-
508209
tion 115/230Vac - 2 reversing switches : 4A cos ϕ 6,35 ADAPTER
R4343E1048-ST005 UV standard amplifier incorporated for
mini Cell C7027 or C7035 - 115/230Vac - 2 reversing switches : 508210
4A cos ϕ 6,35

Adapter 4-20mA for M9184 (internal connection)


Description Ref
Q7230A005 4 - 20mA 508207

Half automatical industrial relays - Universal relay- 115/230VAC Start auto


control for pluggable amplifier R72xx - 2 independant relays
Description Ref
R4348B1057 Output and LED meter contact rating 4-20MA
LANDIS & GYR STAEFA - SIEMENS FUEL
Gives an indication of flame current strength (measure not 508212 CONTROL BOX
security) IP54 APAVE D 15/95 -40.1 approved
R4348B1008 Standard model - No flame current jack socket
LOA type
IP54
508211

BASE
Pre Post- Safety
Type Pre Purge Ref
Ignition Ignition Time
Characteristic : Special VIESSMANN

Description Ref
LOA 14 171B2V - - - - 424004
Characteristic : alternative for LOA 22 + decrease voltage
Base box R4348 508200 security
LOA 24 13“ 13“ 0/13“ 10“ 502052
Characteristic : Will replace LOA 24 when no more available.
AMPLIFIER LMO 24 111A2
(1)(2) 16“ 15“ 10“ 10“ 502385
Characteristic : Special CHAPPEE - IDEAL STANDARD
LMO14 111A2 ou
B2 (1)(2) 16“ 15“ 10“ 10“ 502006
Characteristic : Special WEISHAUPT
1 2 LMO 82 3s gas
For UV : R7824/47/49/61/86 - Pluggable - additional modules 100C2WH (1)(2) - - - 5s fuel 407024
Description Mark Ref Characteristic : Special BUDERUS
LMO 54
R7323B1026 standard (U.V.) - 2s - for detector 200B2BU (1)(2) - - - 7s 420035
C7027/35/44 1 508216
Characteristic : Special VIESSMANN
R7323B1018 standard (U.V.) - 2s 1 508215 LMO 54 210B2V - - - - 424005
R7061A1016 Auto-verifying (U.V.) - 2s - for detector (1)(2)
C7061 APAVE D 15/86 -10.3 approved
2 508213
(1) Automatic failure detection box.
R7247A1005 Auto-verifying (U.V.) - 2s - for detector 3 blinking different colors signal a defect.
C7012E APAVE D 15/95 -40.1 approved
2 508214 (2) Use with QRB1 or QRC1.
No need to replace the base. 9
Control unit
BO return to the
retour of
beginning sommaire
the chapter

ADDITIONAL TECHNICAL OVERVIEW (contd...)


LANDIS & GYR STAEFA - SIEMENS FUEL LAL LOK 16
CONTROL BOX Box type
1.25 2.14 2.25 2.65 250A27
Control unit

LOA type (contd...) Programmable starter


Decrease voltage Protection
X
X
X
X
X
X
X
X
X
X
Remote control release X X X X X
Cell QRB X X X X -
Cell QRB X X X X -
Cell RAR - X X X X
 Contact 2 Ev X X X X X
Pre Post- Safety  Contact air flap X X X X X
Type Pre Purge Ref
Ignition Ignition Time
 Temperature adjustment or
Characteristic : decrease voltage protection X X X X X
boiler pressure
LOA 26  13“ 13“ 15“ 10“ 502049
Characteristic : 2 firing rates + 30 kg/h
LOA 44 25“ 25“ 5/8“ 5“ see 502383 LAE
NOTE :
type
Characteristic : Will replace LOA 24 when no more available. Adjustable preventilation from 8“ to 63“.
LMO 44 255A2 Total preventilation and post ventilation
(1)(2) 26“ 25“ 5“ 5“ 502383 cannot exceed 90“ (when Pre-purge = 8“,
Characteristic : Special BENTONE post-purge = 82“ etc...)
Adjustable security delay from 0“ to 9“
LMO 64 302A2B
(1)(2) - - - - 432022 Pre Post- Safety
Type Pre Purge Ref
Characteristic : voltage light - flame light Ignition Ignition Time

LOA 36 13“ 13“ 15“ 10“ 502048 LAE 1/1355 30“ 3“ -: 5“ 502172

((1) Automatic failure detection box. -


3 blinking different colors signal a defect.
(2) Use with QRB1 or QRC1.
FLAME DETECTOR
No need to replace the base Yellow flame detector box for fuel oil burner
flame control. Use with cell RAR7 and RAR8.
Use with program LEC1.

LAL ... /LOK type


Description Ref
LAE 10 502171

Cell
Pre Post- Safety
Type Pre Purge Ref 3 4
Ignition Ignition Time
1 2
Characteristic : 3 firing rates remote control release +
Air damper QRB1
LAL 1.25 22.5“ 27.5“/2.5“ 22,5“/5“ 5“ 502091 Description Mark Ref
Characteristic : 3 firing rates remote control release + QRB1A with cable L800mm for WEISHAUPT lg 65mm 1 407137
Air damper QRB1 + Monitoring detection by RAR (steam boiler) QRB1A with AMP II n°9 for WEISHAUPT lg 65mm 2 407144
or QRB1 QRB1B with AMP III for CHAPPEE - IS - BAXI
Cell lg 50mm- lg 190mm 2 401061
LAL 2.14 14“ 14“/2“ 10“/4“ 5“ 502092
LAL 2.65 67.5“ 27.5“/2.5“ 22.5“/5“ 5“ 502093
QRB1A with AMP III n°13 for WEISHAUPT lg 65mm 3 407143
QRB1A for LAI - LAB- LAC - LOA - and LAL1 Ø9 mm 4 502221
Characteristic : photo resistant or electric cell + air pressure
+ QRB1
LAL 2.25 27.5“ 27.5“/2.5“ 22,5“/5“ 5“ 502094
Characteristic : Detection by RAR 7 or RAR 6
LOK 16 250A27 27.5“ 27.5“/2.5“ 15“ 5“ 502056
5 6 7

ADDITIONAL TECHNICAL OVERVIEW


IMPORTANT : For telegestion, replace LAL by LOK 16. 8 9
In that case move the polarization pins.
Description Mark Ref
LAL LOK 16
Box type
250A27
QRB1B A148B70B - 502226
1.25 2.14 2.25 2.65
Intermittent functioning X X X X -
QRB1B high sensibility 5 502222
  Permanent functioning - - - - X
QRB1B wire 1,50 m 6 502224
QRC1 UV sensitive.
  Voltage 230V X X X X X
Use with boxes ref: LOA & LMO (except LOA 25 & LOA 28)
7 502235
  Box model M X X X X X
QRB1B specific CUENOD and ELCO 8 502223
  Contact MO = motor
X X X X X QRB1B 4MST with AMP II for KORTING 9 502225
10 (synchrone)
BO
Control unit
return to the
beginning of the chapter

CONTROL BOX TESTER


LANDIS & GYR - STAEFA - SIEMENS

Control unit
KF 8840 type
10 11 12
Description Mark Ref
QRB1B 4MST with AMP II for WEISHAUPT Lg 56 mm 10 407011
QRB1B with AMP III n°13 for WEISHAUPT Lg 65 mm 10 407043
QRB3 for LAI - LAB - LAL1 - LOA - LAC - LAE 11 502230
RAR7 selenium cell replaces RAR2 12 502260 The fixed adapter, located between the base and the box, indicates the activa-
tion program, and at the same time measures the voltage control through the
RAR8 selenium cell replaces RAR3 12 502300 pin plugs. There are 2 measuring sockets to control the flame signal and one
RAR9 Cell - 502261 simulation selector
Description Ref
KF 8840 TESTER 502199

