Professional Documents
Culture Documents
Automatic Transfer Switch
Automatic Transfer Switch
Automatic Transfer Switch
ENGINEERING
GET YOUR FREE
CONSULTATION
AUTOMATIC TRANSFER SWITCH
An automatic transfer switch is an integral component of an emergency power supply system
(EPSS). This transfer switch allows safe switching from utility power to standby generator power
while maintaining isolation of each source from the other. The main goal is to provide electrical
power to the facility loads (during a power outage) from the standby generator without
backfeeding that can damage utility equipment and hurt (or kill) utility workers. Automatic
transfer switches safeguard data and telecommunication networks, industrial processes and
critical installations such as health care facilities and financial transaction centers.
TRANSFER SWITCH COMPONENTS
Automatic transfer switches continually monitor the incoming utility power. If the normal power
source, often the utility, fails or exhibits some anomalies such as voltage sags, spikes or surges,
these switches detect this loss of power (or anomaly) and send a start signal to the standby
generator. The switches connect the generator to the facility loads when the generator has
achieved proper frequency and voltage. When utility power returns or no anomalies have
occurred for a set time, the transfer switch will then transfer back to utility power. It will instruct
(command) the generator to turn off, after a specified amount of "cool down" time with no load
on the generator. Electrical power to a facility's loads will be lost for a period of approximately
10 seconds while the generator set starts-unless there is an uninterruptible power supply (UPS)
serving loads in the system to bridge the power gap while the generator set starts.
Power system specialists can set up a transfer switch to provide power only to critical circuits or
entire electrical (sub) panels. Some transfer switches allow for load shedding or prioritization of
optional circuits, such as heating and cooling equipment.
There exist three different ways in which a transfer switch can provide power-switching
operation:
Transfer Logic Controller to monitor the condition of the power sources and provide the
control signals to the power-switching device.
Control power source to supply operational power to the controller and switching device
TRANSFER SWITCH
TESTING
Power system specialists should test automatic transfer switches on a monthly basis for EPSS in
accordance with NFPA (National Fire Protection Association) Code 110. This standard also
requires a monthly generator run. There are two main steps for such testing: 1) automatic
generator start that is initiated by the transfer switch, 2) automatic transfer of facility load onto
the standby generator. During the test, the specialists should also take appropriate action when
power interruption to the facility load is a matter of concern.
EXISTING FACILITIES
For existing facilities, the engineer must determine the loads that may actually suffer negative
impact from monthly interruptions in power. One solution for this is to use UPS for protection
from these negative impacts. Also, engineers can replace existing open transition switches with
closed transition switches.
Silver alloy main contacts (highly conductive) and arcing contacts (resistant to heat)
Staffed service centers that operate 24/7. Service vans that are stocked with parts and not
dependent upon supply from other manufacturers
We understand that automatic transfer switches require regular maintenance including preventive
maintenance in the form of testing. Our engineers are highly experienced to carry out testing of
automatic transfer switches to see you and your business prepared for a power-outage
emergency.
Along with starting batteries, fuel is the most common reason an emergency power
supply (EPS or “generator”) fails to start. Problems with the fuel system stem mainly
from foreign matter such as fine abrasives, water, and “coagulated” aging fuel. These
contaminants cause reduced performance and expensive repairs, not to mention
preventing the generator from starting in an emergency.
The need to store substantial quantities of fuel on-site for a potential long-lasting
emergency creates a problem, the one of dealing with this “aging” fuel. The technical
committee responsible for NFPA 110, Standard for Emergency and Standby Power
Systems, recently held its annual meeting to discuss proposed changes. One topic of
discussion included stored diesel fuel.
Fuel tanks should be kept cool and dry, and the tank as full as possible to help with the
reduction of water build-up. But over time there is no stopping the degrading of fuel
quality — especially tanks exposed to extreme temperature variations, such as storage
tanks located outside and above ground.
Fuel Quality
Diesel fuel maintained in a condition as close to “refined” as possible will outperform
fuel that is poorly maintained. To achieve optimal fuel quality, the contaminants in fuel
must be filtered out, water must be separated and removed, and the fuel must be
conditioned. This process of filtration, separation, and conditioning (known as the fuel
polishing process) is the foundation for achieving and maintaining, the quality of fuel
necessary for ultimate reliability.
One of the major causes of an emergency generator not to start is starting batteries.
Corrosion, sulfation, and loss of electrolyte are the most common reasons. With proper
maintenance and testing, these failures can be prevented and extend the life of your
battery. Not caring for your starting batteries could cost the life of a patient, or possible
financial loss, from extensive downtime.
In this article, we will explain the different types of generator starting batteries and
battery conductance testing.
Flooded Lead-Acid
Flooded lead-acid batteries include a removable cap for each cell, allowing visual
inspection of the battery plates and electrolyte level. Venting is standard during
charging. To replenish electrolyte levels always use deionized water. If electrolyte levels
are not “topped off” during scheduled maintenance, permanent damage may occur.
Valve regulated batteries, also known as “maintenance free” or sealed batteries, do not
have a removable cap. Instead, gas escapes through vents designed to release at
increased pressure levels. The term “sealed” means there is no way to access the
individual battery cells as you can with a flooded lead-acid battery. Therefore, the
battery charger must be set correctly to prevent the battery from drying out. Electrolyte
levels are not replenishable.
While not as common as lead-acid, the nickel-cadmium battery, or NiCad, is best for its
ability to operate through a high-temperature range. It has a higher life span and fewer
maintenance requirements. Also, NiCad batteries initially cost more than lead-acid and
include cadmium, a potentially hazardous material.
Lead-acid and NiCad batteries have been around for a long time. However, until the
introduction of the battery conductance tester, battery maintenance was a slow and
challenging process. Taking specific gravity readings from each battery cell and
recording on maintenance checklists is time-consuming. The use of a hydrometer is no
longer needed.
Maintenance Requirements
NFPA 110, 8.3.6.1 “Battery conductance testing shall be permitted in lieu of the testing
of specific gravity when applicable or warranted.”
With the battery conductance tester, personnel can save time and money with more
accurate results, quickly identify battery health, and uncover potential problems before
an actual emergency. Batteries fail due to buildup on charging plates. This buildup
disrupts the flow of energy increasing the batteries resistance to charge. A battery
conductance test will measure impedance and provide a report on the batteries health.
Testing Procedures
Depending on the brand of battery conductance tester, set up may vary. The tester
should guide you through the steps in selecting the correct settings. The most important
will be “Cold Cranking Amps” or CCA. This specification is the measure of a battery’s
ability to supply a certain amount of power for a short period. Make sure the CCA
setting is identical to the rating of your battery.
When connecting the battery conductance tester to the battery ensure the positive (+)
clamp attaches to the positive terminal, and the negative (-) clamp connects to the
negative terminal. Make sure both clamps grip the terminals. A poor connection will
prevent testing. Most testers will indicate if the link is weak or not so you can make
adjustments if necessary. Some also come pre-installed with a printer, or the ability to
add one, or transfer the data to a computer for further analysis and archiving.
Conclusion
Whichever method you choose, written, printed, or electronic format, ensure you keep
good records. Analyzing results over time will allow you to make informed maintenance
decisions and avoid costly downtime. Although conductance testing will give you a good
indication of the batteries health, cranking voltage is the truest test of readiness. Be on
the lookout for an additional article on Voltage Drop Testing in our upcoming
newsletters.
Who has the last word on maintenance and testing requirements? NFPA 110, 8.1.1 is
essentially the genesis of all maintenance and testing (M/T) programs. Why? Because
while other standards are concerned with maintenance and testing, all refer to NFPA
110, and paragraph 8.1.1 marks the beginning. This paragraph is just one sentence in
length, but what does it mean?
How each facility responds to this simple statement is what complicates the equation,
because while manufacturers’ recommendations should be the basis of the M/T
program, manufacturers cannot control what M/T programs are ultimately followed by
the end user. Your responsibility is to see that an M/T program which adheres to the
intent of the manufacturer is put into place.
The automatic transfer switch (ATS) is a critical system component of the emergency
power supply system (EPSS), and proper maintenance of an ATS depends on the type
of switch and its position in the critical power infrastructure. Imagine losing power during
a natural or human-made disaster due to incorrect sensing or time-delay function. Or,
the result of a maladjusted ATS control panel. A large percentage of automatic transfer
switch failures are attributed to preventive maintenance.
Compliance
Below is the sole reference in NFPA 110 (2019 Edition) referencing transfer switch
maintenance.
1. Checking of connections
2. Inspection or testing for evidence of overheating and excessive contact erosion
3. Removal of dust and dirt
4. Replacement of contacts when required.
1. Checking connections
2. Inspecting or testing for evidence of overheating and excessive contact erosion
3. Removing dust and dirt
4. Replacing contacts when required
5. Verifying that the system controls will operate as intended
The transfer switches and parallel gear are the brains of the EPSS; and while no
frequency interval for maintenance is specified, it is strongly recommended that
scheduled comprehensive reviews are performed by a ‘qualified’ technician quarterly
with ‘internal’ maintenance performed once a year.
These steps are reversed upon the return of the normal power source. The
ATS/switchgear logic will again verify the normal power is within the desired parameters
and stable before retransfer. Once the ATS/switchgear returns to the normal position,
the ATS/switchgear logic dictates a cool down period for the EPSS generator(s).
Preventive Maintenance
Proper maintenance of all components of the emergency power supply system (EPSS)
is essential and directly linked to the integrity of the critical power system. As it relates
to NFPA 99 and 110; this system is only called upon to function in an emergency. Of
course, this is the worst time for a malfunction of any one element. The total aspect of
maintenance extends far beyond the routine tasks recommended to properly maintain
any single element. Maintenance programs must be carefully reviewed, and
maintenance provider selection is just as important as any other aspect of the EPSS.
* This work is performed before de-energized maintenance with normal loads applied,
and against each source of power. If discrepancies are addressed; and after any
physical maintenance is performed to the transfer switch, comparison imaging should
be taken. The resultant report will define problem areas and/or resolutions…and will
allow the maintenance provider to take a proactive approach for potential changes to
the maintenance plan.
Training
Although the tasks listed above do not appear especially extraordinary; these steps
require specific training and tooling. NFPA 99 and 110 specifically state maintenance
and testing activities will be performed by qualified/competent personnel.
Conclusion
The total aspect of maintenance extends far beyond the routine operational testing
performed by facility engineers. The example of the annual ATS maintenance illustrates
the requirement of these procedures to be carried out by a dedicated, trained
professional.
Special thanks to Steve Works with Blanchard Machinery for assistance in editing this
article.
Diesel Generator Exhaust Issues and NFPA
110
Published: January 23, 2019 Danny Chisholm
In 1999, the technical committee for NFPA 110 adopted a substantial change in the
procedure to check for wet stacking conditions present in diesel engines not being
loaded sufficiently. The modification involved comparing exhaust gas temperatures with
manufacturers’ recommended minimum temperatures. In contrast, the wording in
previous editions stated that evidence of wet stacking was indicated “by the presence of
continual black smoke during engine-run operation.” Clearly, using exhaust temperature
data will yield more objective information with which to determine if wet stacking exists.
NFPA 110 (2019 edition), 8.4.2* Generator sets in service shall be exercised at least
once monthly, for a minimum of 30 minutes, using one of the following methods:
The 2019 edition removed the word “Diesel” from the paragraph text. The 2010 edition
states “8.4.2* Diesel generator sets in service…”
Option A: Thermocouple
On the high-end side of the expense scale is a temperature probe unit, or
thermocouple, which is embedded in some portion of the exhaust system or cylinder
head and sends data automatically. Once installed, tracking exhaust temperatures is
automatic. The drawback to this system is the price: they’re rather expensive to retrofit –
upwards of several thousand dollars per engine.
Unfortunately, these connections are not easily accessible on some engines, and
attempting to obtain readings here may present a real threat to personal safety and
should be avoided. We recommend the safer option of specifying a location on the
exhaust manifold where all exhaust ports empty their gases and obtaining temperatures
in the same spot. Since your specified location may be some distance from the
combustion chambers, the temperatures you obtain will be cooler, and the data must be
adjusted for this difference.
Manifold temperature data can provide a very accurate picture of the condition under
which an engine is running. Readings that are too low – after adjusting for the
temperature differential between the combustion chamber location the manufacturer
used for their recommendations and the location the facility chooses to obtain their data
– can be a clear indication that wet stacking conditions are present, and appropriate
action can be taken to alleviate the problem.
Supplemental Loads
If a facility is unable to make the 30% of nameplate rating and does not have the
exhaust temperatures that demonstrate the generator is sufficiently loaded, an annual
supplemental “load run” will need to be performed. As stated in NFPA 110, 8.4.2.3,
installations that do not meet the requirements of 8.4.2 shall be exercised monthly with
the available EPSS load and shall be exercised annually with supplemental loads at not
less than 50 percent of the EPS nameplate kW rating for 30 continuous minutes and at
not less than 75 percent of the EPS nameplate kW rating for 1 continuous hour for a
total test duration of not less than 1.5 continuous hours.”
While the monthly test loading of a generator above the 30% level is not required by
NFPA 110 beyond the above circumstances, we recommend loading the generator to
75-80% of the nameplate “on occasion” to benchmark exhaust temperature readings
starting at a no-load level. The graph below is a record of such Exhaust temperatures.
Most activations of the EPO are unintended. Therefore, any EPO system must be
designed for any possibility of accidental activation and must minimize any reason for
activation other than a life-threatening emergency. Most activations are a human error
— unintentional activation during maintenance, mistaken for the wrong button, etc.
If the main disconnect device is not readily accessible, the Emergency Power Off switch
(or button) provides a means to disconnect the power and shut down the prime mover
from another location. Section 445.18 of the NEC® covers disconnection means and
shutting down of the prime mover.
Generators shall have provisions to shut down the prime mover. The means of
shutdown shall comply with all of the following:
(1) Be equipped with provisions to disable all prime mover start control circuits to render
the prime mover incapable of starting.
The provisions to shut down the prime mover shall be permitted to satisfy the
requirements of 445.18(A) where it is capable of being locked in the open position in
accordance with 110.25
Generators with greater than 15kW rating shall be provided with an additional
requirement to shut down the prime mover. This additional shutdown means shall be
located outside the equipment room or generator enclosure and shall also meet the
requirements of 445.18(B)(1) and (B)(2).
5.6.5.6* All installations shall have a remote manual stop station of a type to prevent
inadvertent or unintentional operation located outside the room housing the prime
mover, where so installed, or elsewhere on the premises where the prime mover is
located outside the building.
5.6.5.6.1 The remote manual stop station shall be labeled.
5.6.5.6 All installations shall be provided with at least one remote emergency stop
switch for each prime mover.
5.6.5.6.1 The remote emergency stop switch shall be located outside the room housing
the prime mover or exterior enclosure and shall be permitted to be mounted on the
exterior of the enclosure.
5.6.5.6.3 The remote emergency stop switch shall identify the prime mover it controls.
If you read the 2010 edition paragraphs above and compare to the 2019 edition, you will
see the addition of “shall be permitted to be mounted on the exterior of the enclosure.”
As you may know, most generators located outside within an enclosure come with an
EPO switch mounted on the outside of the enclosure. Since the 1980’s most
manufacturers deliver the new emergency power supply with the EPO installed.
However, this has raised some questions in the health care community on what the
CMS is allowing.
CMS
After receiving several emails from students regarding placement of the EPO, we sent a
question to the Centers for Medicare & Medicaid Services. “Is the CMS now disallowing
remote manual stop stations from being located on the outside of a generator
enclosure, located outside of a building?”
Manual record keeping for total compliance can sometimes be inaccurate and onerous.
Mechanical and electrical systems are often spot checked rather than continuously
monitored and out-of-parameter readings may be missed.
Monitoring Fundamentals
A fundamental feature of automated monitoring is the archival of data over the lifetime
of the equipment for compliance purposes. This archived data allows for analysis of the
EPS before a major mechanical issue occurs. For example, the median oil pressure
during loaded running events may remain in acceptable range over years, but if that
measurement is slowly declining over time, that trend can reasonably point to future
failure, and of course, failure prevention is the objective of remote monitoring.
