Specification: Constant Current Discharge Characteristics: A (25)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DC2-1500(2V1500Ah)

Specification
Cells Per Unit 1
Voltage Per Unit 2
Capacity 1500Ah@10hr-rate to 1.80V per cell @25℃
Weight Approx. 91.0 Kg (Tolerance±3%)
Internal Resistance Approx. 0.5 mΩ
Terminal F10(M8)
Max. Discharge Current 6000A (5 sec)
DC (Deep Cycle) series batteries provide
Design Life 20 years (floating charge)
superior high integrity and reliability.It is
Max. Charging Current 300.0 A specially designed for frequent cyclic charge
and discharge.By using strong grids,thick
C1 916.5Ah
plate and specially active material are designed
C3 1161.0Ah
Reference Capacity for repeated deep-discharge applications.
C5 1308.5Ah
C10 1500.0Ah The DC series batteries offer 30% more cyclic
life than the standby series.It is suitable for
2.27 V~2.30 V @ 25℃
Float Charging Voltage solar and wind renewable nergy storage,mobility
Temperature Compensation: -3mV/℃/Cell
and medical equipment,V,telecom,broadband
2.43 V~2.47 V @ 25℃ and cable TV,UPS systems etc.
Cycle Use Voltage Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: 0℃~50℃
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
ISO 9001 ISO 14001 OHSAS 18001
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charged batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional.


MH 28539

Dimensions
Φ20 Length 355±2mm (14.0 inches)
M8
Width
102

337±2mm (13.3 inches)


Height 330±2mm (13.0 inches)
5

Total Height 342±2mm (13.5 inches)


337
342
330

Terminal Value
102

M5 6~7 N*m
M6 8~10 N*m
M8 10~12 N*m
155 F10 TERMINAL Unit: mm
355

Constant Current Discharge Characteristics : A(25 ℃)


F.V/Time 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR
1.60V 1436 916.5 553.1 423.1 333.8 283.0 186.4 158.2
1.65V 1379 885.1 535.5 410.0 324.7 275.6 184.3 156.3
1.70V 1318 856.3 517.8 398.9 315.9 268.5 181.4 154.0
1.75V 1260 825.0 499.7 387.0 307.8 261.7 178.9 151.9
1.80V 1204 793.4 481.8 375.0 299.0 255.0 175.9 150.0
1.85V 1037 711.6 441.5 346.7 277.9 237.8 165.1 141.2
Constant Power Discharge Characteristics : WPC(25℃)
F.V/Time 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR
1.60V 2609 1722 1048 808.1 640.7 545.5 364.0 311.1
1.65V 2531 1673 1020 786.4 625.7 533.3 360.7 307.7
1.70V 2443 1628 991.6 768.4 611.0 521.3 355.9 303.5
1.75V 2359 1578 961.4 748.7 597.6 509.9 351.7 299.8
1.80V 2278 1527 931.7 728.4 582.6 498.5 346.5 296.4
1.85V 1981 1378 858.3 676.4 543.5 466.4 326.0 279.4
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
The battery must be fully charged before the capacity test. The C 10 should reach 95% after the first cycle and 100% after the third cycle.
DC2-1500(2V1500Ah)
Discharge Characteristics Curve Charge Characteristic Curve for Cycle Use(IU)
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.12 2.60
Charge Volume
2.16

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.10 2.50

Charge Volume (%)


Charge Voltage
2.00

80 0.08 2.40
1.84
0.1C 0.05C
0.4C 0.2C 60 0.06 2.30
1.68 After 50% Discharge
0.55C
After 100% Discharge
2C1C 40 0.04 2.20
1.52

1.36 20 0.02 2.10


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 2.00
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.70

100
2.60

Charge Voltage (v )
Cycle use
80
2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 50% 30%
DOD DOD DOD 2.40

40

2.30
20 Float charging
2.27~2.30VPC@25℃
2.20
0 -20 -10 0 10 20 30 40 50
300 600 900 1200 1500 1800 2100
Number of Cycles Temperature (℃)

Temperature Effects on Capacity Storage Characteristics


120 100

100 0℃
0 .1 C A 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
25 2.20

2.15
Battery Voltage (V)
Lift Expectancy (y ears)

20
2.10

2.05
15

2.00

10
1.95

1.90
5
1.85

0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

HENGYANG RITAR POWER CO.,LTD. Add: No.1 Huagong Road, Songmu Industrial Park, Shigu District, Hengyang, Hunan, China 421001
URL: www.ritarpower.com Tel: +86-734-8595528 Fax: +86-734-8595518 E-mail: sales@ritarpower.com Version 19B-0