BASE

1 2 3 LAI / LAB / RBQ REPLACEMENT INDEX


The adapters are a necessary tool when out- of -production security boxes
need to be replaced.
The new KITS, are easy to fix and avoid the replacement of the base ; they are
designed to keep the same height position.
When a replacement is needed, a wiring modification may be necessary :
5 4 the instructions are then provided.
Description Mark Ref OLD RELAY ADAPTATION KIT
AGK 86.10A27 for Weishaupt WG30 5 407086 Type New Relay Primary all Adapter
Cell Ref
AGK4 104.13450 for LAE 10 - LAI - LAB - LF1 - LFM with none
height 20 mm
1 502350
LAI 1/2/4 - LAB
AGK4 104.90250 for LAI - LAB - LF1 - LFM - 16.3 type 01
LOA 24 QRB1/3 KF 8819 - X 502062
height 27 mm
1 502351
AGK11 for LOA - LGA - LMO 4 502352 LAI 12 type 01 LOA 24 QRB1/3 KF 8826 - X
AGK85.22A27 for WEISHAUPT 4 502355 LAI 12.1 LOA 24 QRB1/3 KF 8826 - X
AGM410.490500 for LAL 3 502367
AGG4 104.1713 (AE) 2 502363
LAB 1 LOA 44 QRB1/3 KF 8819 - X 502063
AGM16 for LOK16 - 502354 LAB 15 / 15.1 LOA 44 QRB1/3 KF 8819 - X 502063
LAB 16.3 type 3 LOA 44 QRB1/3 KF 8819 X 502063
RBQ 31 / 34 LAL 1.25 QRB3 re-wire - - -

ADAPTER KF type RBQ 33 LAL 1.25 QRB3 re-wire - - -

Allows the replacement of old control boxes without re-wiring LAI - LAB LAI / LAB by LOA type REPLACEMENT KIT
- LAC LFA - LFB - LFi - LFM
Description Ref
KF 8810 in replacement of LAC 3 by LAL 502374
KF 8819 in replacement of LAI et LAB by LOA 502370
KF 8826 in replacement of LAL 12.1 by LOA 24
(MONARCH) QRB1 407300 LOA 21 & LOA 22 , have been stopped in january. 1997.
Those are replaced by ref: LOA 24 ,CE conform.
KF 8829 in replacement of LFI 5 by LGA 502377
Description for Replacement KIT Composition Ref
KF 8852 in replacement of LFI 7 by LGB 502378
LAI 1 / LAI2 / LAI 2.2/ LOA 24 + KF 8819
KF 8880 in replacement of LFM by LGB2
502360 KIT LAI
LAI 4 /LAB 16.3 type 01 no cell replacement
502062
((burner with fan)
KF 8862 in replacement of LFM by LB41 (atmospheric burner) 502381 KIT LAB
LAB 1/ LAB15 /15.1 LOA 44 + KF 8819
502063
LAB 16.3 type 03 no cell replacement
IMPORTANT : Fix these adapters between the new box and the old box
base 11
Control unit
BO return to the
retour of
beginning sommaire
the chapter

LANDIS & GYR STAEFA - SIEMENS FUEL MIXED LFE10 type


CONTROL BOX
Control unit

LAC 1/2/3 REPLACEMENT INDEX


The adapters are a necessary tool when out- of -production security boxes
need to be replaced.
The new KITS, are easy to fix and avoid the replacement of the base ; they are
Blue flame detector used for fuel or gas.
designed to keep the same height position.
Link with LEC program.
When a replacement is needed, a wiring modification may be necessary : the
instructions are then provided. Description Ref

Old box
ADAPTATION KIT LFE 10 502170
Replaced by Primary all Adapter
Characteristic : -
LAC 1.013 LAL 2.14 QRB1 - BASE
LAC 1.025 LAL 1.25 QRB1 -
LAC 1.035 LAL 1.25 QRB1 -
Characteristic : QRB1 & QRB3 used according to burner type.
LAC 1.125 LAL 2.65 QRB1/3 -
1 2
LAC 2.013 LAL 2.14 QRB1 - Description Mark Ref
LAC 2.025 LAL 1.25 QRB1 - AGG4 104.1713 (AE) 1 502364
LAC 2.035 LAL 1.25 QRB1 -
AGK4 104.13450 FOR LFE 10 2 502350
Characteristic : QRB1 & QRB3 used according to burner type.
LAC 2.125 LAL 2.65 QRB1/3 KF 8808
Characteristic : - RWA REPLACEMENT INDEX
LAC 3.013 LAL 2.14 QRB1 KF 8810 Old box Replaced by Cell
Characteristic : If there is any control connection to screw 8 or 14, replace RWA2   LEC1 NONE
the LAC3 with a LAL 2.25 type.
LAC 3.025 LAL 1.25 QRB1 KF 8810
Characteristic : If there is any control connection to screw 8 or 14, replace
the LAC3 with a LAL 2.25 type. LANDIS & GYR STAEFA - SIEMENS GAS
LAC 3.035 LAL 1.25 QRB1 KF 8810 CONTROL BOX
Characteristic : QRB1 & QRB3 used raccording to burner type.
LAC 3.125 LAL 2.65 QRB1/3 KF 8808
LFE type

RAQ / RAI / LAB10 REPLACEMENT


INDEX
OUT OF PRODUCTION boxes. Base re-wiring and a new cell are necessary
where you take a new box.
Pre- Pre- Post Safety
Type Ref
Old box Replaced by Cell Purge Ignition Ignition Time
RAQ 15.1   LAE 1/1 355 RAR 7/8/9
LFE 50 * - - - - 502001
NOTE :
RAQ 15.2   LAE 1/1 355 RAR 7/8/9 * Control box of flame that works with a LEC1 relay. The direction is done with a
RAQ 15.3   LAE 1/1 355 RAR 7/8/9 QRA50M (frontal shot) or QRA51M (side shot)
RAQ 10.1/2   LAE 10 RAR 7/8/9
RAI 20   LAE 10 RAR 7/8/9
RAI 15.1   LAE 1/1 355 RAR 7/8/9 LFI 7 / LFM 1 type
RAI 15.3d   LAE 1/1 355 RAR 7/8/9
RAQ 15.4d   LAE 1/1 355 RAR 7/8/9
LAB 10   LAE 10 RAR 7/8/9

LFI relay provides automatic activation and monitoring of blown air gas burner
(monotube 1 firing rate).
LANDIS & GYR STAEFA - SIEMENS MIXED LFM relay is used for automatic control and activation of gas burner (with 1 or
2 stages; with or without a fan).
CONTROL BOX Pre- Pre- Post Safety
Type Ref
Purge Ignition Ignition Time
MIXED LEC type
Scheduler for double monitoring with detector
Characteristic : instant steam generator
LFI 7-13 8“ 0,5“ 3“ 3“
LAE 10 or LFE 10. see
Characteristic : -
NOTE : replacement
LFI 7-33 30“ 0,5“ 3“ 3“
Adjustable preventilation from 8“ to 63“. index page
Characteristic : atmospheric burner
Total Preventilation time + post-ventilation BO.15
LFI 7-35 30“ 0,5“ 5“ 5“
can not exceed 90“ (when Preventilation = 8“, post-ventilation = 82“ etc...)
Characteristic : ignition spark control
Pre- Pre- Post- LFM 1-33F 30“ 0,5“ 3“ 3“
Type Safety Time Ref
Purge Ignition Ignition Characteristic : atmospheric burner
12 LEC 1/8 853 30“ 3“ - 5“ 502173 LFM 1-35 30“ 0,5“ 5“ 5“
BO
Control unit
return to the
beginning of the chapter