Wired or Wireless?
Automated remote monitoring can be implemented on different data transport
technologies.
If you would like to learn more about EPS monitoring options, please click here to
contact Dan Chisholm Sr.
For the most part, AHJ’s refer to NFPA standards for guidance; however, you would be
wise not make a buying decision based on any “standard” until you have a specific
written agreement with the local AHJ. NFPA 99, Health Care Facilities Code, defers to
NFPA 110, Standard for Emergency and Standby Power Systems, for design
requirements of Type I, II and III essential electrical system (EES) power sources. Each
of these designated “Types” are further designated as “Type 10, Class X,” as defined by
NFPA 110.
“Type” refers to the maximum time, in seconds, that the EPSS will permit the
load terminals of the transfer switch to be without adequate electrical power.
“Class” refers to the minimum time, in hours, for which the EPSS is designed to
operate at its rated load without being refueled.
“Class X” is defined as the time, in hours, as required by the application, code, or user.
In other words, NFPA 110, through its classification structure, creates broad guidelines
concerning how to utilize the EPSS, and the AHJ’s then make the specific calls.
Why do variances exist? Each local AHJ makes a judgment about fuel stored on each
site based on local factors, including the estimated time a facility would have to wait for
fuel delivery, seismic classification, storm history, and general history of power outages.
Although you must check with the local AHJ for their recommendation, we favor having
the equipment, such as boilers, use fuel from the same tank as the EPSS. The fuel in
“dedicated” tanks, especially EPS skid mounted tanks, are normally not used or “turned
over” at the same rate as non-dedicated tanks. In these types of setups, the pickup
tubes for the other equipment are inserted into the tank in such a manner that the EPSS
“dedicated” fuel is not disturbed.
“Fuel polishing” has become the standard way of ensuring fuel meets the
manufacturer’s standards. It can be accomplished using either a portable or
permanently installed apparatus. Economics is a concern as well as having a plan to
ensure clean fuel whenever an event will occur. See “Fuel polishing aids facility in
emergency power readiness” (Health Facilities Management)
1. A test is an active demonstration that the EPSS is still able to function as intended. If a
switch is going to fail to transfer, it’s better to have the switch fail while connected to a live
normal source during a test than to have it remain connected to a dead normal source during
an actual power outage.
2. An automatic transfer switch is an electromechanical device with moving parts. Like
the pistons and crankshaft in an automotive engine, the moving parts in an ATS can seize if
they’re left in one position for months or years. Regular exercise will help ensure that moving
parts will continue to operate smoothly.
3. A transfer switch test transfers building load onto the generator for the duration of
the generator test. Most standby power generators of more than 100kW are diesel engine
driven, and all major diesel generator manufacturers recommend a load of at least 50% of
maximum capacity during monthly generator tests. NFPA requires the same thing, for the
simple reason that running under a light load is very bad for a diesel engine.
Check wiring and connections are tight with no discoloration of metal, melted plastic
and odour indicating excessive heat.
Verify external operating mechanism is clean and re lubricate if found dirty.
Check for any deterioration of wiring insulation such as cuts and abrasions. Replace or
repair any damaged wiring.
Check tightness of wiring connections. Retighten to specification if any loose wiring
found.
Perform insulation resistance tests on all control wiring with respect to ground.
Perform a contact/pole-resistance test.
Verify settings and operation of control devices.
Calibrate and set all relays and timers.
Verify phase rotation, phasing, and synchronized operation as required by the
application. .
Check ATS main power switching contacts condition. Clean or replace. Replace
contractor assembly if necessary.
Exercise the generator set under load.
Test the transfer switch’s automatic control system.
Test all indicators (LEDs) and all remote control systems for operation.
Inspect the outside of the transfer switch for any indication of wear, excessive
vibration, leakage, high temperature, contamination or other deterioration.
Verify all external components are in place, firm, tightened and not excessively worn.
Inspect the inside of the transfer switch for any indication of excessive vibration,
leakage, high temperature, contamination or any other deterioration.
Verify all internal components are in place, firm, tightened and not excessively worn.
Electrical Tests
With respect to ground execute insulation resistance tests on control wiring entirely.
Perform a contact/pole-resistance test.
Verify settings and operation of control devices.
Calibrate and set all relays and timers.
Check phasing, phase rotation and synchronized function as needed.
Perform automatic transfer tests:
Simulate loss of normal power.
Return to normal power.
Simulate loss of emergency power.
Simulate all forms of single-phase conditions.
General Inspection
The inspection work should be conducted externally and internally on the transfer
switch.
External Inspection
The transfer switch should be kept in good condition by performing a weekly overall
examination of the unit. This inspection must consist of inspecting for signs of excessive heat,
vibration damage, any level of deterioration, any leakage or contamination.
Any accumulations of dirt or dust must be removed. Dirt, dust and any other
contaminants should always be removed from the outside and inside with a vacuum cleaner,
dry cloth or brush. One should not use compressed air to blow away contaminants and dirt.
This can result in debris being lodged in components resulting in damage to the switch.
If the inspection exposes damaged or loose components contact a trained professional
to perform the repair work.
Any worn, broken or missing external sections must be substituted with
manufacturer’s recommended components.
Contact the local authorized distributor or dealer for the specific part number to
order.
Internal Inspection
All power sources must be turned OFF afore any internal inspection.
Verify to see if any external glitches found have disturbed internal components, while
opening the switch door.
A trained service technician must be called to perform any service work. If any of the
following conditions are detected:
1. Dirt, dust, moisture and other contaminants accumulating on the surfaces of the unit
and components
2. Any signs of corrosion
3. Loose, missing or broken components
4. Deterioration of wiring or insulation due to cuts, abrasion or wear
5. Indications of overheating due such as melted plastic, discolored metal or burning odor
6. Any other evidence of damage, wear or malfunction of the transfer switch and its
components
Only a trained technician must carry out internal service work and inspection on a
standby system that doesn’t permit power interruption in the course of required inspection.
When inspections are internal or more than just a visual inspection by the operator,
they should be performed by an authorized distributor or dealer under a scheduled
preventative maintenance agreement.
Have an approved dealer or distributor replace or repair all damaged internal parts
with the manufacturer’s suggested components.
The transfer switch automatic control system should be tested monthly. The test
should verify the following:
The necessary sequence of functioning happens when the load shifts to the emergency
source which results in primary source failure
Verify indicator LEDs on the transfer switch operates properly
Watch and eavesdrop for any unnecessary vibration or noise in the course of operation
Finish the test once the switch transfers the load to the standby source and check the
foreseen sequence of operations happening as the transfer switch shifts the load to the
primary power source and signals the generator set to turn OFF later or after a cool down
period.
Check if the time delay in the OFF position works while load is transferred to the
standby source and transferred back to the favored source, in the case of systems with
programmed time transitions.
Functional Test
The transfer switch functional tests comprise of electrical and manual tests. A manual
operator handle is provided with the transfer switch for maintenance purposes only.
Before it is operated electrically, manual operation of the switch must be checked.
A usual method of an automatic transfer switch functional test for a standby
generator is explained below:
1. To begin the test, close the normal source circuit breaker. The switch controller will
light up the available LED when right voltage is sensed. If the source 1 stages the automatic
transfer switch mechanism, the LED at source 1 will turn on. Verify the phase to phase
voltages at the utility line terminals.
2. Start the engine generator after closing the alternate source breaker. The S2
(Alternate) Available LED will illuminate when correct voltage and frequency levels are
sensed. Turn OFF the engine generator after both sources have been validated and place the
generator’s start control in the automatic position.
3. Replicate a utility failure by opening the Source 1 i.e. the normal side breaker. The
delay to engine start timer begins its timing cycle. After the timer has completed its timing
cycle, the engine start contacts close to start the generator.
4. When generator frequency and voltage touch the fixed reinstate points the Source 2
available LED lights up. Simultaneously, the delay to generator timer begins its timing cycle.
When the time delay is completed the ATS will transfer to Generator, the S1 position LED
goes off, and the S2 position LED illuminates. Systems shall transfer in no less than 10 seconds
where failure of the equipment to perform could result in loss of human life or serious
injuries.
5. Reclose the Source 1 breaker to re transfer to the normal source. The delay to utility
timer begins its timing cycle. When the timer has completed its timing cycle, the ATS will
transfer. The S2 position LED goes off, and the S1 position LED illuminates.
6. The delay engine stop timer will begin its timing cycle. The generator runs unloaded
for the duration of this timing cycle. The generator will Turn OFF, once the timer finishes its
timing cycle, The S2 Available LED goes off. A minimum time delay of 5 minutes should be
provided for unloaded running of the EPS prior to shutdown to allow for engine cool down
(NFPA 110). The minimum 5-minute delay is not required on small air-cooled prime movers 15
kW or less.
Precautions
Inspection and Cleaning Before doing any work on the transfer switch, de-energize all
sources of power.
The switch must be checked for any moisture, dirt or dust and must be vacuumed or
wiped with a soft brush or dry cloth.
DO NOT use a blower since debris may become lodged in the electrical and mechanical
components and cause damage.
Any surface deposits must be removed with a clean cloth.
Direct Measurement
When testing the grouped live conductors of a circuit, the magnetic fields produced by
the load currents cancel each other out. Any uneven current coming from the conductors to
ground is measured with a leakage clamp meter and must have a reading less than 0.1 mA.
If you performed an insulation test on a circuit that was powered down, the result
would be in the range of 50MΩ or further, because the insulation tester utilizes s a dc voltage
for checking, which do not consider the capacitive effect.
If you measured the same circuit loaded with office equipment, the result would be
significantly different due to the capacitance of the input filters on these devices.
When a lot of parts of equipment are functioning on a circuit, the result will be
collective, that is, the leakage current will be greater and could well be in the range of
milliamps. Adding new pieces of equipment to a circuit protected by a GFCI could trip the
GFCI. And as the value of leakage current differs based on how the equipment is functioning,
the GFCI may trip unintentionally.
When telecommunications equipment is present, the value of leakage indicated by a
clamp meter may be considerably more than that resulting from insulation impedance at 60
Hz because, telecommunications system usually consists of filters that generate functional
grounding currents and other gears that generates harmonics, etc.
When the load is switched on, the leakage current measured includes leakage in load
equipment. If the leakage is adequately small with the load attached,
then circuit wiring leakage is even smaller. If circuit wiring leakage alone is required,
disconnect the load.
If you test single-phase circuits by clamping the phase and neutral conductor, the
obtained amount will be any current streaming to ground.
Test 3 phase circuits by fastening a clamp around all 3 phase conductors. If a neutral is
present, it must be clamped along with the phase conductors and the measured amount will
be any current flowing to ground.
To quantity the sum of leakage streaming to the proposed earth connection, position
the clamp around the ground rod.
This series of measurements identifies the overall leakage and the source. The first
measurement can be made on the main conductor to the panel.
Measurements 2 to 5 are made consequently to find out circuits carrying
the bigger amounts of leakage current.
Excessive leakage current can cause the heart to go into ventricular fibrillation
resulting in cardiac arrest which can lead to death.
Leakage current measurement levels depend on the amount of capacitance in the
products’ solid insulating materials. Different types and number of layers of an electrical
insulation results in varying amounts of inherent capacitance through the insulation. This
capacitance causes low amounts of current to “leak” through the insulation.
Leakage current levels can be significantly elevated in products that are subject to EMI
requirements (FCC, CE-EMC). These products must incorporate EMI filters on their incoming
mains power to provide clean power to sensitive electronics while also protecting from
radiating emissions back onto the power line. These filters incorporate capacitors to ground,
these capacitors can cause high leakage current when operating normally. If the product is for
professional use only, the standard may permit high leakage current with warning markings
for the user to insure the product is reliably grounded (so the user isn’t subjected to the high
leakage current). Otherwise, an isolation transformer must be added to power the product
thereby isolating the product from ground – which will almost eliminate leakage current to
ground.
The HIPOT test also called Dielectric Withstand Test is a routine test that is performed
in electrical production industry. This is a high voltage test that stresses the insulation of an
electrical product far 80 M.
If the insulation of product can withstand a much higher voltage for a given time, then
it can withstand normal voltage for its whole life.
The basic function of HIPOT tester is to monitor excessive leakage current to ground.
Hipot tester applies a high voltage across the insulation of device that is tested. This
is generally higher 1400 Volts to test a device that is planned to be operated on 220 Volts.
Terminals A and B are connected to supply voltage of 220 or 110, terminal C is
grounded, return lead is floating as shown here.
The device to be tested should be separated electrically from ground.
One lead from winding is connected to HV out probe and return lead to motor body.
This applies high voltage across winding and case.
If winding is short or weak at any point a current will stream to return lead and meter
will display that current.
All HIPOT testers have an over-current trip to secure the tester itself. This is vital in
case if device is completely shorted to its body and extreme current flows upon application of
high voltage from HIPOT tester.
The device under test is not placed into service, and its polarity need not be
reversed
No stressing due to high switching current
Capacitors have the opposite effect to the inductive motors where it cancels out a
large current flow and thereby, this capacitor bank reduces your electricity bill.
In this test, a direct voltage of 4.3 times of rated rms voltage or alternating voltage of
2 times of rated rms voltage is applied to the bushing stands of capacitor unit. The
capacitor range must withstand any of these voltages for at least ten seconds. The
temperature of the unit during test should be maintained at 25 ± 5 Degree. In case of
three phase capacitor unit, if the three phase capacitor elements are connected in
star with neutral connected through a fourth bushing or through casing, the voltage
applied between phase terminals, would be √3 times of above mentioned voltages.
Same voltage as above would be applied across phase terminal and neutral terminal.
This test is only applicable where internal capacitor elements of a unit are isolated
from its casing. This makes sure the withstand capacity of over voltage of the
insulation offered between capacitor elements and metal casing. The test voltage is
applied between casing and bushing stand for 10 seconds. For the capacitor unit
having bushings of different BIL, this test is done based on lower BIL bushing.
Capacitance Test
This test is done to ensure that each of the capacitor unit in a batch or lot should give
not more than 110 % of its rated VAR during normal functioning within possible
temperature limit which is considered as ˚C. If the measurement is done at any
temperature other than 25˚C, then the meandered result should be calculated
according to 25˚C.
This test is done to ensure that the limit is free from any leakage. In this test the test
unit is heated by an external oven, to force the insulating liquid to come out from the
casing if there is any leakage point. This test makes sure that all joints are tightened
and sealed correctly.
This test is done on each capacitor unit to ensure that internal discharge device or
resistor is capable enough to discharge the capacitor unit from its initial residual
voltage to 50 V or less with in specified time limit. Initial residual voltage may be √2
times of rated rms voltage of the capacitor.
Loss Determination Test
This test is performed on each capacitor unit to demonstrate, the loss occurs in the
unit during operation is less than the maximum allowable loss of the unit.
In this test the capacitor unit is first charged with direct voltage (DC) up to 1.7 times
of the rated rms voltage of the capacitor unit. Then this unit can discharge through a
gap situated as closely as possible without any additional impedance to the discharge
circuit. The capacitance of capacitor should be measured before application of
charging voltage and after discharging the unit. The variance of these 2
measurements should be smaller than the variance of capacitance when an internal
fuse element is activated.
Capacitance Measurement
Before doing this task any threats at the site should be assessed and identified with
proper control measures.
If any hazards cannot be decreased or managed to a suitable limit, don’t continue with
the task and ask for assistance from your Supervisor.
All the tests should be carried out with the capacitor bank de-energized and
appropriate control measures in place to prevent inadvertent contact with adjacent live plant
or breaching exclusion zones.
Issue a Test Permit and follow the requirements of P53 Operate the Network Process.
