Professional Documents
Culture Documents
Specification: Constant Current Discharge Characteristics: A (25)
Specification: Constant Current Discharge Characteristics: A (25)
Specification: Constant Current Discharge Characteristics: A (25)
Specification
Cells Per Unit 1
Voltage Per Unit 2
Capacity 1500Ah@10hr-rate to 1.80V per cell @25℃
Weight Approx. 91.0 Kg (Tolerance±3%)
Internal Resistance Approx. 0.5 mΩ
Terminal F10(M8)
Max. Discharge Current 6000A (5 sec)
DC (Deep Cycle) series batteries provide
Design Life 20 years (floating charge)
superior high integrity and reliability.It is
Max. Charging Current 300.0 A specially designed for frequent cyclic charge
and discharge.By using strong grids,thick
C1 916.5Ah
plate and specially active material are designed
C3 1161.0Ah
Reference Capacity for repeated deep-discharge applications.
C5 1308.5Ah
C10 1500.0Ah The DC series batteries offer 30% more cyclic
life than the standby series.It is suitable for
2.27 V~2.30 V @ 25℃
Float Charging Voltage solar and wind renewable nergy storage,mobility
Temperature Compensation: -3mV/℃/Cell
and medical equipment,V,telecom,broadband
2.43 V~2.47 V @ 25℃ and cable TV,UPS systems etc.
Cycle Use Voltage Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: 0℃~50℃
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
ISO 9001 ISO 14001 OHSAS 18001
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charged batteries before using.
Dimensions
Φ20 Length 355±2mm (14.0 inches)
M8
Width
102
Terminal Value
102
M5 6~7 N*m
M6 8~10 N*m
M8 10~12 N*m
155 F10 TERMINAL Unit: mm
355
80 0.08 2.40
1.84
0.1C 0.05C
0.4C 0.2C 60 0.06 2.30
1.68 After 50% Discharge
0.55C
After 100% Discharge
2C1C 40 0.04 2.20
1.52
Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.70
100
2.60
Charge Voltage (v )
Cycle use
80
2.43~2.47VPC@25℃
Capacity(%)
2.50
60
100% 50% 30%
DOD DOD DOD 2.40
40
2.30
20 Float charging
2.27~2.30VPC@25℃
2.20
0 -20 -10 0 10 20 30 40 50
300 600 900 1200 1500 1800 2100
Number of Cycles Temperature (℃)
100 0℃
0 .1 C A 80
Capacity (% )
Capacity (% )
80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
20
20
0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)
Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
25 2.20
2.15
Battery Voltage (V)
Lift Expectancy (y ears)
20
2.10
2.05
15
2.00
10
1.95
1.90
5
1.85
0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)
(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.
HENGYANG RITAR POWER CO.,LTD. Add: No.1 Huagong Road, Songmu Industrial Park, Shigu District, Hengyang, Hunan, China 421001
URL: www.ritarpower.com Tel: +86-734-8595528 Fax: +86-734-8595518 E-mail: sales@ritarpower.com Version 19B-0