LFL type LGC 22 type

Control unit
 Pre  Post- Safety
Type  Pre Purge  Ref
Flame control by UV or ionization Ignition Ignition  Time
Characteristic : Box for wall unit gas boiler
 Post- Safety specific to BROTJE (270961)
Type  Pre Purge   Pre Ignition Ref
Ignition  Time
Characteristic : steam generator
 LGC 22 002C271 1,5“ - - 10“ 502180
 LFL 1.122 14“ 4“ 2“ 2“ 502107
Characteristic : -
 LFL 1.133 14“ 4“ 3“ 3“ 502004 LGK type
Characteristic : 2 ionization sensors possible
 LFL 1.148 14“ 2“ 4“ 4“ 502112
Characteristic : burner 1 or 2 tubes 3 firing rates
remote control release + air damper ionization or UV
 LFL 1.322 37,5“ 4“/2“ 2“/4“ 2“/4“ 502101
 LFL 1.335 37,5“ 5“/2,5“ 2,5“/5“ 2,5“/5“ 502102
Characteristic : burner 1 or 2 tubes 3 firing rates
remote control release + air damper ionization or UV
LFL 1.622 66“ 4“/2“ 2“/4“ 2“/4“ 502110 LGK 16.622A27 self-controled detection circuit, linked to a ionization sensor or
LFL 1.333 32“ 6“ 3“ 3“ 502109 UV cell like QRA 53/55 ; same program as LFL boxes
With spark detection by QRE1. Control by ionization or UV. NOTE : LGK 16 Necessary for self or remote heating plant. It replaces the LFL
relay. In that case.
Characteristic : burner 1 or 2 tubes 3 firing rates
remote control release+ air damper ionization or UV monitoring Description Ref
LFL 1.622F 66“ 4“/2“ 2“/4“ 2“/4“ 502103 LGK 16.622A27 502060
Characteristic : - LGK 16.322A27 502113
LFL 1.322F 37,5“ 4“/2“ 2“/4“ 2“/4“ 502104 LGK 16.635A27 502114
LFL 1.122F 14“ 4“ 2“ 2“ 502105
Characteristic : gas and mixed
LFL 1.635 67,5“ 5“/2,5“ 2,5“ 2,5“ 502106 LME type

LGA type
Relay Compatible with small and medium power
burners (ionization sensor control) Designed for
earthed neutral wire installations.
NOTE : 220V standard voltage- 110V on request.
Can replace LGB and LMG boxes and detect any defect (Reset button blinking)
When operating with UV sensor, you must use a control module (AGQ3 Ref
 Pre  Pre  Post- Safety 502323)
Type Ref
Purge  Ignition Ignition  Time
 Pre  Post- Safety
Characteristic : atmospheric burner Type  Pre Purge  Ref
Ignition Ignition  Time
2 firing rates with fan + manostat
LGA 52 171B27 Characteristic : defect box detection
replaces LGA 52 170A27 13“ - - 5“ 502185 LME 11 330A2 30“  2“ - 3“ 502010
LGA 52 150B27 13“ - - 5“- 502175 Characteristic : defect box detection replaces LGB 21.130A27
Characteristic : atmospheric burner and LMG 21.130B27
LGA 41 173A27 15“ 15“ 1“ 10“ 502200 LME 21 120A2 7“ 2“ - 3“ 502011
replaces LGA 41 153A27 Characteristic : defect box detection replaces LGB 21.230A27
NOTE : 220V standard voltage - 110V on request. and LMG 21.230B27
LME 21 230A2 20“ 3“ - 3“ 502012
Characteristic : defect box detection replaces LGB 21.330A27
LGB 21 / 22 / 41 type
Box for small or medium power gas burners, with or
and LMG 21.330B27
LME 21 33A2 30“ 2“ - 3“ 502013
without a fan. Flame monitoring by ionization sensor
Characteristic : defect box detection LGB 21.350A27 et
or UV sensor.
LMG21.350B27
Lower voltage Security . Remote control release .
Air pressure control when startup.
LME 21 35A2 30“ 2“ - 5“ 502014
When operating without any motor, it is necessary to cable on plug 3 a resis- Characteristic : defect box detection replaces LGB 21.550A27
tance type AGK 2500 A 27 (except for LGB41) and LMG 21.550B27
when a LFI is replaced you must adapt the monitoring module UV A6Q2.1A27 LME 21 55A2 50“  2“ - 5“ 502015
ref 502321. Characteristic : defect box detection replaces LGB 22.130A27
 Pre  Post- Safety and LMG 22.130B27
Type  Pre Purge  Ref
Ignition Ignition  Time LME 22 131A2 50“ 3“ - 3“ 502016
Characteristic : steam generator 2 firing rates Characteristic : defect box detection replaces LGB 22.230A27
LGB 21 130A27 7“  2“  2,4“ 3“ 502205 and LMG 22.230B27
Characteristic : 2 firing rates LME 22 232A2 20“ 3“ - 3“ 502017
LGB 21 330A27 30“  2“  2,4“ 3“ 502177 Characteristic : defect box detection replaces LMG 22.330B27
LGB 21 350A27 30“  2“  4“ 5“ 502206
Characteristic : 2 firing progressive rates
LME 22 233A2 20“ 3“ - 3“ 502018
LGB 22 330A27 30“  3“  2,4“ 3“ 502178 Characteristic : defect box detection replaces LGB 22.330A27
Characteristic : 2 firing rates /atmospheric burner LME 22 331A2 30“ 3“ - 3“ 502019
LGB 41 258A27 18“  2“  4“ 5“ 502179 Characteristic : defect box detection replaces LGB 32.330A27
NOTE : For the startup with ignition spark control use QRE1 for LGB 21/22 LME 23 331A2 30“ 1“ - 5“ 502020 13
and 41.
Control unit
BO return to the
retour of
beginning sommaire
the chapter

LANDIS & GYR STAEFA - SIEMENS GAS LAMP / REPLACEMENT BULB


CONTROL BOX
Control unit

LME type (condt...)


Description Ref
UV LAMP standard for QRA ref AGR 45 02 11310 502313
UV LAMP high sensitivity ref AGR 45 02 0650M 502314
UV LAMP ref AGR 450242680 502317
Can replace LGB and LMG boxes and detect any defect (Reset button blinking)
When operating with UV sensor, you must use a control module (AGQ3 Ref
502323)
Pre- Pre- Post- Safety
BASE
Type Ref
Purge Ignition Ignition Time
Characteristic : defect box detection replaces LGB 32.350A27
LME 23 351A2 30“ 1“ - 5“ 502021
1 2 3
Characteristic : defect box detection replaces LGB 41.255A27
Description Mark Ref
LME 44 056A2 9“ 2“ - 5“ 502022
Characteristic : defect box detection replaces LGB 41.258A27 AGG4 104.1713 (LFE1) - 502362
LME 44 057A2 9“ 2“ - 5“ 502023 AGK11 for LOA - LGA - LMO 1 502352
AGK 4101 13450 for LFI - LFE10 - LFM - LAE 10 2 502350
AGK 4101 90250 same base for these different models
height 27 mm instead of 20 mm
- 502351

LMG/ LMO type LGK16 BASE AGM17 3 502356


These control boxes can replace the LGB types LFL BASE 4104 0550 - 502366
(the detection and defect analysis).
It uses reset switches that blink. AGK85.22A27 for Weishaupt - 502355
example :
 flame detection defect - 2 blinks
 pressure air defect - 3 blinks
The analysis is stored even when device is off. KF ADAPTER
When operating without any motor, it is necessary to cable on plug 3 a resis-
tance type AGK 2500 A 27 (except for LGB41)
when a LFI is replaced you must adapt the monitoring module UV A6Q2.1A27
ref 502321.
Pre- Pre- Post- Safety
Type Ref
Purge Ignition Ignition Time
Characteristic : defect box detection Description Ref
LMG 21 230A27 20“  2“ - 3“ 502382 KF 8852 in replacement of LFI 7 by LGB 502378
LMG 25 330B27 20»  2“ - 3“ 502005 KF 8853K in replacement of LFI 7 by LGB22 502361
LMG 21 330B27 30“ 2“ - 3“ 502007 KF 8880 in replacement of LFM by LGB 2 502360
LMG 22 330A27 30“ 3“ - 3“ See 502019
KF 8862 in replacement of LFM by LGB 41 502381
LMG 22 233A27 20“ 3“ - 3“ 502008
Characteristic : Limp mixed gas and fuel for Weishaupt SPARK DETECTOR
QRE 1 spark ignition electronical detector.
LMO 82 100C2WH - - - 3“ 407024 Used on burner controlled by ionization whose
light flow is higher than 15% of the nominal capacity
Description Ref
QRE 1 502315

Cell
RC CIRCUIT
Essential tool when LFI / LFM et LGA- LGB - LMG
are connected to 220V mono electric supply
(between 2 phases).
1 2 3 4
Description Mark Ref Description Ref
QRA 2 UV detection cell for gas or mixed burner RC circuit 502316
RED SPOT
2 502310
QRA 2M UV detection cell, same application, high
sensitivity GREEN SPOT
- 502311 UV MONITORING MODULE
AGQ1.1A27 for relay type LGB... LMG
QRA 10C UV Cell - 502308 Additional module for gas burner flame
QRA 10MC UV high sensitivity cell - 502309 monitoring with UV sensor type QRA...
Under base assembly.
QRA 55 UV Cell of 70 mm for LGK 16 1 502320
Description Ref
QRA 50M UV Cell 3 502002
QRA 51M UV Cell 4 502003
AGQ1.1A27 for relay type LGB... LMG 502321
14 AGQ3.1A27 for relay type LME 502323
BO
Control unit
return to the
beginning of the chapter

LFG / LFI / LFM REPLACEMENT RAI / RAQ REPLACEMENT INDEX


OUT OF PRODUCTION boxes. Base re-wiring and a new cell are necessary,
INDEX when you take a new box.