According to Substation Primary Plant and Secondary Systems Field Testing, safety risks
applicable to capacitors include:
Manufacturer’s name
Manufacturer’s type description
Manufacturer’s serial number
Year of Manufacture
Measured capacitance and rated Capacitance Cn as marked on the nameplate
Serial number of each capacitor can
Rated Output Qn
Rated Voltage Un
Rated Current In
Temperature Category
Visual Inspection of Capacitor Bank Condition
Inspect the external surfaces and ensure the capacitor units and reactors are clean
and dry.
Check that primary connections are correct.
Check earthing to capacitor bank mounting frames and enclosure.
Insulation resistance tests as listed below are to be applied for one-minute duration
each.
Safety CTs/VTs attached to the bank star point must be detached for these tests.
Where several components are connected in parallel, for example capacitor cans, it is
not necessary to obtain a separate insulation resistance measurement of each component.
To make sure that capacitors being assessed have altered adequately to allocate
precise IR measurement make sure that the capacitor has been charged by the megger such
that there is less than a 5 % change in IR over a 1-minute period.
Measure Capacitance
Measure the capacitance of each individual capacitor unit using a capacitance bridge.
The use of any test equipment is to be performed in accordance with the operating
instructions specific to the equipment being used.
Note that tong type capacitance bridges can normally be used without disconnecting
the capacitor units from the bank.
It is favored not to dettach the capacitor units for measurement to evade unintended
harm to the capacitor unit bushings.
Note that the bushings have strictly specified maximum torque limits which must not
be exceeded during tightening of connections.
On the other hand, an AC current source must be attached to insert into a capacitor
unit in series.
The voltage measured across each unit from which the capacitance can be calculated
according to the formula:
C = I / (2 x Pi x f x V)
Where C = capacitance in farads. V = induced voltage in volts. I = injected current in amps. f
= frequency of injected current.
The capacitance calculation must be done at a period when the temperature is steady
across the bank.
Measure Reactance
Where inrush limiting reactors or tuning reactors are fitted, measure the reactance of
the reactors.
The favored technique is to insert a huge alternating current and determine the
voltage induced across the reactor, from which the reactance can be calculated according to
the formula:
Z=V/I
Where Z = reactance in ohms. V = induced voltage in volts. I = injected current in amps.
This formula ignores the resistive component of the impedance, which is a valid
simplification for typical reactors (the Q of a typical air cored reactor exceeds 40.
Perform checking of the balance of every bank by inserting the measured capacitance
amount into a proper balancing program.
Where necessary swap cans to achieve acceptable balancing of the bank.
A capacitor bank being placed in service for the first time requires that the following
items are checked (if applicable) prior to energization:
Check sheet metal work is free from transport damage and assembled correctly.
Check that all permanently fixed panels are properly bolted in position.
Check all door fittings are tight.
Check door locks operate properly.
Check overall appearance and paintwork is clean and free from scratch marks.
Check all control cable terminations are correct and tight.
Check capacitors are neat and free from breaks or leaks.
Check that busbar connections have been torqued correctly.
Check that capacitor bushing connections have been torqued correctly.
Check earth switch operation.
Check isolator operation.
Check operation of discharge timers and electrical interlocking with control systems
and HV circuit breakers and switches capable of energizing the bank.
Check operation of point on wave relays, including adaptive capability of the POW
relays.
Ensure interlock system keys are provided.
Check cubicle lighting operation.
Check the heater operation.
Check all fuses/links are in place.
Check all CT secondary links are closed.
Check external fences and gates.
Check that all labels and nameplates are in position.
Record asset management plant details for SAP/MIMS.
Check operation of all control and protection functions.
After energization save secondary currents and voltages on all protection and metering
secondary circuits, including residual, phase and out of balance measurements.
Prove and record correct operation and adaptivity of point on wave switching devices.
Several test energizing may be necessary.
Benefits of Capacitor Bank Testing
A ground fault is any short circuit that outcomes in an unintentional connection amid
a ground and energized ungrounded phase conductor and ground. Ground faults are
the most common type of fault on power distribution systems. They are due to the
insulation failure or accidental grounding of an ungrounded phase conductor that
causes the ungrounded phase conductor to meet ground. Unintentional grounding of a
phase conductor can occur when a small animal enters a piece of equipment and
contacts both an ungrounded phase conductor and the grounded enclosure. They
monitor that the current going out any one phase is coming back on another phase or
neutral. If current is going out on a phase but is coming back on the ground path a
ground fault has occurred. All systems with ground fault protection include:
Certain systems have a monitor panel indicating system status and a test panel for
generating a ground fault signal to test the breaker.
NEC Article 100 defines ground fault protection of equipment as, “A system
envisioned to give safety of equipment from harming line to ground fault currents by
functioning to bring about a detaching means to open whole ungrounded conductors
of the faulted circuit. This protection is offered at current levels smaller than those
needed to shield conductors from harm through the functioning of a supply circuit
overcurrent device.” Ground-Fault Sensing and Relaying Equipment requires that
manufacturers provide information sheets describing system testing instructions. As a
minimum, UL requires the following performance testing for manufacturers’ test
requirements:
Have a trained personal examine the ground fault protection system to safeguard that
it was fixed properly according to manufacturer’s recommendations. – Verify that the location
of sensors and the polarity of their connections are correct.
Detect system grounding points to ensure that no ground paths occur that would
sidestep the sensors.
Test the ground fault protection system using either a simulated or actual controlled
ground fault to determine that the system settings are correct and that the system is
operating as intended.
Record the results of the performance testing on the manufacturer-provided test
form.
In addition, NEMA Publication PB 2.2 requires the following for performance testing:
A simulated fault current is created by a coil round a window type sensor or with the
help of a distinct test winding in the sensor.
A secondary current in the sensor is created, when the monitor panel sends a small
current through the test winding, which the relay act in response to as if it were created by a
primary current of thousand six hundred amperes.
In a similar method which can be utilized with any window type sensor providing a
ground fault relay, number of twists of wire are covered round the sensor core, like twenty
turns of #14 wire.
A current is passed through the wire to simulate the ground-fault current, which is
approximately 125 percent of the pickup setting of the relay divided by the number of turns
Testing with simulated fault current offers a way of explaining the functioning of the
relay, sensor and shunt trip and the sufficiency of the control power supply.
GFP system must be checked to confirm. that neutral ground points are placed
properly with regard to sensors, that sensor polarities are correct when several are connected
in parallel, and that conductors which pass through a sensor window all run in the same
direction.
The significance of adding simulated fault current testing with sufficient inspection is
highlighted when 1 understands that the first 5 items on the Checklist are problems that
cannot be identified by just simulated fault current testing only.
The high-current injection test method might be used to test ground fault protection
systems with integral ground fault trips on circuit breakers or ground fault relays.
It is an alternative to simulated fault current testing along with inspection in the case
of relays.
Integral ground fault protection in circuit breakers can be system tested only with the
help of high-current injection test method.
No. TAK-TS2, which is utilized along with AKR-SST/ECS trips can be used to determine
the internal electronics of these breakers.
High-current testing of ground fault protection systems comprises of injecting full-
scale current into the equipment phase and neutral conductors to replicate the ground fault
current flow under various states.
The testing gear needed consists of a high-current supply sufficient enough to deliver
up to thousands of amperes or more at 2.5V, or similar.
With the help of smaller ground fault current pickup settings on relays and breakers or
switches, the current necessary to trip can be maintained to a minimum, such as 400 or 300
amperes or less.
If inspection experts needs tests at complete ground fault protection setting, a current
supply sufficient enough to deliver thousand two hundred amperes or more may be necessary.
Connect the current supply and jumpers between the points indicated in the tables
accompanying the diagrams.
Ground fault protection can be supplied for three wires and four wire gear supplied
from a solidly grounded four wire supply.
This is necessary to offer a low-impedance ground fault current return path to the
neutral to make sure functioning of the overcurrent device is correct.
Electrical Tests
Verify right polarities by employing current to each phase neutral current transformer
pair, for summation type systems, utilizing phase and neutral current transformers.
This test also applies to molded-case breakers utilizing an external neutral current
transformer.
Relay must function when current direction is constant relative to polarity marks in
the 2 current transformers.
Relay should not function when current course is contrasting to polarity marks in the 2
current transformers.
Quantify relay time-delay at 140% or greater of pickup.
Check decreased control voltage tripping ability is 81 percent for dc systems and 56
percent for ac systems.
Verify blocking capability of zone interlock systems.
Test Values
Type tests are organised with the aim of proving the abilities and making sure the
rated characteristic of the circuit breaker are exact. Such tests are conducted in the
specially built testing laboratory.
1. Mechanical Test– It is mechanical ability type test involving the repeated opening and
closing of the breaker. A circuit breaker must close and open at proper speed and do its
allocated job and function without any failure.
2. Thermal Test– Thermal tests are carried out to check the thermal behavior of the
circuit breakers. Due to the streaming of rated current through its pole in a rated condition,
the breaker under test undergoes steady-state temperature rises. The temperature rise for
rated current should not exceed 40° for current less than 800A normal current and 50° for
normal value of current 800A and above.
3. Dielectric Test– These tests are performed to check power frequency and impulse
voltage withstand capacity. Power frequency tests are kept on a new circuit breaker; the test
voltage changes with a circuit breaker rated voltage. In impulse tests, impulse voltage of
particular value is employed to the breaker. For outdoor circuit dry and wet tests are
conducted.
4. Short -Circuit Test– Circuit breakers are subjected to sudden short-circuits in short-
circuit test laboratories, and oscillograms are taken to know the behaviour of the circuit
breakers at the time of switching in, during contact breaking and after the arc extinction.
The oscillograms are studied with particular reference to the making and breaking currents,
both symmetrical and asymmetrical restriking voltages, and switchgear is sometimes tested at
rated conditions.
By analysing the current consumed by the trip coil during the circuit breaker’s
operation, it is possible to determine whether there are mechanical or electrical
issues present. In many cases, such issues can be localised to aid in finding the root
cause. Optionally, monitoring the tripping supply’s voltage during the operation can
detect issues arising with tripping batteries.
For individual breaker resistance testing, load and line conductors should be
preferably disconnected. If not detached the test values will also involve the
characteristics of the connected circuit. Resistance testing is crucial for verifying
that the insulating material which makes up the molded cases breakers are
performing correctly. In order to test for insulation resistance, an instrument known
as a megger is used. A megger instrument applies a known DC voltage to a given wire
for a given period of time in order to test the resistance within the insulation on that
particular wire or winding. It is vital that voltage is employed as the resistance
checked with an ohmmeter may differ when there are no report of potential
differences. It should also be noted that if you apply a voltage that is too high for
that insulation to withstand, then you could potentially damage the insulation.
Connection Tests
Normal wear and tear of contacts within the CB emerges after extended usage. An
easy method to identify traces of weakening within the circuit breaker is to quantify
the resistance across every pole of the breaker. Indications of abnormal conditions
within the CB such as erosion and contamination of contacts are evident if there are
excessive millivolt drops across the breaker. The contact resistance test is important
in finding out if or not a circuit breaker is still apt for functioning.
Overload tripping components of CBs can be tested by inputting 300% of the breaker
rating into each pole of the circuit breaker to determine that it will open
automatically. The motive of this is to make sure that the circuit breaker will
operate or not. Refer to NETA standards for trip times that are acceptable for the
overload tripping test. When trying to find out tripping characteristics, it is advisable
to consult with manufacturer’s manuals.
In routine tests, it is relevant to find out that the magnetic feature is functional and
will trip the circuit breaker instead of finding the precise value at which the
instantaneous magnetic feature functions.
How it works
Its tolerances,
Reference values of previous tests,
Initial values with which to compare the actual results, sometimes defined by a rated
timing graph,
Established settings or initial features given by manufacturer
In this sense, how to test a circuit breaker becomes a trending analysis since test
results are not always definitive but have meaning just when compared to previous
data or results.
The timing tests of the different open and close operations of the breaker is an
efficient way of how to test a circuit breaker, analyzing not only the trip times but
also the essential synchronism of the poles in the different operations. This define
how to test a circuit breaker through different simulations of its operation, which can
be directly commanded from the circuit breaker analyzer, or initiated by an external
signal, checking the opening or closing time of each pole, in single or combined
operations, and checking the possible difference between poles or mismatch time
which may lead to a dangerous lack of synchronism. How to test a circuit breaker with
a circuit breaker analyzer depends also on the type of possible problems to be
confirmed, which leads to check other features such as the possible bouncing, the
proper performance of the pre-insertion resistances, the coils condition, and the
mechanical analysis through contact travel speed and acceleration data with the use
of the appropriate transducers.
Circuit breakers generally bear a huge value of current. Greater contact resistance
cause greater losses, low current carrying capability and threatening hot spots in the
breaker, so that the resistance testing with micro-ohmmeters are other way of how to
test a circuit breaker for identifying and avoiding upcoming issues. How to test a
circuit breaker with a micro-ohmmeter requires also reliable measurements and a
wide injection range with high power that enables for longer test leads, less
connections problems, and more accurate measurements.
Testing with a High Current Primary Injection Tester
The analysis of the tripping time characteristics of LV circuit breakers and molded-
case circuit breakers is performed using high current injection, as the way to check
the entire functionality. How to test a circuit breaker of this type depends on its
maximum rated current, the trip protection settings and the inverse curve types
which will define the overload and short-circuit trip pickup levels and time delays; all
these features must be checked with the appropriate primary injection test set with
the capacity to simulate the corresponding high current faults required and capture
the answer of the breaker. A system which be easily upgraded in power capacity
enables how to test a circuit breaker in the different possible situations and range of
breakers; how to test a circuit breaker of this kind also needs a bendable design of
the test set to fruitfully attain the certain large current job, and a design that create
possible to position it nearer to the breaker, and so decreasing the power needed
with smaller test leads; this is the case of the Raptor System, a modular and flexible
primary injection system which easily and quickly adapts its power capacity to the
several high currents ratings of the different circuit breakers.
Soil resistivity
Stratification
Size and type of electrode used
Deepness to which the electrode is covered
Dampness and chemical composition of the soil
Soil resistivity influences the plan of an earthing system absolutely and is the major
factor that decides the resistance to earth of a grounding system. Thus before
designing and installing a new grounding system, the determined location should be
tested to find out the soil’s resistivity.
Clay 40 8 to 70
Type of earth
Stratification
Moisture content; resistivity may fall rapidly as the moisture content is increased
Temperature
Chemical composition and concentration of dissolved salt.
Presence of metal and concrete pipes, tanks, large slabs.
Topography
The results, if adequate investigation is not made prior to the test, or the test is not
correctly undertaken, may be incorrect or misleading. To overcome these problems,
the following data gathering and testing guidelines are suggested:
Note: Temperature and moisture content both become more stable as distance below
the surface of the earth increases. So, to be operative through the entire year, a
grounding system should be fixed as deep as possible.
Following are the steps usually performed during soil resistivity testing:
Test Method
Factors such as maximum probe depths, lengths of cables required, efficiency of the
measuring technique, cost (determined by the time and the size of the survey crew)
and ease of interpretation of the data need to be considered, when selecting the test
type. Three common test types are
Wenner Array: The Wenner array is the least efficient from an operational
perspective. It requires the longest cable layout, largest electrode spreads and for large
spacings one person per electrode is necessary to complete the survey in a reasonable time.
As all 4 electrodes are shifted after every analysis, the Wenner Array is most vulnerable to
lateral variations.
Schlumberger Array: Manpower is hugely utilised with the Schlumberger array as for
each move of the inner electrodes, the outer electrodes are moved four or five times. The
decrease in the number of electrode shifts also decreases the consequence of lateral
variation on end outcomes. Considerable time saving can be achieved by using the reciprocity
theorem with the Schlumberger array when contact resistance is a problem.
Driven Rod Method: The driven rod method (or Three Pin or Fall-of-Potential Method)
is normally suitable for use in circumstances such as transmission line structure earths, or
areas of difficult terrain, because of: the shallow penetration that can be achieved in
practical situations, the very localised measurement area, and the inaccuracies encountered
in two layer soil conditions.
Traverse Locations.