Control unit
Not necessary to rewire, when replacement
OLD BOX Replaced by Cell
Type Replaced by Primary all Adapter none
Characteristic : - RAI 15.2 LFE 1/8 853 Io
LGB21 330A27or 502177 or  502350  RAI 15.1 LFE Io or QRA2
LFG 1.33 X RAI 15.3d LFE Io or QRA2
LMG21 330A27 502007
LFI 713 LGB 21 130A27 Io KF8852 X RAQ 10.1 LFE 10 Io
LGB 21 330A27 or RAI 20 LFE 10 Io or QRA
LFI 733 Io KF8852 X
LMG 21 330A27
LFI 735 LGB 21 330A27 Io KF8852 X
Characteristic : Check that terminal 4 stays connected to the old base LDU type CONTROL BOX
For UV type, add module AGQ ref Diff 502321
KF8880
LFM 1.33 LGB 21 330A27 or Io/UV except X
LFM 1.33F LMG 21 330A27 CUENOD
LGB 21 350A27 or
LFM 1.35 LGB 22 330A27 or Io/UV KF8880 X
LMG22 330A27
Characteristic : Check that terminal 4 stays connected to the old base.
Replacements for atmospheric burners The Leak detector LDU11 is designed for double shuttings gas installations .
LFM 1.33 After each activation cycles, the box programs automatically the seal control,
LGB 41 258A27 Io KF8862 X
LFM 1.33F
and prevents the burner to start in case of internal leakage
Description Ref
LFC / LFI REPLACEMENT INDEX LDU 11 523A27 type 220 volts 502111
OLD BOX ADAPTATION KIT
Primary Cell
Type Replaced by
all
Adapter
with none MAY & CHRISTE
Characteristic : -
LFC 1.1 LGA 41 173A 27 Sensor Io - - X Cell
LFI 5.19 type 02 LGA 41 173A 27 Sensor Io - - X
Characteristic : without ventilator 1 firing rate
LFI 1 série 02 LGA 41 173A 27 Sensor Io - - X
Characteristic : without ventilator 2 firing rates
LFI 1 série 02 LGA 52 150A 27 Sensor Io - - X
Description Ref
Cell OF 14 for ML3.5 - Ø14 mm 508600
LFA / LFB / LFD REPLACEMENT INDEX
OLD BOX ADAPTATION KIT
Cell
Type Replaced by Primary all Adapter
with none PACTROL CONTROL BOX
Characteristic : when ignition spark detected, use boxes type F+QRE Ref
502315 P14 type
LFL 1.122
LFA 2.12 Io - - X
type 02
Characteristic :
(1) when ignition spark detected, use boxes type F+QRE Ref 502315
(2) LFA ionization flame monitoring
(3) LFB UV flame monitoring
LFA (2) or LFB (3)
1.32/ 1.322 (1) LFL 1.322 - - X Description Ref
Io or UV
2.32 /2.322 (1) type 02
4.32/ 4.322 (1) - - X
P14 110 AL for radiant gas (selfcontrol gas) 443010
LFA (2) or LFB (3)
1.33/ 1.355 - - X
2.33/ 2.355 LFL 1.335
type 01
Io or UV P16 type
Range of Control boxes, completely automatic,
4.33/ 4.355 (1) - - - for atmospheric or air (forced up to 60 kw)
LFA (2) or LFB (3) burners. The case includes an ignition
1.62/ 1.622 (1) LFL 1.622 - - X generator and a mono or double electrode .
Io or UV The range of PACTROL P16 controls alternatively the ignition and the flame for
2.62/ 2.622 (1) type 02
4.62/ 4.622 (1) - - X burners up to 60 Kw (forced air) or above. Supplied without base.
LFA (2) or LFB (3) Pre Pre Post- Safety
LFL 1.635 Type Ref
1.63/ 1.635 Io or UV - - X Purge Ignition Ignition Time
type 01
2.63/ 2.695 Characteristic : 1 firing rate
P16C /FL402801 - 6“-12“ - 5“ see 448005
Characteristic : 2 firing rates
LFA / LFB / LFD REPLACEMENT INDEX P16D /402901 - 6“-12“ - 5“-10“ 448005
Type Replaced by Ref
Base for
Cell P16DI /400601 - 6“-12“ - 5“-10“ 448001
re-wiring ref P16DI / S (NF)400601/
Characteristic : V03
- 6“-12“ - 5“ 448002
(1) use these models for atmospheric burners P16FI (CE)406203 - 30“ - 5“ 448007
LFD 1.33 LFL 1.335 or 502102 or 502366 or
none
P16H 403402 - 10“ - 20“ 448009
type 02 LGB 41 (1) 502179 (1) 502350 P16 HIJ 409701 - 10“ - 20“ 448010
LFL 1.335 or 502102 ru 502366 or Characteristic : -
LFD 2.35 none
LGB 41 (1) 502179 (1) 502350 P16B 402701 - - see 448009
LFD 2.38
LFL 1.335 or 502102 or 502366 or
none
P16 AFT - - 448014 15
LGB 41 (1) 502179 (1) 502350
Control unit
BO return to the
retour of
beginning sommaire
the chapter

PACTROL CONTROL BOX 503 SE type


CFR - CSS - CSA type NOTE :
Control unit

The RMO 503 SE (new model) with its release


button replaces the 503SE, but not the old version
of the 502SE.
Pre Pre Post Safety Manufactu-
Type Cell Ref
Purge Ignition Ignition Time rer ref.
503SE 2 + 3 34“ 8“ 7“ 5“ 300.1150 404062

Type Pre Purge Pre Ignition


Post-
Ignition
Safety
Time
Ref 483/520/522 RBO/530/531 SE/535
Characteristic : - RSE type
CSS 01-24R/E 20“ - - 7“ 448050
Characteristic : 2 electrodes ignition and detection
CSS01.12 9“ - - 12“ 448064
Characteristic : same electrode ignition and detection
CSS01-12SJV11 9“ - - 12“ 448062
Characteristic : - 1
CSS01-24JV03 30“ - - 24“ 448063 2
CSA 12 10“ - - 12“ 448065 Type Cell
Pre Safety Manufacturer
Mark Ref
CSA 6 10“ - - 6“ 448066 Purge Time ref.
 483 SE* 3 10“ 5“ see 530 SE -
300.1132 Mectron
 520 SE** 3 6“ 4“ 1 404071
CONNECTOR Four
300.1156 replaces
Description Ref  530 SE 3 10“ 10“ 483 SE 404894
CONNECTOR 10 terminals for P16 448012 300.1158
CONNECTOR 12 terminals for P16 448013  531 SE 3 10“ 10“ for burner with 404895
preheater
10“ 300.3896 for RL28
522 RBO 3 10“ 2 404021
BASE to 190 burner
300.8652 for burner
Description Ref 535 RSE - - -
with preheater
404025
Base for box CSS01.24 448051 * replacement of 483 SE by 530 SE , except when delay timer on 483 SE is
out of order (531 SE with Base in that case.)
** Replacement box kit + coil
APPLICATION INDEX
Type
P 16 A / FL 402601
Manufacturer
SOLARONICS
550 / 552 / 553 SE type
FERROLI (NEF) / SOLARONICS / Control box for blue flame burner
P 16 C / FL 402801 SOLARTUBE/DIFOTHERM (Gulliver BLU BG1).
P 16 D / FL 402901 SPAO RAY/FADIME / LAIDET
P 16 DI / FL 400601 SCHWANK
Pre Post
P 16 DIA / FL 400601 / V07 GENERFEU/KUBBLER Pre Safety Manufac-
Type Cell Igni- Igni- Ref
GAZ INDUSTRIE / EMAT / DIFOTHERM/ Purge Time turer ref.
P 16 DI /S (NF) 400601/ V03 tion tion
FADIME/AIRGARRY/JETTO
550SE =550
P 16 FI (CE) 406203 BABCOCK / AIRCALO
SMD *
IRD 5“ - - - 300.1168 404640
P 16 402701 EMAT
552SE - 8“ - - - 300.1174 404265
P 16 FIS 406203 / V01 (CE) AIRCALO
553SE - - - - - 300.1175 404638
P 16 H 403402 BABCOCK / SCHWANK
555SE - - - - - 300.8850 404024
P 16 HI - J 409701 SCHWANK / BABCOCK
CSS 01 - 24 RE REZNOR / CIAT * A wiring modification is sometimes necessary.
CFR V 401400 -
P 14 110 AL GENERFEU CELL
CSS 01 - 12 GENERFEU
CSS 01 - 12 SJV 11 ETA
CSS 01 - 24 JV 03 HAMWORTHY / POWELL DUFFRYN
CSA 12 SARGI
CSA 6 SARGI / SMITH INDUSTRIE 1 2 3