Soil resistivity can differ considerably both from 1 location to another and depth at a
site, and single soil resistivity quantity is generally insufficient. To get an improved
image of soil resistivity difference, it is sensible to perform a thorough survey. A Line
Traverse survey is inexpensive and easy to find differences in soil resistivity at a
location and can give considerable money savings, in terms of labour and material,
when trying to obtain the necessary resistance value.
Spacing Range.
The limit of spacing determined involves précises close probe spacings i.e. less than
1m, which are necessary to find out the upper layer resistivity, utilised in quantifying
the touch and step voltages. Bigger spacings are utilised in quantification of grid
impedance and remote voltage gradients. Calculations at huge spacings usually
provide significant problems and they are vital if the bottom layer is of bigger
resistivity, i.e. ρ2 > ρ1. In such cases considerable error is introduced if a realistic
value of ρ2 is not measured due to insufficient spacing.
It has been found that special care is required when testing to:
Eliminate mutual coupling or interference due to leads parallel to power lines.
Ensure the instrumentation and set up is adequate
Undertake operational checks for accuracy
Reduce contact resistance
Instruct staff to use finer test spacing in areas showing sharp changes
Plot test results immediately during testing to identify such problem areas
4 test rods are evenly placed apart in a straight line and are hammered into the
ground to be reviewed to a deepness of not greater than one by twentieth of the distance
between the neighbouring rods.
An earth resistance tester is connected to these four stakes.
The DC test option on the tester is then selected and performed, and the resistance
figure R recorded.
The soil resistivity level r in ohms/cm is then found out using the formula:
o r = 2 ρaR
o where: R = the resistance figure (in ohms), a = the separation of the test
stakes, in metres.
Fault finding of at least one of the above can save your facility countless hours of shut
down and numerous dollars in savings.
This was accomplished by putting a low voltage motor through extensive testing
rigors, until inducing a failure. Following the failure, additional testing investigated
the possible deteriorating effects on turn-turn insulation due to impulse testing
beyond the motor’s dielectric breakdown. NOTE: This paper was edited from the
original version of the IEEE paper published in 2003.
Electric Motor Rotation Testing
Check for fan or pump motor rotation when testing offline with the MCE. Fans may
continue to slowly rotate due to drafting in the Plenum. Pumps that are attached to a
shared header might remain rotating if other pumps attached to the header are
functioning. This will adversely affect the Standard Test results, possibly creating
higher than normal resistive and inductive imbalances.
Wound Rotor Electric Motor Testing
Wound rotor motors have a three-phase winding wound on the rotor which is
connected to three phases of start-up resistors to provide current and speed control
on start-up. Failed components in the resistor bank are common and often overlooked
when troubleshooting. These damages can have major influence on the complete
functioning of the motor and must be provided significant attention when
troubleshooting these motors.
Electric Motor Insulation Resistance Testing
Electric motor insulation exhibits a negative temperature coefficient, meaning as
temperature increases, resistance decreases. This will make you certain that
insulation resistance of a de-energized motor will reduce after commencing the
motor. However, most often the resistance will initially increase after running due to
moisture being evaporated by the increasing temperature of the windings. The
standard IEEE43 on insulation resistance testing needs a temperature rectification to
forty degrees Celsius, which could instantly turn suitable measured resistance
readings into disappointingly low rectified resistance readings. Before sending a motor
to be renovated, consider space heaters.
Meg-ohm Test
The meg-ohm test has long been the tool of choice for most engineers, and this
simple test is often the only electrical test performed on a motor. However, while the
meg-ohm test has a valid role to play, it is simply not capable of detecting all the
likely faults within a motor’s winding.
PC tests
Modern test equipment utilises PC control to provide automatic testing and fault
diagnosis, thus removing the responsibility on the operator to interpret the results.
The equipment can detect micro arcs, and to stop the test automatically. Database
software permits resources to be saved with all test outputs, so that a practise can be
built up with time, preferably from the inauguration of first-hand motor. Automated
testing also helps remove operator error, inconsistency created by different operators
applying different parameters and the possibility of the operator applying over-
voltage to the motor. The latest testers combine all static electrical tests within one
portable device, which also can create professional test reports.
Static or Insulation Testing
It is performed with the motor disconnected from the power supply. It is particularly
done from the motor control cabinet and must be performed in a predetermined test
sequence.
Winding Resistance Test
It will highlight dead shorts, loose connections and open circuits. Such tests must be
performed with accurate equipment, which can measure down to 0.001 ohm. It is
extremely important to correct the resistance values to a constant temperature,
typically 20 degrees Celsius. The motor temperature should be quantified as precisely
as achievable, and the copper temperature should be utilised wherever possible. A
motor that has been recently operating is very unlikely to be at ambient temperature,
so the use of ambient temperatures should be avoided. Upon conclusion of the test,
the one imbalance between the phase-to-phase readings are quantified.
DC Step Voltage Test
It is typically performed at twice line voltage plus 1000 volts. The voltage is increased
in a series of steps, and the leakage current is plotted. Effective insulation to earth
will denote a linear plot, whereas a non-linear plot will indicate an insulation
deterioration at that voltage where the leakage current instantly amplified. The step
voltage test provides a great deal more information than the basic DC hipot test.
DC Hipot Test
Simply applies a voltage, measures leakage current and calculates meg-ohms. If the
meg-ohms are greater than the acknowledged smallest estimate, the motor passes.
Even if there is an area of damaged insulation which causes a lower reading of meg-
ohms, if that value is higher than the minimum accepted value, it will still pass.
Surge Test
This test is used to verify the turn-to-turn, coil-to-coil and phase-to- phase insulation
condition and is typically performed at twice line voltage plus 1000 volts. It can
identify dead shorts, frail insulation, unbalances and loose connections caused by
incorrect winding. It works by injecting high voltage pulses into each phase, creating
a potential difference between one turn and the next. The resulting sine waves from
every phase must equal 1 another.
The above-mentioned tests are offline tests.
Dynamic Motor Testing or online Testing
A more recent addition to electrical testing technologies, this involves measuring the
voltage and current of the motor’s three phases, while the motor is functioning in its
usual setting, and quantifying a host of data related to, the motor, the power supply
and the load. Both electrical and mechanical issues can be identified.
Power quality values, including voltage level, unbalance and distortion are
determined and compared to industry standards. Bad power quality can point to rise
in temperature within motors, and as heat is the greatest enemy of insulation power
quality problems must be determined and rectified where possible.
Three Phase
Make sure the link for power supply is in decent state. Verify the connection bar for
terminal (U, V, W). Connection type – STAR OR DELTA.
Confirm the power supply VOLTAGE for electric motor. 230/400.
With the help of multimeter, verify the continuity of winding from phase-to-phase (U
to V, V to W, W to U). Every phase-to-phase should have a steadiness if winding is OK.
Verify the motor winding reading in ohms utilising ohmmeter or multimeter for phase-
to-phase terminal (U to V, V to W, W to U). The ohms reading for each winding must be the
same (or nearly the same).
Insulation resistance of motor winding using Insulation tester meter set to the 500 Volt
scale (1000v DC)
With the motor running, check the running amps of the motor using Clamp on meter.
Match up to the full load current on the name plate of motor.
After the completion of every step choose the condition of electrical motor either
NEED TO REPAIRE or OK
Single Phase
1. Common (C)
2. Start (S)
3. Run (R)
All Types
Check the appearance of the motor. Verify for body deterioration or damage to the
cooling fan blade or shaft.
Manually rotate the shaft to check the bearing condition. Check for free & smooth
rotation.
Note the motor data from the motor NAME PLATE.
Earth Continuity: Use your ohmmeter to verify the resistance between earth and
motor frame is less than 0.5 Ω.
Power supply, 415 v between Ll to L2, L3 to L1 and L2 to L3.
Increase up-time
Save money
Conserve energy
Improve safety
WHAT IS GROUNDING SYSTEM DESIGN
AND PLANNING, HOW IS IT DONE
Grounding System Design and Planning starts with a site analysis, collection of
geographic data, and soil resistance of the area. Generally, the site engineer or
equipment manufacturers specify a resistance to ground number. The National
Electric Code states that the resistance to ground shall not exceed 25 ohms for a
single electrode. However, great technology manufacturers will often state 3 or 5
ohms, depending upon the requirements of their equipment. For sensitive equipment
and under extreme circumstances, a one ohm specification may sometimes be
needed. When designing a ground system, the risk and cost increase exponentially as
the target resistance to ground approaches the unobtainable goal of zero ohms.
Low-voltage breakers
They conduct the flow of current as long as a nominal value of current is flowing
through the circuit to the load attached to it. Even at the slightest contact, current
conduction occurs. But as soon as the breaker senses an excessively large amount
which does not lie in its operating range (which can be checked through the ratings of
the circuit breaker), the trip unit actuates the bimetallic strip and the contact breaks
and immediately further flow of current is stopped. In addition to the safety
operation, it also provides a kind of voltage insulation to the circuit and retains the
flow after the current retains its appropriate value.
The field-testing and calibration of solid-state trip units can be performed by either
primary current injection method or secondary current injection method. A
coordination study is an organized effort to achieve optimum electrical distribution
system protection by determining the appropriate frame sizes, ampere ratings and
settings of overcurrent protective devices. When an overcurrent occurs in a properly
coordinated distribution system, only the protective device nearest the fault will
open. The secondary injection test is performed using a specially designed power
supply unit. It should be noted that the secondary injection method only tests the
solid-state trip unit logic and does not test the current sensors, wiring, or the breaker
current handling components. Most solid-state trip units have terminal blocks that are
equipped with test plug terminals for making the calibration test. The test set allows
checking of the solid state trip unit operation without using primary current. The test
set will pass enough current to check any desired calibration point. The breaker must
be de-energized before checking the operation of the solid-state trip units. If the test
set shows that the solid-state trip unit is not functioning properly, the trip unit should
be replaced.
The primary current injection method is usually preferred because this method
verifies the sensors and wiring, as well as the conduction path in the breaker. It is
recommended that the primary injection test be performed simultaneously on all
three phases when testing breakers with solid-state trip units. If three phase primary
injection testing is not practical, then it is recommended that the sensors and wiring
should be tested separately. This testing should be performed per NETA and the
National Electrical Manufacturers Association (NEMA) procedures, and in accordance
with manufacturer recommendations. Coordination Time-current curves are used to
show the amount of time required for a circuit breaker to trip at a given overcurrent
level.
Relays
A relay is an automatic device which senses an abnormal condition of electrical circuit
and closes its contacts.
The first electrical test made on the relay should be a pickup test. Pickup is defined
as that value of current or voltage which will just close the relay contacts from the
0.5 time-dial position. Allowing for meter differences, interpretation of readings,
etc., this value should be within ±5% of previous data. Generally, one or two points on
the time-current curve are sufficient for maintenance purposes. Reset the relay to
the original time-dial setting and two points that could be checked and 3 and 5 times
pickup. Of course, other points could be used, but the important thing is to always
use the same point(s). The instantaneous unit should be checked for pickup using
gradually applied current for reasons previously discussed. Wherever possible, current
should be applied only to the instantaneous unit (to avoid over-heating the time unit).
There are different types of relays:
Current Relays
Relays can include phase overcurrent, current balance, negative sequence, zero
sequence, thermal, and ground fault.
This is the first generation oldest relaying system and they have been in use for many
years. They have earned a well-deserved reputation for accuracy, dependability, and
reliability.
Contact function – Manually close (or open) contacts and observe that they perform
their required function, i.e. trip, reclose, block, etc.
Pickup – Gradually apply current or voltage to see that pickup is within limits. Since
preventive maintenance is the guide post, gradually applied current or voltage will
yield data which can be compared with previous or future data and not be clouded by
such effects as transient overreach, etc.
Dropout or reset – Reduce the current until the relay drops out or fully resets. This
test will indicate excess friction. Should the relay be sluggish in resetting or fail to
reset completely, then the jewel bearing and pivot should be examined. A 4X eye
loupe is adequate for examining the pivot, and the jewel bearing can be examined
with the aid of a needle which will reveal any cracks in the jewel. Should dirt be the
problem, the jewel can be cleaned with an orange stick while the pivot can be wiped
clean with a soft, lint free cloth. No lubricant should be used on either the jewel or
pivot.
Test should be made to check that the overcurrent unit operates only when the
directional unit contacts are closed.
Directional and Power Relays
Directional overcurrent relaying refers to relaying that can use the phase relationship
of voltage and current to determine direction to a fault.
Power Directional Relays provides protection against excess power flow in a
predetermined direction. And are used for anti-motoring protect on of AC generators.
The simplest pickup test for a directional unit is an in-phase test – i.e. current and
voltage in phase. This test will eliminate the need for a three-phase supply, phase
shifter, and phase-angle meter. However, it must be kept in mind that such a test is
usually far from the angle of maximum torque (usually 60° lag for ground relays) and
thus, small changes in components can yield large variations in in-phase pickup. As
long as this fact is recognized and the pickup value is within limits, an angle of
maximum torque check would not be necessary. Clutch pressure must always be
measured in the same manner. For example, some instruction books express clutch
settings in both grams and current/voltage levels. Portable pre-calibrated reactance-
resistance test boxes are available for many of these tests. The use of such
equipment, properly applied, will yield results which will exceed in accuracy those
obtained with conventional phase-angle meters, ammeters, voltmeters, etc. In
addition to the tests previously described for the overcurrent relay, the directional
unit should be tested for minimum pickup, angle of maximum torque, contact gap,
and clutch pressure. Further, a test should be made to check that the overcurrent
unit operates only when the directional unit contacts are closed. . Either test is valid,
but to have comparative data, the same method, either grams or electrical quantities
should be employed each time
Voltage RelaysSecondary Injection Test
Measure the relay auxiliary supply to ensure it is within the nameplate rating
allowable range.
Creep or Pickup Test
Set Red phase of injector’s voltage to 80% of relay setting. Note: Set Yellow and Blue
phase to zero.
Inject Red phase voltage through the relay in order to record the tripping time. Check
test results against the tripping curve characteristics of the relay.
Differential Relays
A test of minimum pickup should be performed. The differential characteristic (slope)
should be checked and where applicable the harmonic restraint should be tested.
Generally, differential relays are extremely sensitive devices and require some special
consideration. For example, those relays employing ultra-sensitive polarized units as
sensing devices are slightly affected by previous his-tory such as heavy internal or
external fault currents. To eliminate previous history and truly perform a
maintenance test, it is the usual practice to disregard the first pickup reading and use
the second reading for comparison with previous and future data. By “disregard” it is
not meant to imply that the initial reading be forgotten; rather it is meant that this
reading not be used for comparison purpose.
Fuses
The fuse is a reliable overcurrent protective device, primarily used as a circuit
protection device for over currents, overloads and short-circuits.
A time-current characteristic curve, for any specified fuse, is displayed as a
continuous line representing the average melting time in seconds for a range of
overcurrent conditions.
NFPA 70B recommends checking fuse continuity during scheduled maintenance, but
testing to assure proper operation and protection against overcurrent conditions is not
required. Fusible switches and fuse blocks require maintenance, such as tightening of
connections and checking for signs of overheating as recommended per NFPA 70B.
In all cases, though, the idea is to send a small current through the fuse; if it passes
through the fuse the fuse is good. If it does not the fuse is blown and needs
replacement. This means that a battery is necessary to provide that small current and
every fuse tester will have a battery in it.If a tester shows that a fuse is blown, the
next step is to check the tester. This is accomplished by touching the test leads
together or, in the case of testers without leads, to put a piece of metal (wire, coin,
dinner spoon, anything metal) across the probes. If it does not indicate “good” the
battery probably needs replacing.
Element testing,
Functional testing, and
Black box testing.
Types of Residual Current Device
There are various types of RCDs that can be used to make sure you are always as safe
as possible.
Fixed RCDs
These are installed in the consumer unit (fuse box) and can provide protection to
individual or groups of circuits. A fixed RCD provides the highest level of protection as
it protects all the wiring and the sockets on a circuit, and any connected appliances.