RIELLO FUEL CONTROL BOX


ACCESSORIES for 480 SE 4 5 6
Description Mark Ref
Replacement kit of Cell 300 5737 1 404185
1
Spare plug for replacement KIT 2 404890
2 Cell 300 2280 for 483/530/531 SE /520 5 404891
Description Mark Ref Cell 300 7839 for 552 / 553 SE 3 404639
Replacement kit / cell 300 5737 1 404185 Cell 300 7492 for 550 SE 4 404637
16 Spare plug for replacement kit 2 404890 Cell 300.8646 for 535 SE 6 404088
BO
Control unit
return to the
beginning of the chapter

BASE RV GAS CONTROL BOX


05 type

Control unit
1 2
Description Mark Ref
BASE 300 2256 for 502/503/505/506/508 SE 1 404061 Description Ref
BASE 300 2278 for 483/520/530 SE 2 404889 Model 05125001 for EMAT (RS22) replaced by P16DIS 448002
BASE 300 2310 for 531 SE 2 404896
Model 0514 for SOLARONICS (SR21/31/41/42/62/82) 453005
Model 05125004 for SOLARONICS/TRATHERM/RENDAMAX
453009
DELAY TIMER replaced model 05125002 and 05125003

SATRONIC FUEL CONTROL BOX


TF type
Description Ref
Delay timer 300 2301 G20D 404641

RIELLO GAS CONTROL BOX


505 - 506 - 508 SE type
Pull-out equipment for oil burner control and security . Flame monitoring by
The RMG 508SE with its release button replaces
photo-resistant cell .
the 508SE, but not the old version of the
505 + 506SE Post-
NOTE : Wiring modification supplied with the box Type Pre Purge Pre Ignition Safety Tme Ref
Ignition
Pre Post Characteristic : 1 firing rate- Replaces TF 701 on 1 firing rate
Pre Safety Manufacturer
Type Cell Igni- Igni- Ref burners
Purge Time ref.
tion tion  TF 801 12“ 12“ 20“ 10“ 507005
508SE Ionizat. 38“ - 2,5“ 3“ 300.1138 404067 Characteristic : 2 firing rates same for 2 firing rates burners.
509SE ionizat. 35“ - 2,5“ 3“ 300.1139 for
404019  TF 802 12“ 12“ 20“ 10“ 507006
FS 10/15/20 Characteristic : 2 firing rates .
 TF 804 12“ 12“ 3“ - 5“ 10“ 507007
525 SE / RMG 88 type Note : TF700 boxes are replaced by Type 800 while adding an extension
cable ref 507301 adjusting the reset switch level

Pre Post Safety Manufac-


Pre
Type Cell Purge Igni- Igni- Time turer ref. Ref
tion tion
525SE Io 30“ - - 5“ 300.1164 404068
Pull-out equipment for oil burner control and security . Flame monitoring by
RMG88.62A2 - - - - 3“ 301 3073 404268 photo-resistant cell .
Post-
Type Pre Purge Pre Ignition Safety Tme Ref
Ignition
566 / 568 SE / MG 569 type Characteristic : With amplifier of the detection circuit. Replaces
without changing the base the TF 730 with an extension cable for
Blue flame, oil burner control box the release button.
(GULLIVER BLU BS 1/2/3/4)  TF 830 12“ 12“ 18“ 10“ 507051
Pre Post Safety Manufac- Characteristic : 2 firing rates .
Pre
Type Cell Purge Igni- Igni- Time turer ref. Ref  TF 832 12“ 12“ 24“ 10“ 507053
tion tion
 TF 840 12“ 12“ 5“ 10“ 507054
MG 569 replaced 568SE and 566SE Characteristic : For burner with pre-heating 1 firing rate.
Ioniza- Replaces without changing the base the TF 734 with an extension
tion - - - - 300.1176 404020 cable for the release button.
see
 TF 834 12“ 12“ 18“ 10“ 507001
BASE Characteristic : Security low voltage.
 TF 834.3 12“ 12“ 20“ 10“ 507001
Characteristic : Security low voltage no Post-ignition.
see
 TF 834E.3 12“ 12“ - 10“ 507001
1 2 Characteristic : For burner with pre-heating 2 Firing rates.
 TF 836 12“ 12“ 25“ 10“ 507050
Description Mark Ref Characteristic : 1 or 2 firing rates.
BASE 300 2256 for 505 /506 / 508 1 404061  TF 844 12“ 12“ 5“ 10“ 507057
BASE 300 2307 for 525 2 404069 Note : TF700 boxes are replaced by Type 800 while adding an extension
cable ref 507301 adjusting the reset switch level
17
Control unit
BO return to the
retour of
beginning sommaire
the chapter