Socket-Outlet RCDs
These are special socket-outlets with an RCD built into them which can be used in
place of a standard socket-outlet. This type of RCD provides protection only to the
person in contact with equipment, including its lead, plugged into the special socket-
outlet.
Portable RCDs
These plug into any standard socket-outlet. An appliance can then be plugged into the
RCD. They are useful when neither fixed nor socket-outlet RCDs are available but, as
with socket-outlet RCDs, they provide protection only to the person in contact with
the equipment, including its lead, plugged into the portable RCD. Portable RCDs are
plugged into a fixed socket and are suitable for monitoring appliances in high-risk
areas such as workshops, outdoor areas or damp locations. They should be used where
RCD protection is not already provided or is unknown.
The effectiveness of the RCD must be verified by a test simulating an appropriate fault
condition and independent of any test facility, or test button, incorporated in the device
(Regulation 713-13-01)
Where an RCD of 30mA provides supplementary protection the operating time must
not exceed 40 ms at a residual current of 5 I∆n. (Regulation 412-06-02 refers)
Tests are made on the load side of the RCD between the phase conductor of the
protected circuit and the associated cpc. Any load or appliances should be
disconnected prior to testing. RCD test instruments require a few milliamperes to
operate; this is normally obtained from the phase and neutral of the circuit under
test. When testing a three-phase RCD protecting a three-wire circuit, the
instrument’s neutral is required to be connected to earth. This means that the test
current will be increased by the instrument supply current and will cause some
devices to operate during the 50% test, possibly indicating an incorrect operating
time. Under this circumstance it is necessary to check the operating parameters of
the RCD with the manufacturer before failing the RCD.
The RCD Testing Requirements indicate that a manager is required to test each device
every three months. To conduct these tests, they must present the test button found
on the residual current device. The RCD Testing results determine if the device is
worked correctly. After each test, the manager must reset the device by pressing the
appropriate button.
If at any time the test indicates that it isn’t operating properly, the manager must
order a new device and shut down power to the location. They must tag and lock the
device in the location in which it is used. This notifies workers of an existing issue and
prevents them from using any connections running to it.
Performed by an electrician, this test measures how long the RCD takes to trip,
indicating whether it is fast enough be effective.
The push-button test is to ensure that the RCD will trip when there is an earth
leakage, and break the electrical circuit protecting the individual from suffering an
electric shock, or electrocution. When you press the test button, and the RCD has
detected an imbalance, the on/off switch will jump to the “off” position. The test
button will only test the RCD if an electricity supply is connected. This test should be
performed daily or before each time you use the RCD – whichever is the longer.
However it is not particularly accurate and should never be relied on as a reliable
assessment of the RCD working correctly. The “trip time” test using the “applied
current” method is a far more accurate means of testing RCDs and is a required test
under AS/NZS 3760.
It measures the actual trip time and must be performed with equipment able to
measure this to within +/- 8 ms (0.008 of a second).This is a simple test that can be
performed by the user, to determine that the RCD’s tripping mechanism is working.
Portable RCDs
Portable RCDs requires the use of an isolation transformer to carry out operating time
test.
Follow these simple steps to ensure your RCDs are operating correctly:
Plug a small lamp into a power point and make sure it works. Leave it turned on.
Make sure that electricity is connected to the property and the main switch is in the
“on” position. The lamp should be on.
Turn off all electronic equipment (computers and televisions) etc.
Push the test button on each RCD. Do not hold your finger on the test button. The RCD
should operate (turn off). If it does not operate, it must be checked by an electrical
contractor.
After pushing the test button and the RCDs have turned off check that the small lamp
is now off. Also check that all the lights and power points do not operate. To do this, plug the
small lamp into all the power points and turn the power point on. If the lamp turns on, a
licensed electrical contractor must be engaged to correct the wiring.
When finished testing, turn the RCDs back on and check that the lamp works when
plugged into a power point.
First we will disconnect all the line and neutral terminals of the transformer.
Megger leads are connected to LV and HV bushing studs to measure Insulation
Resistance IR value in between the LV and HV windings.
Megger leads are connected to HV bushing studs and transformer tank earth
point to measure Insulation Resistance IR value in between the HV windings and earth.
Megger leads are connected to LV bushing studs and transformer tank earth
point to measure Insulation Resistance IR value in between the LV windings and earth.
The empirical relation as below gives the recommended minimum value for IR, its unit
being mega ohm (MΩ). . The value measures gives us the idea about the insulation
strength of the cable and whether it is deteriorated or not.
IRmin (in MΩ) = kV + 1
Where kV = rated service voltage in kV
There are instances when the measured IR is almost 10 to 100 times more than the
IRmin found from above equation.
General measurement procedure consists of measuring IR between the three phases
and also between individual phase and earth. IR is also measured for equipment body.
The procedure varying from equipment to equipment. There are different voltage
levels which are applied to cable based on their rating and size. For doing a Megger of
a 33kV HT cable. The voltage level applied is of 5000V and the value of IR can
be anywhere between 1GigaOhm to 200GigaOhm.
When we are using a multimeter, we are measuring a resistance, voltage, and
current. Based on this, I hope we are familiar with the term Insulation. This means
that a current cannot pass or leak through a certain conducting wire when it is
properly insulated or protected. These wires may be inside a building, appliances or
an electric motor.
You are basically testing the resistance on a wire. For instance if you want to see if a
motor is bad, you will “megger” it, testing each of the three phases of motor to
ground and to each other to see if it is shorted to either ground or itself.
Types of Megger
This can be separated into mainly two categories:
Still keeps important in such high-tech world as it’s an oldest method for IR
value determination.
No external source required to operate.
Cheaper available in market.
But there are another types of megger which is motor operated type which does not
use battery to produce voltage it requires external source to rotate an electrical
motor which in turn rotates the generator of the megger.
Insulation Resistance or IR Test is carried out by maintenance engineers to ensure the
healthiness of overall insulation system of an electrical power transformer. It reflects
the presence or absence of harmful contamination, dirt, moisture and gross
degradation. IR will be usually high (several hundred Mega ohms) for a dry insulation
system. Maintenance engineers use this parameter as an index of dryness of the
insulation system.
This test is performed at or above rated voltage to determine if there are low
resistance paths to ground or between winding to winding as a result of winding
insulation deterioration. The test measurement values are affected by variables such
as temperature, humidity, test voltage, and size of transformer.
This test should be conducted before and after repair or when maintenance is
performed. The test data should be recorded for future comparative purposes. The
test values should be normalized to 20°C for comparison purposes.
The general rule of thumb that is used for acceptable values for safe energisation is 1
MΩ per 1000 V of applied test voltage plus 1 MΩ.
1. Temporarily link the line conductor to the CPC in the Consumer Unit.
2. Test between the line and the CPC at each accessory point e.g. a ceiling rose,
switch or socket outlet. The reading obtained at each accessory point should be a low
resistance value. The resistance measured at the extremity of the circuit is the sum of
the resistances of the line conductor and protective conductor (R1 + R2).
When we talk about Continuity Testing within the Inspection and Testing
Procedure then we apply the same principle, but with a bit more detail.
Step 1: Select the circuit to be tested in the distribution board and remove the Line
conductor from the MCB
Step 2: Connect the Line conductor to the Earth conductor (for simplicity, connect it
to one of the spare terminals on the Earth bar). This way you will form a circuit which
is half made up of the Line conductor and half made of the Earth conductor (provided
that the terminations within the electrical accessories such as wall sockets are
correct).
Step 3: Select the correct test function on the test equipment, which is the low
reading ohm meter function (Megger 1553).
Step 4:. Do not forget to null the test instrument if required (you can do this by
connecting the two test leads together and pressing the TEST button until the
measured value on the display becomes zero ohm`s)
Step 5: Measure between Line and Earth terminals at each outlet in the circuit. The
highest reading should be recorded on the Schedule of Test Results as the value of
(R1+R2).
Step 6:.Return the Line conductor back in to the MCB
Continuity Testing Overview
Do not forget that with the lighting circuits the intermediate switch should be
switched to all available positions so that all the conductors could be tested for
continuity.
Do not forget to link out the dimmer switch on the other lighting circuit,
otherwise you will get wrong test results.
Remember, that by doing these steps you will also confirm the correct polarity
of the conductors, so there is no need to do polarity dead tests again.
Remember to constantly inspect the installation for faults and signs of
damages.
Multimeters and ohmmeters are normally used for continuity tests. Specialized
continuity testers are also available which are more basic in nature, inexpensive and
have a light bulb which glows in the case of current flow. The continuity test is
performed on an electrical circuit when it is not powered and with help of the testing
device.
Can an electronic circuit which is passing currents be tested by a multi-meter’s
continuity test? Would it be meaningful or harmful? Why?
A continuity test is like a simplified resistance/ohms measurement. A basic method is
to apply a voltage across the resistor and measure the current OR apply a current and
measure the voltage. Then through R = V/I you can calculate the resistance.
Imagine you applied 100 V DC but your meter can only handle 10 V when in the
continuity test mode. Such a test is completely meaningless, and potentially
damaging to the meter. If you want to test continuity or resistance, remove all
sources of power, and discharge any stored energy sources.
The meter is sourcing a (usually low) test voltage. If you connect it to something that
is already powered, you are connecting the two sources together, and the meter isn’t
designed to handle external sources in continuity or resistance (or capacitance, or
inductance, or any other passive) mode..
There is a risk of certain parts being damaged, especially parts that cannot
tolerate the 1 to 9 volts that a multimeter might deliver across the probes in continuity
mode.
The above is especially true when the component (or other components on
connected traces, which will also be affected) is not powered. Many parts can tolerate
voltages when powered but not otherwise.
To minimize the voltage, an option is to use the multimeter in resistance
mode, at the lowest resistance setting – The higher resistance scales work on higher
probe voltage, going by a quick check on a couple of multimeters at my desk.
Note that basic multimeters often combine continuity and diode testing modes,
so the voltage is at minimum sufficient to forward bias silicon diodes and perhaps LEDs.
This means a voltage of 2 to 3 volts.
Return of that investment is a long-term one and it will also save time.
Tests can be done 24/7.
Fewer human resources are required.
Reusability: The scripts are reusable. You don’t need new scripts all the time.
Reliability: It is more reliable and quicker way when running boring repetitive
standardized tests which cannot be skipped.
It not only checks for continuity but also for shorts.
Practical Ground Resistance rods have much less than 160 Ω. Typical rod resistances
will be less than 25 Ω in most soils because of the existence of proximate utility
ground references
Low ground resistance (< 10 Ω ) can be achieved with:
Earth Bonding
“Bonding” is a method by which all electrically conductive materials and metallic
surfaces of equipment and structures, not normally intended to be energized, are
effectively interconnected together via a low impedance conductive means and path
in order to avoid any appreciable potential difference between any separate points.
The bonded interconnections of any specific electrically conductive materials,
metallic surfaces of enclosures, electrical equipment, pipes, tubes, or structures via a
low impedance path are completely independent and unrelated to any intended
contact or connection to the Earth.
The common mean to effectively bond different metallic surfaces of enclosures,
electrical equipment, pipes, tubes or structures together is with a copper conductor,
rated lugs, and the appropriate bolts, fasteners, or screws. Other effectively bonding
means between different metallic parts and pieces might employ brackets, clamps,
exothermic bonds, or welds to make an effectively connections.
In addition to preventing potential differences that may result in hazards, effectively
bonded equipment can also be employed to adequately and safely conduct phase-to-
ground fault current, induced currents, surge currents, lightning currents, or transient
currents during such abnormal conditions.
The principle purposes for an “effectively bonded grounding system via a low
impedance path to earth” are intended to provide for the following.
1. All single pole devices (fuses, switches and circuit breakers) are connected in
the phase conductor only.
2. The phase conductor must be connected to the centre terminal of an Edison screw
lamp holder (with the exception of E14 & E27 lamp holders, these are European and
occasionally crop up in the exam).
3. All polarities of socket outlets (ring & radial) must be verified.
4. The polarity of the mains supply must be correct, using an approved voltage tester.
(This is done with the supply connected, therefore carried out at a different stage then the
above three).
This method is exactly the same as test method one for ‘Continuity Of Protective
Conductors’ if we take a lighting circuit, by putting a temporary link between phase
and circuit protective conductors (cpc), at the consumers unit and our instrument at
lamp holders themselves, we are creating a circuit. When we operate the light
switch, the instrument changes, and then changes back to the original reading on
operation of the switch again. If the reading did not change, then the switch is likely
to be connected in the Neutral. (Not good!) With a little foresight this could be
carried out at the same time as the continuity test. The only difference being, for
radial circuits every point must be tested. The main benefit with this is it allows you
to conduct 2 tests at the same time, polarity and R1 + R2.
This method, like wise is similar to test 2 of the continuity test, we simply use
a wander lead as the return lead. There is little use for this method, within the
polarity test. Method 1 is less clumsy, and is far more flexible and useful.
A Note on radial socket outlets: We have covered ring final circuits, but radial
final circuits involving sockets can prove to be little more involved. Why?
Well simply because doing a polarity check using method 1, will not uncover a phase
to cpc reversal. If the phase and cpc were reversed at the socket, the instrument will
still provide a reading. It will however tell you if you have a phase to neutral reversal
(you wouldn’t have a reading at the socket). So what can we do to expose a
phase? We can simply link the phase and neutral together at the board, and put our
instrument across phase and neutral at the socket, if the cpc and phase have been
reversed, then no reading will be recorded on the instrument.
If visual inspection is not possible, you will need to use a low-resistance ohmmeter for
this test. When you continuity test radial and ring final circuits, part of the process is
to test and visually inspect the polarity of fixed equipment and socket outlets.
Steps:
If the two methods are not possible due to urgency we can perform live polarity
testing by using the approved voltage GS38.
Steps:
The test instrument should indicate full voltage (230V) between Line-Neutral and Line-
Earth conductors. No voltage should be detected between Neutral-Earth.
The requirements for polarity test are:
This test must be done with the supply disconnected and may be carried out as
follows:
Remove circuit FUSE or open MCB. Remove all lamps from relevant circuit. Connect
one end of the long trailing lead to the outgoing terminal of the circuit MCB. Using
the other end in conjunction with the test meter leads, take readings from the phase
terminal at all the points around the circuit e.g. switches and ES lamp holders.
Continuity (approx. resistance of conductor involved) at each point ensures that
polarity is correct.
If the supply is disconnected from the installation the long trailing lead may be
connected to the phase busbar and the MCB should then be left in the “on” position.
Why PSC and PFC are Done?
It is important that we conduct the tests to make sure that the protective devices
installed within a circuit are rated at the correct breaking capacity. Within a
domestic installation, it is common to find 6000A (6kA) rated MCB’s installed within a
circuit. If a domestic premises is situated particularly close to a supply sub-station
and the measured external impedance (Ze) of the property was 0.03 Ohms, Ohm’s law
calculates that 7,666A may flow in the event of a fault on a 230V supply. This may
cause concern if the switch gear is only rated at 6000A.
< 75 V 55 V
≥=300 V 400 V
A possible difficulty in measuring PSC, and thus being able to use fuses or circuit
breakers with a lower breaking capacity than that suggested by the Supply Company,
is that the supply may be reinforced. More load may result in extra or different
transformers and cables being installed, which may reduce supply impedance and
increase PSC.
In terms of PFC, there is no such thing as acceptable PFC. It is what it is. When
testing on 3-phase supplies the simplest and quickest way is to take the highest PFC
reading off the single phase and double the value. Use Ohms Law to check. Fault
current readings should be very high. Anyway its result must be lower than breaking
capacity of the protective device. For example, a BS 1361 type 1 cartridge fuse has a
rating of approximately 16.5KA. The result must be lower than this at the origin of
installation.
Maintenance of Lightning Arrester
Resistance testing
Continuity testing
Ground or soil resistivity testing
Visual inspection
Visual inspection an installation should take into account the following key points and
observations recorded in the detailed inspection report:
Inspections should repeat at fixed intervals, not exceeding 12 months. If the intervals
fixed at 11 months, the system will inspect throughout every season of the year over 11
years.