SATRONIC FUEL CONTROL BOX CELL


TMO /TTO/MMO/DKW/DKO type
Control unit

3 4

Pull-out equipment with flame monitoring by photo-resistant cell (on medium 5 6


and high power burners). Description Mark Ref
Remote control release. MZ 770 S Cell reduced, to be used only with boxes
With or without recycling. TF730-1/ TF730/ 733/734 & TF 821/822/830/834/84
Pre Post- Safety 0/740.1 - Supplied with FZ transformation taper 3 507101
Type Pre Purge Ref
Ignition Ignition Time MZ 770 long GIERSCH 6 507102
Characteristic : -
 TMO 720-4-35 30“ 30“ 10“ 5“ 507020 MZ 770 S long BROTJE 5 507103
Characteristic : 2 firing rates Sheath and joint for MZ 770 BROTJE 4 430112
 TTO 810-35 30“ 30“ 20“ 5“ (1)
 TTO 836-35 30“ 30“ 20“ 5“ (2)
Characteristic : - SH type
 TTO 872 30“ 30“ 20“ 5“ (3)
Characteristic : Use with preheater
 TTO 876 20“ 20“ 4“ 5“ (4)
Characteristic : -
 MMO 872 10“ 23,5“ 8,5“ 5“ (3)
Characteristic : preheater
 MMO 876 10“ 23,5“ 8,5“ 5“ (4)
Characteristic : -
DKO 970 - - - - 507009
DKO 972 - - - - 507012 Post- Safety
Type Pre Purge Pre Ignition Ref
DKO 974 - - - - 507014 Ignition Time
DKO 976 - - - - 507015 Characteristic : Special CUENOD - ELCO
Characteristic : Replaces TTO 810-36/ TTO 872-MMO 872 SH 213 mod C1 - - - 5“ 406019
DKW 972 + prolong. 10“ 23,5“ 8,5“ 5“ 507060
Characteristic : Replaces TTO 836-35/ TTO 876-MMO 876
DKW 976 + prolong. 10“ 23,5“ 8,5“ 5“ 507062
Characteristic : - IRD INFRARED DETECTOR
DKW 972 10“ 23,5“ 8,5“ 5“ 507059 FOR FUEL
DKW 976 10“ 23,5“ 8,5“ 5“ 507061
Characteristic : Special CUENOD - ELCO
SH 113 - - - - 406013
replacement Kit see
- - - -
ER1 relay 402023
replacement Kit 1
ER1H relais - - - - 402023 2
Elcopen Analyser The monitoring function follows the infrared light vibration principle.
defect - - - - 402025
Description Mark Ref
NOTE : DXX type boxes, have a defect detection device. The reset switch IRD 911 for FUEL 830.1/832.1/834.1/834E.1/836/840 See
844/TTO872/876 - IRD1010
blinks in a coding type, which indicates the defect location. A pocket size
IRD 810 for FUEL TF 801/802/830/832/834/TTO50.1/ See
terminal type SATROPEN and PC module type SATROCOM are available on
TTO810/TMO720.4 - IRD1010
request.
(1) Replaced by 507060 + (cell MZ ref 507101 if cell FZ stands or detec-
MAN- BUDERUS IRD 1010 white axial shot - 507339
tor IRD1010 depending on brand or cell UVD ref 507003).
BROTJE- BALTUR IRD 1010 blue side shot 2 430412
(2) Replaced by 507062 + (cell MZ ref 507101 if cell FZ stands or detec-
KORTING IRD 1010 blue axial shot 1 507342
tor IRD1010 depending on brand or cell UVD ref 507003). NOTE : IRD 810/910/911 and 820/920 are replaced by type 1010 and 1020.
(3) Replaced by 507060 + (detector IRD1010 depending on brand if you must know the brand of the device to find the right IRD detector.
IRD810 or 910 or 911 stands or cell UVD ref 507003).
(4) Replaced by 507062 + (detector IRD1010 depending on brand if
IRD810 or 910 or 911 stands or cell UVD ref 507003).
BASE
CELL
1 2 3
1 2 Description Mark Ref
Description Mark Ref TF 804/836/844 2 507308
* FZ 711 S OERTLI and DE DIETRICH. special box TF 701/730/734/801/802/830/832/834/840 / 874
Square plug - Red side detection
1 To consult TTO - MMO
1 507300
* FZ 711 S white Cell - side and frontal detection for TTO us TMO 720 3 507310
18 910 - TMO 720 2 S98 for DKW/DKG/DKO/DMG - 507004
* It is necessary to change Cell and the box
BO
Control unit
return to the
beginning of the chapter

ACCESSORIES SATRONIC GAS CONTROL BOX


MMI/ MMG/ DKG/ DMG/ TTG/ SG type

Control unit
1
Description Mark Ref
Extension to find with ref : TF 801 & 802 the same height
as with ref : TF 701
1 507301
Extension specific to BROTJE 1 430733
BROTJE Joint Cell support - 430700
BROTJE Glass Cell support - 430699 Pull-out equipment with flame monitoring using ionization or UV cell (for
medium and high power burners). Remote control release. With or without
recycling.
FR 870 MODEL Type  Pre Purge 
 Pre-  Post-
Ignition  Ignition 
Safety
Time
Ref
Application :
Characteristic : 2 Firing rates ionization replace
 When it’s hard to reach heating equipment.
 If burner fails, difficult to reactivate. box TTI 790-33
 Remote control reset is a necessity. MMI 810-33 33“  3,5“ 2,5“ 1“ 507037
Description Ref Characteristic : 2 Firing rates
FR 870 compatible with ref : TF 800/ TFI 800 / MMI / MMG and MMI 810-35 30“  3“  - 5“ 507034
TTO 876
507304
Characteristic : 1 or 2 Firing rates detection by ionization or IRD
replaced by
MMI 811-35 30“ - - 5“ 507063
ACCESSORIES (except
guillot)
Description Ref
Characteristic : 1 Firing rate ionization with air flap control
Sheath and joint for MZ 770 BROTJE. 430112
Magnetic support M93 for IRD 1020 507350 MMI 812-33 replaced by
63“ 3,5“ 2,5“ 1“ 507033
Adapter plug for IRD BROTJE 430712 MMI 812-23
Fixing tube cell IRD specific MAN RE1 and RE2 420008 Characteristic : 2 Firing rate ionization with air flap control
Tube assembly set cell IRD for MAN 420120 MMI 813.1
mod 23
63“ 3,5“ 2,5“ 1“ 507042
Characteristic : -
KBR and TF REPLACEMENT INDEX MMI 815
Replaced ADAPTATION KIT
OLD BOX Adapter Extension Cell Ref mod 5 replaced by
by with none - - - 5“or 10“
MMI 815 mod 507049
TF20/TF21A
Base to yes Use 10
TF22
KBR611
TF 832 re-wire 507301 Cell MZ - - Characteristic : 1 Firing rate ionization with air flap control
507300 507101
KBR612 MMI 962-23 63“ 3,5“ 2,5“ 1“ 507033
KBR612A Base to yes Use Characteristic : 2 Firing rates replaces without changing
KBR614A TF 832 re-wire 507301 Cell MZ - - the base the TTG 760-33 with an extension cable for the reset
KBR617A/AC 507300 507101
Use switch
TF 740 TF 840 - - Cell MZ - 507023 MMG 810-33 30“ - 3“ 5“ 507056
507101
Characteristic : 2 Firing rates
TF 701/TF714 TF 832 - - - - 507006
TF 704 TF 834 - - - - 507007 MMG 811-33 60“ - - 5“ 507055
Use MMG 811-63 57“ 3“ 2,5“ 3“ 507058
TF 721 TF 832 - - Cell MZ - -
507101 Characteristic : replaces box MMI 811 mod. 35
Use DMG971 - 24“ - 3“ 507063
TF 821
TF 822 TF 832 - - Cell MZ - -
507101 Characteristic : replaces box MMG 810-33
Use replaced by
TF 730 TF 832 - - Cell MZ - - TTG 760-33 30“ - 3“ 3“ 507056
507101
Characteristic : with control of parasite light and 2 Firing rates
Use
TF 734 TF 834 - - Cell MZ - - TTG 760 FN 60“ - 3“ 3“ replaced by
507101 507058
Use Cell MZ
TF 740 TF 840 - - 507101 - - Characteristic : -
DKG 972 - - - 10“ 507049
Characteristic : Special CUENOD - ELCO
TMO / TTO / MMO REPLACEMENT INDEX SG 113 - - - - 406009
OLD BOX Replaced by Note
TTO 750-1 DKW972 Change Cell SG 513 - - - - 406020
TTO 810 model 35 DKW972 Change Cell Kit replacement
TTO 836 model 35 DKW976 Change Cell relay EM41
- - - - 402024
TTO 872 DKW972 Change Cell
Elcopen Analy-
TTO 876 DKW976 Change Cell
ser defect
- - - - 402025
MMO 872 DKW972 Change Cell
MMO 876 DKW976 Change Cell NOTE : DXX type boxes have a defect detection device. The reset switch blinks
TMO 720 in a coding type, which indicates the defect location. A pocket size terminal
TMO 720.2 TMO 720.4 - type SATROPEN and a PC module type SATROCOM are available 19
TMO 721 on request.
Control unit
BO return to the
retour of
beginning sommaire
the chapter

SATRONIC GAS CONTROL BOX CELL


TFI / DKG type
Control unit

Pull-out equipment with flame monitoring using ionization


or UV cell (for medium and high power burners). Remote
control release. With or without recycling. Description Ref
UVZ 780 red spot - UV flame control cell for MMG 810 and 811 507111
 Pre  Post- Safety UVZ 780 white spot - UV flame control cell for TMG 740-2 and
Type  Pre Purge  Ref 507112
Ignition  Ignition  Time 740-3 +TTG
Characteristic : Special for REZNOR
 TFI 812-2  mod replaced by
- - - 10“ 507049
10E
Characteristic : - UV DETECTION LAMP
 DKG 972 - - - 10“ 507049
Characteristic : for atmospheric gas burner 2 firing rates
replaces box TFI 712-10. For remote control reset use FR 870 ref
507304.
 TFI 812-2 maxi
120 Kw mod 10
-- 10“ non 10“ 507043 Description Ref
Characteristic : for atmospheric gas burner 2 firing rates SYLVANIA UV detection Lamp P607.08 Ø 22mm - 4 pin plugs 502312
replaces box TFI 712 without changing the base ; with an exten-
sion cable for reset switch.
 TFI 812-2 maxi
350 Kw mod 5
- 15“ - 5“ 507041

NOTE : DXX type boxes, have a defect detection device. The reset switch blinks
IRD INFRARED DETECTOR
in a coding type, which indicates the defect location. A pocket size terminal
type SATROPEN and PC module type SATROCOM are available
on request

TTG type For Gas The monitoring function follows the infrared light vibration
principle
Description Ref
see
IRD 820 compatible with gas box IRD1020
OLYMP -HG-HLG IRD 1020 BLEUE side shot ( IRD 920 replacement
with IRD 1020 needs a M93 support)
507341
NOTE : IRD 810/910/911 and 820/920 are replaced by type 1010 and 1020.
 Pre Igni-  Post- Safety you must know the brand of the device to find the right IRD detector.
Type  Pre Purge  Ref
tion  Ignition  Time
Characteristic : replaced by MMG 810-33
replaced by
 TTG 760-33 30“ - 3“ 3“ 507056
Characteristic : with control of light parasitic and 2 firing rates. ACCESSORIES
replaced by
 TTG 760 FN 60“ - 3“ 3“
507058

TMG type 1 2
Programmable control box and ionization flame Description Mark Ref
monitoring . M93 Magnetic support for IRD 1020 - 507350
Designed for gas burner models, the TMG can be ZT 870 Transformer 1 805913
used with a UV sensor on fuel-oil burner equipment.
AZ 5 Burner 2 708790
 Pre  Pre  Post- Safety
Type Ref
Purge  Ignition  Ignition  Time
Characteristic : for fuel-oil and gas burner (2 Firing rates)
TMG 740.3 model 32-32
replaces TMG 30“ 3“ - 2“ 507032 BASE
740.2  model 32-32
TMG 740.3 model 43-35
replaces TMG 30“ 3“ 5“ 5“ 507039
740.2  model 45-54
1 2 3
The extension for TFI is used to adjust the height on the old boxes (The new
DANFOSS FFW type to ones are lower)
REPLACE FRA - FRU Description Mark Ref
For Atmospheric, ventilated, fuel or gas burner TMG 740 1 507307
 For semi-automatic installation. TTG - FN - MMI 811/ 812 - MMG 811/ 812 - TTG - TTI
 Flame formation delay : 1 second. MMI 810 - MMG 810- TTI 790 - TF 804 /836/844
- 507308
 Flame safety time delay : 1 second. TFI/TMG740 3 507300
Control by Ionization or cell UVZ or infrared detector IRD 1020.
DKG/DMG/DKO - 507004
Description Ref
Extension TFI 812 2 507301
20 FFW 930 FUEL - GAS 507320 Extension specific BROTJE - 430733
BO
Control unit
return to the
beginning of the chapter

IBR - BR - GBR - TTG TFI - MMI - TMA - TMG STANDARD INSULATION TRANSFORMER
- TTI REPLACEMENT INDEX

Control unit
Kit or replacement box Ref FEATURES :
OLD BOX Replaced by Adapter  IN :220- 240V OUT : 260-280V
Base to re-wire  50 -60 HZ
TME 780 (estimat°request)  Power : 20VA
IBR 661
(on request) cell to change (UVZE -
 Connection : Terminal faston 6,35 mm
est°req.)
Base to re-wire (ref Cotes Fixation Entraxe
TMG 740-3
BR 661 (Ref 507032) 507302) cell to - L l H F E  G  HT
change (ref 507112)
GBR 681 ou GBR MMI 810.33 (Ref Base to re-wire  64   54   52   72   44  - -
681/74 507037) (Ref 507308) -
MMG 810 mod Terminal 1 and 9 Description Ref
TTG 760.33 33 rewire on base
507056
TTG 760 FN MMG 811 mod - 507058 INSULATION TRANSFORMER 805961
63
TFI 712F-1 /TFI 712F TFI 812-2 mod 5 Provide switch exten- NOTE : To increase and regulate the ionization sensor signal
TFI 812-1 mod 5 tion 507301
507041
TFI 712-1 /TFI 712 TFI 812-2 mod Provide switch exten-
TFI 812-1 mod 10 10 tion 507301
507043
TFI 812-2 mod 10E DKG 972 - 507049
MMI 810 mod 32 MMI 810.33 - 507037
Caution: pressure 507063
MMI 811 mod 35 DMG 971 switch wiring (except
to terminals 4 and 7 Guillot)
MMI 812 mod 23
MMI 812 mod 33 MMI 962-1
MMI 812-1 mod 23 mod23 - 507033
MMI 812 mod 63
MMI 815 mod 5
MMI 815 mod 10 DKG 972 - 507049
TMG 720 /TMG 740 TMG 740-3 mod
TMG 740-1 32-32 - 507032
TMG 740-2 mod TMG 740-3 mod
45-54 43-35 - 507039
terminal 1 & 9 rewire
TTI 790-33 MMI 810-33
on Base
507037

SIT GAS CONTROL BOX


503 and 537 type
USE:
To increase and regulate the ionization sensor signal in control box installa-
tions which are not earthed neutral wired.

 Pre  Post- APPLICATION :


Type  Pre Purge  Safety Time Ref
Ignition Ignition  The ionization sensor wire comes from the control box, goes through the isola-
Characteristic : RIELLO - SEET tion transformer secondary and returns to the sensor. The isolation transformer
0.503.902 - - - - 503008 primary is supplied through the same supply as the control box..
Characteristic : WOLF - DE DIETRICH
0.503.501 - - - - 503009 Note: be careful this transformer is a primary and secondary transformer.
Characteristic : BALTUR - ARIANE - SIME - HERMANN - UNICAL
The fact of using the primary and the secondary is harmful.
0.537.301 type
DMT 1,5“  -   -  10“ 431015
Characteristic : BENESSERE - PRONTACQUE SALVASPAZIO
BERETTA - RIELLO
0.537.002 type
DMT 1,5“  -   -  7,5“ 404026
MICRO AMMETER MAP type portable
577 type USE
 The micro Ammeter MAP measures the very
 Pre  Post- low intensity of the ionization and UV cell current for fuel
Type  Pre Purge  Safety Time Ref blue flame burners with ionization sensor.
Ignition Ignition 
Characteristic : GAZ INDUSTRIE  Checks functionning state of flame detection :
0.577.503 30 - - 30 471003 By ionization (burner with electrode)
Characteristic : GAZ INDUSTRIE - BIASI By UV cell
0.577.504 5 - - 30 503001  Measurement -10µA / 0 / +10µA, -50µA/ 0 /
Characteristic : ACV -50µA ou -100µA / 0 / -100µA
0.577.009 - - - 5’ 503002 (according to the selected model).
Characteristic : EMAT Its zero allows measurement even if the wires are commutated.
0.577.308 - - - 5’ 503003 A micro Ammeter is installed in series (on the same line as the probe or the
Characteristic : SAUNIER - UNICAL cell to be measured).
0.577.311 1,5 - - 10 503004
Characteristic : OERTLI - DE DIETRICH Description Ref
0.577.211 - - - 55 503005 MAP -10/0/+10µA Size : L 140 x H 85 x E 55 mm 906567
Characteristic : DE DIETRICH MAP -50/0/+50µA Size : L 140 x H 85 x E 45 mm 906565
0;577.705 - - - 10 503006
Characteristic : SAUNIER MAP -100/0/+100µA Size : L 140 x H 85 x E 55 mm 906562
0.577.304 1,5 - - 10 503007
21
Control unit
BO return to the
retour of
beginning sommaire
the chapter