The mechanical condition of all conductors, bonds, joints and earth electrodes should
check and any observations noted.
If a part is unable to inspect, this should note.
The bonding of any recently installed/added services should check.
The risk that an arrester is in the process of failing without also generating some heat
is very low. At the same time, if an arrester is damaged by lightning strike or
switching surge only days after its last thermal scan, it may well fail before the next
scheduled scan. This potential for failure between successive scans is perhaps the
only major negative of thermal imaging.
Other usual tests carried out on Lightning arrestors are harmonic tests, hipot test
and insulation resistance test
Lightning protection testing would make sure that all structures, key electrical and
electronic installations are safe from the effect of lightning strike.
The financial benefits are determined as follows: how does the total annual cost for a
lightning protection system compare to the costs of potential damage without a protection
system? The cost evaluation is based on the expenditures for the planning, assembly, and
maintenance of the lightning protection system.
Statistics show the UK alone subjected to around two million strikes per year and, to
make sure your lightning protection system is functional when called upon, bearing in
mind you have no way of determining when that any maintenance work should be
carried out with suitable expediency.
In the hands of experienced engineers, proper testing and maintenance of lightning
protection systems can become a routine, but very necessary, part of a
comprehensive safety programme. At the very least the consequences of not taking a
thorough approach could incur unnecessary costs but, given the destructive potential
of a lightning strike, those consequences could be much worse.
All lightning protection systems and static earthen systems must inspect and test by
skilled person using calibrated test equipment. Complete lightning protection testing
would make sure that all structures, key electrical and electronic installations are
safe from the effect of lightning strike.
LEARN HOW INSULATION RESISTANCE
TEST IS DONE
Developed early in the 20th century, the insulation resistance (IR) test is the oldest
and most widely used test for assessing the quality of insulation. The Insulation
Resistance Test is the second test required by the electrical safety testing
standards. The Insulation Resistance Test consists in measuring the Insulation
resistance of a device under test, while phase and neutral are short circuited
together. The measured resistance has to be higher than the indicated limit from the
international standards. A megohmmeter (also called insulation resistance tester,
teraohmmeter) is used to measure the ohmic value of an insulator under a direct
voltage of great stability.
Insulation cannot be perfect in the same way that something cannot be frictionless.
This means that there will always be a little bit of current travelling through. This is
known as “leakage current”. It’s acceptable with good insulation, but if the insulation
deteriorates, leakage can start causing trouble. So what makes “good” insulation?
Well, it needs a high resistance to current, and it needs to be able to sustain high
resistance for a long time
This wear and tear can reduce the electrical resistivity of the insulating materials,
thus increasing leakage currents that lead to incidents which may be serious in terms
of both safety (people and property) and the costs of production stoppages. Thus it’s
important to identify this deterioration quickly so that corrective steps can be
taken. In addition to the measurements carried out on new and reconditioned
equipment during commissioning, regular insulation testing on installations and
equipment helps to avoid such incidents through preventive maintenance. These tests
detect ageing and premature deterioration of the insulating properties before they
reach a level likely to cause the incidents described above.
This test is often used as a customer acceptance test, with minimum insulation
resistance per unit length often specified by the customer. The results obtained from
IR Test are not intended to be useful in finding localized defects in the insulation as in
a true HIPOT test, but rather give information on the quality of the bulk material used
as the insulation.
Wire and cable manufacturers use the insulation resistance test to track their
insulation manufacturing processes, and spot developing problems before process
variables drift outside of allowed limit.
Voltage Level IR Tester
The voltmeter input, associated to a resistance, forms the shunt ammeter circuit.
This setting allows measuring any value of I, many combinations of sensitivity and
values of RI. This circuit is used for current measurement of high values which
correspond to resistance measurement of low values.
This circuit is the one mostly used on our instruments. It covers the resistance
measurement of high values.
Indeed the value of a high resistance depends of the voltage applied to it. Other
factors intervene in the high value resistance measurement. Temperature and relative
humidity are two important parameters which influence the resistance value of an
insulator.
Capacitance Charging Current: Current that starts out high and drops after the
insulation has been charged to full voltage (much like water flow in a garden hose when you
first turn on the spigot).
Absorption Current: Also an initially high current which then drops (for reasons
discussed under the section Time-Resistance Method).
Conduction or Leakage Current A small essentially steady current both through and
over the insulation.
About Megger:
Electrical shock
Mechanical/physical injury
Low voltage/high energy
Fire
Although additional safety requirements are also included in most safety standards,
these four hazards are the foundation upon which all safety standards are based.
Electrical shock and its effects can be caused and influenced by several factors. The
primary effect is the result of electrical current passing through the human body.
Severity of the injury to the human body is directly affected by such variables as: the
nature of the electrical voltage (AC vs. DC); the pathway through the human body;
conductivity of the contact (wet or dry); the size and shape of the individual
involved i.e., the person’s impedance), duration of the contact, and the size of the
contact area. All these affect the magnitude of current that flows through the
person’s body.
Most safety standards address the shock issue by incorporating requirements that
instructs appropriate product enclosures: connectors that do not allow direct user
access, good dielectric or insulating barriers, as well as very low leakage current. Not
all voltage potentials, however, are considered hazardous. Some are considered safe
for user contact because of the low levels at which they operate. Since the standards
are very specific about these limits, manufacturers must be careful to test their
products against the right product standard to be sure that the products are safe.
1. Dielectric Withstand / Hipot Test: Withstand test apply high voltage on power
and ground terminal circuit of product to measure its collapse status.
2. Isolation Resistance Test: Measure product electrical isolation status.
3. Leakage Current Test: Inspects whether leakage current of AC/DC power flows
to ground terminal is over standard.
4. Protective Ground: Inspect whether metal mechanics of accessible part surely
grounding.
Following are the basic tests we conduct during electrical safety testing:
The purpose of ground protection test is for protecting users from electrical hazards
from touching equipment when unsuitable current is created and flows to the earth.
The test method of ground continuity is inputting 1 ampere DC current to power
terminal for confirming the resistance value between two ends is lower than 1Ω.
Ground bond test is to inputting 25A or 1.5 times rated current to power terminal and
check resistance values are lower than 100mΩ.
This test will ascertain whether the earth continuity between the earth supply to the
equipment and the internal component earth connections and the metal casing of the
equipment are earthed correctly.
Electrically isolate power supply at fused spur switch and remove fuse. (Always
ensure the boiler is fused at 3 amps on completion of work).
Set Multimeter on ohms scale for resistance readings.
First put black lead from Multimeter to the retaining screws of the fused socket
connection and then the red lead from the multi meter to the boiler casing.
The resistance reading must be no more than 1 ohm and whenever the resistance
reading proves to be more than 1 ohm, there is a fault present and must be traced
and rectified before proceeding any further. Check all the earth wires for continuity
and check all connections are secure.
Poor grounding not only increases the risk of equipment failure; it is dangerous.
Facilities need to have adequately grounded electrical systems so in the event of a
lightning strike, or utility overvoltage, current will find a safe path to earth.
Simple grounding systems consist of a single ground electrode driven into the ground.
The use of a single ground electrode is the most common form of grounding and can
be found outside your home or place of business. Complex grounding systems consist
of multiple ground rods; connected mesh or grid networks; ground plates; and ground
loops. These systems are typically installed at power generating substations, central
offices, and cell tower sites.
Warning: Poor earth continuity or no earth continuity at all will create a dangerous
situation, as any metal parts that should be earthed may become live and a short
circuit may cause an electric shock
1. Charge
2. DWELL
3. Test
4. Discharge
This is the simplest of the tests. After the required connections are made, you apply
the test voltage for a period of one min. (The one-min interval is an industry practice
that allows everyone to take the reading at the same time. In this way, comparison of
readings will be of value because, although taken by different people, the test
methods are consistent.) During this interval, the resistance should drop or remain
relatively steady. Larger insulation systems will show a steady decrease, while smaller
systems will remain steady because the capacitive and absorption currents drop to
zero faster on smaller insulation systems. After one min, read and record the
resistance value.
The Insulation Resistance Test consists in measuring the Insulation resistance of a
device under test, while phase and neutral are short circuited together. The
measured resistance has to be higher than the indicated limit from the international
standards. The measured resistance indicates the condition of the insulation between
two conductive parts. An infinite resistance would be the perfect result, but no
insulator is perfect, so the higher the reading the better. To perform the tests
needed, you will need an Insulation Resistance Tester or a multifunctional tester such
as Megger.
You can use it as:
Obviously, it’s a good idea to have a basic familiarity with the item you’re testing.
Basically, you should know what is supposed to be insulated from what. The
equipment you’re testing will determine how you hook up your meghommeter.
When performing insulation resistance testing, you must maintain consistency. Why?
Because electrical insulation will exhibit dynamic behavior during the course of your
test; whether the dielectric is “good” or “bad.” To evaluate a number of test results
on the same piece of equipment, you have to conduct the test the same way and
under the relatively same environmental parameters, each and every time. Your
resistance measurement readings will also change with time. This is because
electrical insulation materials exhibit capacitance and will charge during the course
of the test. This can be somewhat frustrating to a novice. However, it becomes a
useful tool to a seasoned technician.
Leakage Current Test or a line voltage leakage current test simulates the effect of a
person touching exposed metal parts of a product and detects whether or not the
leakage current that would flow through the person’s body remains below a safe
level. A person typically perceives current flow through his body when it reaches or
exceeds 1mA (one thousandth of an ampere). Current above the threshold can cause
an uncontrolled muscular spasm or shock. The leakage current is measured by
applying a fixed voltage and measuring the voltage across the shunt that is a result of
the leakage current. The reference design uses different switchable shunt resistances,
which are switched on in a sequence to measure the insulation resistance. When there
is a dead short, the insulation resistance is 0 Ω and a full current (or maximum) can
pass through the insulation resistance. At this point in the measurement having a
smaller shunt value (by turning on all of the switches) is mandatory. In the other case,
when the insulation is higher, a higher shunt value is required. The leakage current
flowing through the shunt or shunts is measured using a current shunt monitor
Running your generator efficiently is the key to ensuring its longevity and avoiding
unnecessary downtime. Standby generators can remain unused for long periods of
time, awaiting a power cut before smoothly intercepting it. Even a regular no-load
test leaves the standby generator prone to faults incurred through underuse or
neglect.
These diesel standby generators that run rarely and or lightly loaded can build up fuel
deposits in parts of the engine over time, which may leave your standby generator
with reduced output capacity when it is needed. Policies. Things like light loading a
generator or neglecting scheduled maintenance can lead to unexpected operating
costs, excessive wear and increased emissions
A load test in this situation will ensure that your standby generator will support your
load when the occasion arises. Annual load testing is imperative to confirm your
generator is capable of handling the demanded load when necessary, and some
insurance companies demand it as part of their
Most importantly, though, regularly scheduled maintenance will help to make sure
that your generator is ready when it’s called upon. For some applications, such as
data centres, blood banks and hospitals, emergency power generators simply cannot
afford to fail. That’s why preventative maintenance techniques like load bank testing
are vitally important.
In fact, load bank testing is a mandatory requirement for some backup power
generation applications. Emergency power generation systems fall under a number of
regulatory oversight conditions and code requirements. The National Fire Protection
Agency (NFPA) and the National Electric Code (NEC) have both drafted rules which
pertain directly to the load bank testing of emergency generators.
To make sure the generator will perform as designed, when it is needed most. This is
the only true way to check the performance of the generator. A load test will allow
verification that the generator system will produce and maintain full load without
overheating and shutting down. It also allows testing of all components of the system, to
ensure all work together as designed and intended and can help identify any potential
weaknesses in controlled conditions. This allows proactive maintenance, as weaknesses are
identified during controlled conditions, not during a utility outage when a weakness can cause
the system to fail.
The load can come from building load, but that may cause business interruptions when
transferring from utility to generator. It also does not allow the load to be applied in steps,
where performance can be monitored and recorded. Generally, utilizing a portable load bank
is the preferred method of load testing a generator system.
Most generator systems are programmed to exercise on a regular basis. Typically this
exercise period is under no (or very little) load. Monitoring the exercise period to ensure the
generator starts and runs as programmed is also important, but does not ensure the generator
will operate as designed.
Most generator systems are installed and then put into automatic mode. As the
generator ages, the possibility of weaknesses in the system will rise. Among other potential
enemies, weather, pests and age can negatively affect the efficiency of a generator system. A
good planned maintenance program that includes load testing is the best way to spot and
minimize potential weaknesses in a generator system.
In addition, because many of the installed generator systems that utilize a diesel
engine present another challenge. That challenge is referred to as wet-stacking. If not
addressed, wet-stacking will degrade the performance of the system and not allow the system
to operate as designed. Many systems are designed with some redundancy on load or for
future expansion. This means many systems are not loaded appropriately to eliminate wet-
stacking. At a minimum, I recommend all diesel system be load tested with a portable load
bank for a minimum of two hours, annually. If a diesel system hasn’t been load tested in over
a year, longer testing may be required. This annual testing will reduce the impact wet-
stacking will have on a generator system.
A good planned maintenance program that includes regular load testing should be a
standard component of a generator system. The regular testing of the system will
provide the highest comfort level that when the system is required, it will operate as
designed.
Start and run the generator until the water temperature stabilizes.
Transfer all manual or automatic transfer switches to the emergency source.
Step load the generator with the load bank until the desired load is reached.
Remove the load bank load first, after the test.
Transfer all transfer switches back to the normal position.
Allow the generator to cool down according to manufacturers’ guidelines.
Load Banks:
Load Banks are electrical devices that are temporarily wired into a generators AC
voltage output. Load is applied to the generator through switches that are calibrated
to produce specific Kilowatt (Kw) output. This allows the operator to apply specific
load steps during the testing process to match the generators rated capacity.
A load bank test ensures that your generator will run property when it’s needed so
that you can depend on its proper operation during an actual emergency situation.
The key to a proper load bank test is that your generator operates and maintains its
full kilowatt (kW) output rating. Most generators do not operate at their full kW
rating during their routine exercising.
It is especially important that you verify your generator can actually produce the
highest possible horsepower that may be called upon to produce. Only through this
type of testing can you verify your unit’s proper operation of recommended
temperature and pressure levels throughout the full range of operational status.
By adding the building load first you will not be in danger of losing power to the
building loads in case of a normal power failure…the building will already be on its emergency
source.
Follow lockout/tagout procedures and wear PPE as prescribed by NFPA 70E and OSHA
regulations as found in 29 CFR 1910 Subpart S. No person should be exposed to a live bus
without wearing the proper levels of PPE.
Wet-Stacking
When a diesel engine powered generator is not used frequently or only run on light
loads, it can be prone to experiencing unburned fuel and soot build-up in the exhaust
system. This is called ‘wet-stacking.’ When wet-stacking occurs, the genset is likely
to perform poorly, to endure damage, can become a fire hazard, and can even lead to
complete failure. During a load bank test, the generator is allowed to run at full
power and full temperature. This will cause any wet-stacking to burn off. Hence, a
load bank test actually serves two purposes:
It tests the generator to determine whether it will function properly and efficiently on
all levels; and
It eliminates any wet-stacking that may have built up within the generator.
Carelab’s load bank testing removes the issue of unburned fuel build-up by permitting
your generator’s engine to reach its maximum operating temperature. As a result,
your standby generator operates more efficiently, thereby guaranteeing the unit is
working exactly as it was designed to do. Regardless of whether your generator’s
engine is fuelled by diesel or natural gas, it can benefit remarkably from our load
bank testing service.
Carelab’s load testing of generator sets is a wide-ranging service that monitors every
critical component of your generator, including the engine temperature as well as the
oil pressure. Throughout the testing process, we wisely oversee the entire unit,
ensuring that it is run at normal operating pressures and temperatures once optimal
levels are achieved. As part of this service, we provide you with a broad report that
includes all your generator’s output readings % load, kW meter, engine speed, power
factor, frequency meter, lube oil pressure, water temp, ambient room temp, oil
temp, battery voltage, fuel pressure and fuel level as well as any comments and
recommendations. As a plus when Carelab’s operates, you will experience
no disruption to your facility’s operating schedule during the testing process.