IONISATION CURRENT MONITORING - RC PRE-WIRED BASE


MODULE BROTJE
Control unit

Improves the value of the ionization


current when, in the electric feeder systems,
the zero lead has a weak potential difference
with the mass of the burner. Bipolar
connection between the zero lead and the 1
mass of the burner.
2
 Size : L 25 x P10 x H 18m Manufacturer
Type Characteristic Mark Ref
Description Ref ref
Module RC model ARC4 66890660 502316 0.501 M for ESB 14-20 521178 1 430108
0.501 M for ESB 24-28 521185 1 430374
0.501 M for ESB 32-41 521192 1 -
0.30U for EB-U 17-25 533577 1 430368
Base wired with
0.30U for EB-U 30-40
preheater
1 430488
533638
AMP and MULTICONTACT CONNECTOR 0.32.2 - 0.31.2 - 0.30.2 1 430488
VARIOUS 0.32U Blue Jet
533577
1 430368
0.32.1 - 0.31.1 - 0.30.1 1 430368
0.501 M for DU 19 539098 1 -
1 2 3 4 0.501 M for DU 25-41 539104 1 430372
-
0.41.1 - 0.42 536004 1 430715
Description Mark Ref
Base wired wi-
With 3 wires cable 0,40 m for RAPA valve, SUNTEC, 0.112 without starter 530323 2 430363
DANFOSS Electrovalve 6 pieces
3 803030 thout preheater
With 3 wires cable 0,40 m for RAPA valve, SUNTEC, 0.112 without starter Base wired with 530309 1 -
DANFOSS Electrovalve 1 piece
3 803034 preheater
With 3 wires cable 0,80 m for RAPA valve, SUNTEC,
0.112 without starter 530316 1 -
DANFOSS Electrovalve 6 pieces
3 803029
With 3 wires cable for ELCO, CUENOD
ignition transformer 6 pieces
3 803031
Straight male 3 pin plugs 4 803032
Straight female 3 pin plugs 1 803033
Cable with connector for preheater 2 803025
Angle connector Female 3 pin plugs 1 470003 CHAPPEE

DOUBLE CONNECTOR
1 2
Manufacturer
Type Mark Ref
ref
Description Ref Characteristic : Base wired with preheater
Double connector contact WEISHAUPT - connector DIN 407100 TIGRA CF 500 58539863 1 401031
TIGRA CF 500 58539864 2 401032
Characteristic : Base wired with preheater
LANDIS type
WIELAND type 1
TIGRA CF 500 58539910 1 401042
Many burners are connected with a 6 male poles
plug. The same piece can be connected between
different installation equipment such as the
circulator, and the regulation and control board.
For the 6 poles plug, we choose the locking type.
Anyway, the 2 parts stay pluggable, with or without a
locking system.
2 CUENOD
Description Mark Ref
Male 3 poles 2 803050
Female 3 poles 2 803051
Male 4 poles - 803040
Female 4 poles - 803041
Male 5 poles - 803010 Ref
Type Ref
Female 5 poles - 803011 constructeur
Male 6 poles 1 803001 Characteristic : -
Female 6 poles 1 803002 NC 4 gas - NC 6 gas - NC 9 gas grey cap 13010521 406008
Male 7 poles - 803020 Characteristic : Base wired with preheater

22 Female 7 poles - 803021 NC 4 - NC 6 - NC 9 grey cap 13010979 406011


BO
Control unit
return to the
beginning of the chapter

DE DIETRICH IDEAL STANDARD

Control unit
1 2

Manufacturer
Type Mark Ref Manufacturer
ref Type Ref
Characteristic : Base wired without preheater ref
MX10 -M1.4S - M1.5S - M1.6S Characteristic : Base wired with preheater
M1.5CS - M1.6CS - M14S 9790-7598 1 405700 HELIS 500 / HELIS MI500 58539863 401031
M18S  M19S - M18CS - M19CS - M10CS Characteristic : Base wired without preheater
M104 9795-5503 1 439118 HELIS 500 / HELIS MI500 58539864 401032
M10R -M16RS -M17RS - Characteristic : Base wired with preheater LANDIS type
M16RCS  M1.4RCS 9790-7599 405701 HELIS 500 / HELIS M500 58539910 401042
Characteristic : Base wired with preheater
M1.3RS -M1.4RS - M1.3RCS  M1.4RCS
M10RD - M10RCS  M10RCS 9790-7597 2 405702
M104 9795-5504 2 439119 OERTLI

ELCO
1 2
Manufacturer
Type Mark Ref
ref
Manufacturer
Type Ref Characteristic : Base wired without preheater
ref
Characteristic : Only SIP66 Base not wired, used to repair SIP OES 310 LE - OES 130 LE 102102 1 405700
45/46/63/64/65 pre-wired base Characteristic : Base wired with preheater
- CAS 106295 803061 OES 310 LEV 101754 2 405701
Characteristic : SIP45 Base wired without preheater OES 130 LEV 102104 2 405702
EL 01A2H /A3H/ A5H CAS 106244 402101
Characteristic : Base wired with preheater
EL 01B2H/ B3H/ B5H CAS 106685 402103
Characteristic : Base wired without preheater
EL 03B20V/30V - EL 1B3/B5/B8 - EL02B16 CAS 106684 402102
Characteristic : SIP45 Base wired without preheater
EL 03.20H / 20V/ 30H/ 30V
EL 01 A3/ A5/ A8 - EL 02.9/02.15 CAS 106156 402100
Characteristic : SIP65 Base wired without preheater
EL 03.20 1D/1DO - EL03.30 1D/1DO
EL02.9 1D/1DO - EL02.15 1D/1DO SIP 065 402104

23
Control unit
BO return to the
retour of
beginning sommaire
the chapter

IGNITION SPARK DETECTOR


DEFINITION :
Control unit

Linked to a flame detector circuit that uses ionization electrode, the system detects a flame
signaling a spark.
It replaces the UV cell for ignition spark detection when the use is compromized.

IGNITION SPARK DETECTOR model DA51 ECEE ref : diff 501660

IGNITION SPARK DETECTOR


model QRE1 Landis and Gyr ref : diff 502315
or
model RT1 Brahma ref : diff 504220

Note : In both cases, the high frequency wave created by the ignition spark, provides a
necessary contact when ionization sensor current goes through. The detection avoids
trouble in case of short-circuit electrode.

INFORMATION

On fuel or gas burners, the modernization and miniaturization of control boxes allow rapid and safe maintenance, through the use of microprocessors.
On the new generation relays, breakdowns indeed are automatically detected by electronics, thus enabling quick diagnosis and reducing attendance.

LMO (replacing soon LOA relays) and LMG (replacing soon LGB relays) have a very fine process. Through a blinking light code, they show the cause of the failure

Failure code tables

LMO Blinking code


LMG Cause
Blinking code Cause
no flame at the end of “TSA”
Blinking 2x no flame at the end of “TSA”  Defective or clogged fuel valves
Blinking 2 x
••  Defective or clogged fuel valves ••  Defective or clogged electrode/cell
 Defective or clogged cell  Bad burner adjustment
 Bad burner adjustment or no fuel Pressure switch does not close
 Defective ignition system Blinking 3x  Defective “LP“
Blinking 4x parasite light when burner starts •••  “LP“ not adjusted
••••  the fan does not function
Blinking 7x flame disappearing too often Pressure switch does not open; parasite light when
 Defective or clogged fuel valves Blinking 4x burner starts
••••••• ••••  Defective “LP“
 Defective or clogged cell
 Bad burner adjustment  “LP“ not adjusted
Blinking 5x
parasite light during preventilation or internal defect
•••••
Blinking 8x Time control of the fuel preheater flame stops during the operation
•••••••• Blinking 7x  Bad burner adjustment
Blinking 10x Bad wiring, internal defect or output con- •••••••  Defective or clogged fuel valves
•••••••••• tacts  Short circuit between ionization electrode and earth
the pressure switch opens during preventilation or
Blinking 18x operation
••••••••••  “LP“ badly adjusted
••••••••
 flame stops for the 4th time
Blinking 19x defective ouptput contacts
••••••••••  Bad wiring
•••••••••  Or another power supply at the output
Blinking 20x
•••••••••• internal defect
••••••••••

24