Step 1: Use an Earth Fault Loop Tester or select the Earth Fault Loop Test option on a
multifunctional tester such as the Megger 1553.
Step 2: Test on the incoming side of the installation. Connect one test lead to the Line
terminal, the second test lead to the Neutral terminal and the third (usually green) test lead
to the incoming Earth conductor.
Step 3: Press the TEST button. The measurement should be a low reading ohm value.
Do not forget to record this value of `Ze` on the Electrical Installation Certificate.
Having obtained the `Ze` value for the installation, the value of `Zs` can be easily
calculated for every circuit.
The maximum measured earth fault loop impedance (Zs) values recorded should be
compatible with the Ze + R1 + R2 value of each circuit, irrespective of the
requirements of the respective protective device(s). Test results measured using low
current tests are not recorded on schedules of test results, it is preferable to record
the Zs values calculated from individual test results i.e.
The formula for determining Zs:
Zs=Ze + (R1+R2)
Zs – earth fault loop impedance of the circuit tested
Ze – earth fault loop impedance external to the supply
(R1+R2) – Sum of the resistance of Line and Earth for the tested circuit.
Where Ze is derived from a high current test and R1 + R2 obtained during continuity
testing of the circuits. The type of test results recorded and the test method used will
be indicated in the appropriate remarks column of the test results schedule.
The Zs earth fault loop impedance is tested at the furthest point of each circuit. In
most cases the circuit breaker needs to be bridged out. The total earth fault loop
impedance is measured by plugging a loop tester into a socket outlet, or in some
cases with an external earth probe. The value of the earth fault loop impedance is
the sum of the resistances. When using an external earth probe, the earth fault loop
impedance is measured by touching an external probe directly to an earth bar,
collector and connection point of an earth bar. The same measurement can be done
by touching the earth probe to exposed, conductive parts of equipment in the circuits
and exposed metal parts.
The Earth Fault Loop Test Sequence:
Step 1: Locate the furthest point on the circuit to be tested (such as the furthest
socket)
Step 2: With the appropriate Earth Fault Loop Tester, connect the test leads to the
Line, Neutral and Earth terminals.
Step 3: Measure and write down the test results on the Schedule Of Test Results.
If the circuit is RCD protected than you will have to select the “No trip” function of
the Megger 1553 to avoid nuisance tripping of the RCD. If your tester does not have this
option then you will have to link out the RCD.
Having obtained the value of Zs for every circuit, you will be expected to verify that
these values are within the accepted limits described by BS 7671.
This is the traditional loop impedance test. Using a test current of up to 20 A and a
simple 2 wire connection, it is by and large the fastest, most accurate test available
on a day to day basis. Most standard loop impedance testers will incorporate this
type of test. Because of the relatively high test current, the readings are not
generally influenced by external factors and will return repeatable, stable readings in
most scenarios.
A DC test current was injected in to the circuit prior to carrying out a standard 2 wire
high current test. The aim of this DC test was to saturate the monitoring coil within
the RCD, allowing enough time for the high current AC test to be carried out.
However, due to the increase in electronic RCDs, this method now has limited
applications
3-wire “No-Trip” test
This test method overcame the need to by-pass even the new electronic protection
devices by utilising a low current Line-Earth test current, whilst still returning a
degree of accuracy. Not having to by-pass the RCD/RCBO obviously introduced a time
saving factor. In addition, by having the requirement of connecting to Line, Neutral
and Earth, the testers were now able to confirm the presence of all three as well as
indicate if there was a reverse polarity at the test point and, due to the limited test
current, there was no issue with tripping the MCB.
They allow testing most RCDs and RCBOs without having to bypass them. With no
neutral connection required, they maintain a true 2-handed operation, but will no
longer indicate reverse polarity or warn of a missing neutral. Although the physical
test time is similar to that of the 3-wire method, the time saving of not having to
bypass the RCD still makes for a more efficient test.
The test uses a 4 wire Kelvin connection, negating internal lead and contact
resistance; such is the accuracy of the test. With test currents up to 1000 A,
measurements down as low as 10 MOhm can be accurately made. Consequently, there
is no “No-Trip” option with this test method. With specific applications being
measurement in sub-station/switch room environments, this tester gives the test
engineer the ability to take accurate readings.
A circuit protected by an RCD will need special attention, because the earth-fault
loop test will draw current from the phase which returns through the protective
system. Thus testing of circuits protected by RCDs has presented instrument
manufacturers’ with difficulties in providing test results similar to that of the testing
of non-RCD protected circuits, without tripping the RCDs during the tests. Therefore,
any RCDs must be bypassed by short circuiting connections before earth-fault loop
tests are carried out. It is, of course, of the greatest importance to ensure that such
connections are removed after testing.
At Carelabs we use an earth loop impedence tester that will not trip out the circuits
RCD that we are testing. Our team will conduct all tests and inspections according to
the current safety standards. Testing is mandatory for the safety of all employees.
Get tested today to make sure your workplace is safe – we’re here to assist with all
your compliance requirements
Since the test result is dependent on the supply voltage, small variations will affect
the reading. Thus, the test should be repeated several times to ensure consistent
results. Anyone on site must avoid shock hazard while establishing contact and while
doing the test. When buying a loop tester ask for distribution board test leads so that
Ze and Zs measurements can be done.
Impedence value:
Earth Fault Loop Impedance Testing and Recording Earth fault loop impedance testing
is carried out on a completed electrical installation to check compliance with BS 7671
(IET Wiring Regulations) with regard to fault protection and is normally carried out as
follows:
1. With a test current of approximately 23A where circuits are protected by overcurrent
devices such as fuses or circuit breakers only; or
2. With a test current of approximately 15mA, to prevent unwanted tripping where
circuits are protected by 30mA or other RCDs.
Typically test results for high current (23A) tests in the range 0.1Ω to 1.0Ω are largely
stable with a resolution of 0.01Ω. For low current (15mA) tests the resolution was
0.1Ω, but attempts to decrease this to 0.01Ω have been largely unsuccessful in
providing the same stable results for readings of less than 1.0Ω.
A recent study by one of the UK leading instrument manufacturers using instruments
from seven different manufacturers under controlled conditions found significant
discrepancies in the instrument readings. Further investigation revealed that the
problem appeared to be mainly with the low test currents, caused by variations in
power supply quality created by voltage magnitude, transients, harmonics etc. Similar
tests carried out using a stabilised power supply with a clean 50Hz waveform
produced more consistent results. It should however, be noted that these
discrepancies, usually in the order of 1.0Ω or less, are not significant in terms of the
correct operation of an RCD.
After testing is complete, we will give you a retest date (for your next earth loop
impedance test) that complies with the national standards. When the time comes, our
team will notify you of the retest. All results will be documented in a detailed report
that is supplied to each client. Within this report, your equipment will be assigned
either a pass or a fail. This document will be kept on file should you need to access it
in the future for compliance verification. We provide a wide range of inspection and
testing services to clients so that you can secure your entire workplace in one visit.
After you’ve had your impedance test, we can provide you other inspection services
too. With such a wide variety of services, there’s no reason to go elsewhere for your
safety testing requirements.
Earth fault loop impedence testing is a way of insuring that you have made an
electrically safe ground connection having a suitably low residual resistance. Earth
loop impedance testing is essential since if a live conductor is accidentally connected
to an earth conductor in a faulty appliance or circuit, the resulting short-circuit
current to earth can easily be high enough to cause electric shock or generate enough
heat to start a fire. Normally, the fuse will blow or another circuit protection device
will trip, but a situation may arise where the actual short-circuit current in a faulty
installation is of insufficient level and the protection device would thus take too long
to activate. The delay can be disastrous for life and property. It is therefore
necessary to know if the impedance of the path that any fault current would take is
low enough to allow sufficient current to flow in the event of a fault and that any
installed protective device will operate within a safe time limit.
Arc Flash is an energy release that takes place when electricity flows through the air
and two live conductors causing short circuit. In a residential setting, arc flashes
usually produce little more than a brief flash of light before extinguishing themselves
harmlessly. In commercial or industrial setting, voltages are high, so electrical faults
usually release high energy. As a result, arc flashes in data centers routinely produce
powerful explosions marked by searing heat, toxic fumes, blinding light, deafening
noise and massive pressure waves.
Electrical safety testing is essential to ensure safe operating standards for any
product that uses electricity. Various governments and agencies have developed
stringent requirements for electrical products that are sold world-wide. Several tests
are conducted to check the safety of products. One among that is earth test.
Potentially the most dangerous appliances are Class I appliances (earthed appliances),
example: microwave ovens/bench grinders and the like, but also in this category are
extension leads. Class I appliances are designed to have a connection to the ground
via an earth conductor. This may, or may not, be a suitable low resistance path for
electric current to protect personnel and equipment. If this conductor is damaged
anywhere then the consequences can be virulent.
Why is Earth Ground Testing Needed?
The measurement of ground resistance for an earth electrode system should be done
when the electrode is first installed, and then at periodic intervals thereafter. This
ensures that the resistance-to-ground does not increase over time. The International
Electrical Testing Association specifies ground electrode testing every three years for
a system in good condition with average up-time requirements.
Poor grounding not only increases the risk of equipment failure; it is dangerous too.
Facilities need to have adequately grounded electrical systems so in the event of a
lightning strike, or utility overvoltage, current will find a safe path to earth. Although
the ground system when initially installed had low earth ground resistance values, the
resistance of the grounding system can increase if the ground rods are eaten away by
corrosive soils with high moisture content, high salt content, and high temperatures.
If our technician finds an increase in resistance of more than 20 percent, we will
investigate the source of the problem and make the correction to the grounding
system to lower the resistance.
A plant or other electrical facility can expand in size. Also, new plants continue to be
built larger and larger. Such changes create different needs in the earth electrode. What was
formerly a suitably low earth resistance can become an obsolete “standard.”
As facilities add more modern sensitive computer-controlled equipment, the problems
of electrical noise is magnified. Noise that would not effect cruder, older equipment can
cause daily problems with new equipment.
As more non-metallic pipes and conduits are installed underground, such installations
become less and less dependable as effective, low-resistance ground connections.
In many locations, the water table is gradually falling. In a year or so, earth electrode
systems that formerly were effective may end up in dry earth of high resistance.
Limiting to definite values the voltage to earth of the entire electrical system. Use of
a suitable grounding system can do this by maintaining some point in the circuit at earth
potential. Such a grounding system provides these advantages:
o Limits voltage to which the system-to-ground insulation is subjected, thereby
more definitely fixing the insulation rating.
o Limits the system-to-ground or system-to-frame voltage to values safe for
personnel.
o Provides a relatively stable system with a minimum of transient over-voltage.
o Permits any system fault to ground to be quickly isolated.
Proper grounding of metallic enclosures and support structures that are part of the
electrical system and may be contacted by personnel. Also to be included are portable
electrically operated devices. Consider that only a small amount of electric current — as little
as 01 A for one second — can be fatal! An even smaller amount can cause you to lose muscular
control. These low currents can occur in your body at voltages as low as 100 V, if your skin is
moist.
Protection against static electricity from friction. Along with this are the attendant
hazards of shock, fire and explosion. Moving objects that may be inherent insulators – such as
paper, textiles, conveyor belts or power belts and rubberised fabrics – can develop
surprisingly high charges unless properly grounded.
Protection against direct lightning strokes. Elevated structures, such as stacks, the
building proper, and water tanks may require lightning rods connected into the grounding
system.
Protection against induced lightning voltages. This is particularly a factor if aerial
power distribution and communications circuits are involved. Lightning arresters may be
required in strategic locations throughout the plant.
Providing good grounds for electric process control and communication circuits. With
the increased use of industrial control instruments, computers, and communications
equipment, accessibility of low resistance ground connections in many plant locations — in
office and production areas — must be considered.
Resistance to earth can vary with changes in climate and temperature. Such changes
can be considerable. An earth electrode that was good (low-resistance) when
installed may not stay that way; to be sure, you must check it periodically. We cannot
tell you what your maximum earth resistance should be. For specific systems in
definite locations, specifications are often set. Some call for 5 Ω maximum; others
accept no more than 3 Ω. In certain cases, resistances as low as a small fraction of an
ohm are required.
Electrode Resistance: Rods, pipes, masses of metal, structures, and other devices are
commonly used for earth connections. These are usually of sufficient size or cross-
section that their resistance is a negligible part of the total resistance.
Electrode-Earth Contact Resistance: This is much less than you might think. If the
electrode is free from paint or grease, and the earth is packed firmly, contact
resistance is negligible. Rust on an iron electrode has little or no effect but if an iron
pipe has rusted through, the part below the break is not effective as a part of the
earth electrode
Resistance of Surrounding Earth: An electrode driven into earth of uniform resistivity
radiates current in all directions. Think of the electrode as being surrounded by shells
of earth, all of equal thickness. The earth shell nearest the electrode naturally has
the smallest surface area and so offers the greatest resistance
Under these circumstances, if conditions 1 and 2 above are met, you can connect to
the water-pipe system and obtain a suitable earth electrode. As a precaution against
any possible future changes in the resistance of the water-pipe system, however, you
should also install an earth electrode.
Clamp-on Method:
Fall-of-potential testing, and its modifications, is the only ground testing method that
conforms to IEEE 81. It is extremely reliable, highly accurate and can be used to test
any size ground system. Additionally, the operator has complete control of the test
set-up and can check or proof his/her results by testing at different probe spacing.
Unfortunately, the Fall of Potential method also comes with drawbacks:
It is extremely time consuming and labour intensive.
Individual ground electrodes must be disconnected from the system to be measured.
The clamp-on ground testing method, although it does not conform to IEEE 81, does
provide the operator with the ability to make effective measurements under the right
conditions. The clamp-on methodology is based on Ohm’s Law (R=V/I). A known
voltage is applied to a complete circuit and the resulting current flow is measured.
The resistance of the circuit can then be calculated. The clamp-on ground tester
applies the signal and measures the current without a direct electrical connection.
The clamp includes a transmit coil that applies the voltage and a receive coil that
measures the current.
Selective Measurement Testing:
Selective testing is very similar to the Fall-of-Potential testing, providing all the same
measurements, but in a much safer and easier way. This is because with Selective
testing, the earth electrode of interest does not need to be disconnected from its
connection to the site! The technician does not have to endanger himself by
disconnecting ground, nor endanger other personnel or electrical equipment inside a
no grounded structure.
Switchgear Thermography
A great deal of investment is presently being made installation of thermal viewing
ports for switchgear. These ports allow infrared inspections to carry out without
removing switchgear covers, thus it would avoid worker arc-flash exposure.
Installation of permanent infrared sensors and continuous infrared monitors are also
reasonable methods for recognizing potential thermal failures of critical equipment.
The principle of outdoor switchgear assemblies is often compromised by defective
strip heaters. The strip heaters increase the switchgear temperature slightly above
ambient to prevent condensation during daily or seasonal temperature changes.
Functionality of these strips heaters and their effectiveness to carry out this duty can
decide by carrying out thermal imaging of the switchgear enclosures. In other words,
and once again, absence of heating identifies a potential problem.
Determines if the elements and system have been properly installed and are
not damaged
Reduces downtime
Reduces risk of equipment failure
Increases safety
Improves insurability
Reduces liability exposure of the designers and installers
Improves system performance
Determines elements and systems carry out properly and meet the design
intent
Determines if elements and systems compliance with the project specifications
and design
Reduces construction schedule delays
Saves money
1. A test is an active demonstration that the EPSS is still able to function as intended. If a
switch is going to fail to transfer, it’s better to have the switch fail while connected to a live
normal source during a test than to have it remain connected to a dead normal source during
an actual power outage.
2. An automatic transfer switch is an electromechanical device with moving parts. Like
the pistons and crankshaft in an automotive engine, the moving parts in an ATS can seize if
they’re left in one position for months or years. Regular exercise will help ensure that moving
parts will continue to operate smoothly.
3. A transfer switch test transfers building load onto the generator for the duration of
the generator test. Most standby power generators of more than 100kW are diesel engine
driven, and all major diesel generator manufacturers recommend a load of at least 50% of
maximum capacity during monthly generator tests. NFPA requires the same thing, for the
simple reason that running under a light load is very bad for a diesel engine.
There are several ways of mitigating or eliminating the problems caused by these
power interruptions, both in new construction and in existing facilities:
Check wiring and connections are tight with no discoloration of metal, melted plastic
and odour indicating excessive heat.
Verify external operating mechanism is clean and re lubricate if found dirty.
Check for any deterioration of wiring insulation such as cuts and abrasions. Replace or
repair any damaged wiring.
Check tightness of wiring connections. Retighten to specification if any loose wiring
found.
Perform insulation resistance tests on all control wiring with respect to ground.
Perform a contact/pole-resistance test.
Verify settings and operation of control devices.
Calibrate and set all relays and timers.
Verify phase rotation, phasing, and synchronized operation as required by the
application. .
Check ATS main power switching contacts condition. Clean or replace. Replace
contractor assembly if necessary.
Exercise the generator set under load.
Test the transfer switch’s automatic control system.
Test all indicators (LEDs) and all remote control systems for operation.
Inspect the outside of the transfer switch for any indication of wear, excessive
vibration, leakage, high temperature, contamination or other deterioration.
Verify all external components are in place, firm, tightened and not excessively worn.
Inspect the inside of the transfer switch for any indication of excessive vibration,
leakage, high temperature, contamination or any other deterioration.
Verify all internal components are in place, firm, tightened and not excessively worn.
LIVE TESTING
Live Testing or Live working shall be defined as the practice of working on parts of
the electrical system while the part in question is still live. This may or may not
include the removal of covers or protective devices without isolating the means of
supply during such an operation. The safest way to conduct electrical work is to shut
off electric power and work on de-energized equipment. However, there may arise
extraordinary circumstances that necessitate work on energized equipment. Live
testing helps ensure all electrical apparatuses within the circuit are set within their
respective recommended electrical polarities for continuous flow of electrical energy.
Live working may not be undertaken unless the following applies (as prescribed by
“The Electricity at Work Regulations” regulation 14):
We require a polarity test to ensure that all single pole devices (fuses, switches and
circuit breakers) are connected in the PHASE conductor only. We cannot simply trust
that the electrician(s) have connected things up the right way; everyone makes
mistakes, even if it’s your own work. “Basically it is a test that creates a circuit using
the phase conductor and the single pole device in question, breaking the circuit when
operating the device, means that the reading on the instrument will change, and thus
confirming that that device must be connected in the phase conductor.
It ensures apparatus connected to the circuit is connected correctly, and does not
become damaged. Plug in tester, and ensure the polarity is correct according to the
charts on the test instrument. (Varies from tester to tester)
The main reason for earth loop impedance testing – which is often simply called loop
testing – is to verify that, if a fault occurs in an electrical installation, sufficient
current will flow to operate the fuse or circuit breaker protecting the faulty circuit
within a predetermined time. i.e.; ensure the resistance of the earth cable is not so
high as to prevent it from working correctly in the event of a fault. The objective is to
make sure that the circuit is disconnected fast enough to prevent overheating and
possibly a fire.
To perform the test plug in the instrument, set the range to the lowest setting first
and press test, then record the result.
Three-wire no-trip testing is one of the method used in earth loop impedance testing.
It requires connections to be made to the live, neutral and earth conductors, and
typically uses a test current of 15 mA or less. Its benefits are that there is no need to
bypass RCDs and RCBOs during testing, which saves time, and that it does not trip
MCBs. There are, however, a few limitations.
It helps to ensure that in the event of a short circuit, the cable tested can carry
enough fault current, to trip the MCB or blow a fuse, as quickly as possible (and
within the stated regulation guideline times of 0.4 seconds for socket outlets
(portable equipment) and 5 seconds for fixed equipment). A PSC test calculates the
current that will flow in the event of a short circuit fault between the live
conductors. That is, Line and Neutral on a single phase installation or Line to Line/
Line to Neutral on a three phase installation. Result should be recorded in hundreds of
amps.
Residual Current Device Test
RCD testing is the process of safely “tripping” your RCD to ensure it will operate
quickly should there be an electrical incident. This is also known as safety switch
testing. Your RCD is designed to trip, or switch off all the power to that circuit. It is
done to ensure that the RCDs installed will trip fast enough in the event of a fault, to
prevent electrocution.
To do RCD testing plug in test equipment (set at the rating of the RCD), and set the
test at 0.5 of the RCD’s rated tripping current – the RCD must not trip out. Repeat the
test at the rated tripping current of the RCD, the device should trip out in around 0.3
of a second. Repeat the test again, setting the test at 5 times the rating of the RCD,
the RCD must trip faster than the last result (even though only slightly)
To make sure that your facility is safe to use, its advised to ensure that the electric
circuit, which is exposed to conditions likely to cause deterioration and consequent
danger, and is supplied at a voltage in excess of 125 volts AC, undergoes a periodic
check by certified authority like Carelabs, so we can establish the ongoing safety of
the electrical equipment. While live testing may be required in order to find the
fault, live repair work must not be carried out. The individual circuit or item
of equipment must first be isolated.
Carelabs is authorized provider of Electrical Installation’s Study, Analysis,
Inspection, and Certification services in UAE, and provide live testing service.
Many a times it has been seen that an electrical short circuit has been the reason
behind a fire breakout in a house. These short circuits are caused by different loose
wires in the meter or in the cabling itself. During the inspection, the inspector can
easily recognize these faults and ask you to rectify them.
Shocks
IEC 60335 is the most widely applied standard for electrical safety testing, especially
for domestic appliances. Many safety testing standards in the world have been based
on it. To safeguard workplace health and safety, many sections of the Occupational
Health and Safety Regulation provide guidelines on electrical safety and the
appropriate equipment required to work on low and high voltage electrical
appliances.
Receptacle Type
The Receptacle Type incorporates a GFCI device within one or more receptacle
outlets. Such devices are becoming popular because of their low cost.
Portable Type
Portable Type GFCIs come in several styles, all designed for easy transport. Some are
designed to plug into existing non-GFCI outlets, or connect with a cord and plug
arrangement.
Cord-Connected Type
The Cord-Connected Type of GFCI is an attachment plug incorporating the GFCI
module. It protects the cord and any equipment attached to the cord. The
attachment plug has a non-standard appearance with test and reset buttons.
Employers provide:
Inspections/Tests:
Exceptions:
Receptacles and cord sets that are fixed and not exposed to damage
Frequency of tests:
All GFCIs shall be tested once every three months using the following procedures to
make sure they are working properly and protecting the employees from electric
shock.
To test a GFCI, first plug a test-light or shop-light into the outlet, the light should be
ON. Then press the TEST button on the GFCI , the GFCIs RESET button should pop-out and
light should go out.
If the RESET button pops out and the light doesn’t go out the GFCI has been
improperly wired.
If the RESET button doesn’t pop out the GFCI is defective and should be replaced.
If the GFCI is functioning properly, and the lamp goes out. Press the RESET button to
restore power to the outlet.
The GFCI will not protect you from line contact hazards (i.e. a person holding two
“hot” wires, a hot and a neutral wire in each hand, or contacting an overhead power
line). However, it protects against the most common form of electrical shock hazard,
the ground-fault. It also protects against fires, overheating, and destruction of wire
insulation.
Ensure that all the safety features and functions of the electrical installation
are functioning correctly.
What should be earthed is earthed and that the earth leakage relay is
operational and trips accordingly.
If your earth leakage or circuit breakers are tripping it’s actually a good sign, it
means your electrical installation is doing what it should be doing, I would be more
concerned if you NEVER have tripping problems. It could be a faulty appliance or circuit.
Very often what happens over the years is that safety features go faulty, are
deliberately disabled or by passed to “fix” a tripping problem instead of the actual fault
being traced and rectified properly.
An Electrical Installation Certificate must be issued for all new electrical installations.
It may also be required for an alteration or addition to the installation – depending
upon whether or not a new circuit has been installed. Where an alteration or addition
is carried out but does not include a new circuit, a MEIWC or an EIC may be used.
The Electrical Installation Certificate will need to be issued any time that
there is:
The Electrical Installation Certificate will be used only for the initial certification of a
new installation or for an alteration or addition to an existing installation where new circuits
have been introduced. It is not to be used for a Periodic Inspection for which a Periodic
Inspection Report form should be used. For an alteration or addition which does not extend to
the introduction of new circuits, a Minor Electrical Installation Works Certificate may be used.
The original Certificate is to be given to the person ordering the work (Regulation 742-01-03).
A duplicate should be retained by the contractor.
This certificate is only valid if accompanied by the Schedule of Inspections and the
Schedule(s) of Test Results.
The signatures appended are those of the persons authorized byx the companies
executing the work of design, construction and inspection and testing respectively. A
signatory authorized to certify more than one category of work should sign in each of the
appropriate places.
The time interval recommended before the first periodic inspection must be inserted.
The page numbers for each of the Schedules of Test Results will be indicated, together
with the total number of sheets involved.
For the proposed date for the next inspection, it should be taken into consideration
the frequency and quality of maintenance that the installation can reasonably be expected to
receive during its intended life, and the period should be agreed between the designer,
installer and other relevant parties.
You should regularly inspect, maintain and test all switchgear and its environment,
for example the switchroom. In all cases you should do this in accordance with the
manufacturer’s instructions.
Switchgear Inspection
You should inspect substations regularly. During the inspection work you should
prioritise any remedial actions as follows:
Immediately (this should always be the case when security of the substation
enclosure has been interfered with).
Earliest possible opportunity.
Next scheduled maintenance.
Important: Dielectric withstand voltage tests should not proceed until insulation-
resistance levels are raised above the recommended minimum values.
Visual/Mechanical Inspection
Insulation Resistance Test
Dielectric Withstand
Turns Ratio Tests
Excitation Tests
Burden Test
Power/Dissipation Factor
Secondary Wiring Integrity
Circuit Breaker and Switch Tests for Switchgear and Switchboards
It’s essential that circuit breakers be tested and maintained to ensure proper
operation during electrical faults. Photo: Vacuum Interrupter Testing
The procedure for the inspection/testing of circuit breakers and switches is beyond
the scope of this guide as each type and voltage class has its own procedure. Conduct
electrical tests on circuit breakers in accordance with NETA. Where applicable,
testing of circuit breakers generally include:
Visual/Mechanical Inspection
Insulation Resistance
Dielectric Withstand
Contact/Pole Resistance
Electrical Operations
Vacuum Integrity
Power/Dissipation Factor
Protective Devices and Instrument Transformers
Tip: Infrared cameras are the easiest way to verify heater functionality without
making contact with the equipment.
Electrical Safety Audit Service can be broadly classified into 3 major areas namely:
1. Pre-Audit
2. Audit
3. Post-Audit
Process details
Electrical Single Line Diagram
Name plate details of major electrical equipment
Details of classified zones in the plant
Details of flammable chemicals handled in the plant
Details of electrical accidents in the plant
Details of addition / expansion of the plant including electrical installation
Overview of electrical maintenance system
Statutory Regulations
Non-Statutory Standards (national and international)
To understand the efficiancy of the various electrical safety elements, the grouping as
indicated below will be of use. This way of grouping enables the consolidation
exercise more effective.
Earthing System
Are the protection relays in place and set in the main PCC / MCC?
Are the relays set in accordance with calculated, design parameters in mind?
Are they calibrated and tested periodically?
Availability of HRC fuses, standard fuse wires, MCBs, MCCBs, RCCBs, etc.
Are the transformer protection devices in place? (Bucholtz Relay, Oil Temperature
Relay, Winding Temperature relay, Silica Gel Breather, Explosion Vent, etc.
Normally, this part is taken up after the field visits. All the relevant
maintenance documentation, test records, electrical records, electrical inspector
reports, OEM (Original Equipment Manufacturer) service manuals,
History cards are subjected to detailed examination. All the relevant
drawings (electrical single line diagram, earthing layout, hazardous are a
classification drawings, protection system schematic, equipment layout,lightning prot
ection drawings) are also checked against actual installation and commended upon,
with reference to applicable standards
While these are not daunting requirements, all too often these basic elements are not
met when installing and commissioning an electrical power system. Poorly written
specifications and contracts, lack of understanding, budget constraints, unqualified
contractors, failure to utilize accredited testing and commissioning companies or a
host of other reasons can lead to issues with the installation and operation of the
electrical power system.
Thus the question arises: “How can the owner of the equipment ensure an unbiased
and qualified assessment of the newly installed system?” That is when third party
electrical certification comes into play.
Third Party Inspection was introduced by DCLG as a way for DIY’ers and those not
registered with a competent persons scheme to have their work checked and
certified by a local authority or a private sector approved inspector. Third-party
certification involves an independent assessment declaring that specified
requirements pertaining to a product, person, process, or management system have
been met. A third-party body is entitled by an accreditation body. Upon definition of
standards and regulations, the accreditation body may allow a Notified body to
provide third-party certification and testing services.
They not only ensure and assess compliance to the previously-defined codes but
also provide an official certification mark or a declaration of conformity. Third party
inspectors also provide periodic Inspection and testing; They perform checking on
installations previously carried out by other contractors and determines whether
the installation is in a satisfactory condition for continued service. Third party
certification should not be used for initial verification and certification of
new electrical installation work undertaken by others.
Before work begins, an installer who is not a registered competent person may
appoint a registered third-party certifier to inspect and test the work as
necessary. Within five days of completing the work, the installer must notify the
registered third-party certifier who, subject to the results of the inspection and
testing being satisfactory, should then complete an electrical condition report and
give it to the person ordering the work.
Registration is of both the individual certifier and the company that
employs them; this ensures that requirements that can only be placed on a legal
entity can be enforced. No electrical business can certify any third party electrical
work until they are registered on a Third Party Certification Scheme. Therefore
technical competencies of all electricians are checked before third party certification
is awarded.
There are 4 types of certificates (electrical safety certificates) provided by third
party inspectors:
Certification of Competency
Certification of competency is particularly important in the electrical testing
industry. Inherent in the determination of the equipment’s serviceability is the
prerequisite that individuals performing the tests be capable of conducting the tests
in a safe manner and with complete knowledge of the hazards involved. They must
also evaluate the test data and make an informed judgment on the continued
serviceability, deterioration, or non-serviceability of the specific equipment.
Electrical Installation Certificate / Domestic Installation Certificate
This is issued to the customer on the completion of any electrical installation works.
It details the type of works undertaken; any deviations from the regulations as listed
in BS 7671, who designed, installed and tested the works and when the next
inspection is due.
Code 1: Major deviation from the regulations, immediate remedial works are
required and the system is unsafe to remain in service in its present condition.
Code 2: Minor deviation from the regulations, remedial works are required to
the electrical installation, this should be carried out soon and in there, present
condition does not provide immediate danger to life or property.
Code 3: Requires further investigation.
Code 4: Third Party Electrical Certification isn’t just about winning more work
for your business. The most important issues for our members is upholding professional
installation standards within your industry. Electricians who are certified for third party
hold that responsibility in their own hands. The ability to act as a Third Party certifier
means that electrician is directly involved in ensuring that standards of competence and
professionalism in the electrical industry always meet the expected level.
Electrical equipment like motors will not function consistently on unbalanced voltages
in systems. Usually, the variance between the maximum and the minimum voltages
must not surpass four percent of the lowest voltage. Larger unbalances may lead to
overheating of components, particularly motors.
A three phase equipment such induction motor with unbalance in its windings.
Any large single phase load, or a number of small loads connected to only one phase
cause more current to flow from that particular phase causing voltage drop on line.
Switching of three phase heavy loads results in current and voltage surges which cause
unbalance in the system.
Unequal impedances in the power transmission or distribution system cause
differentiating current in three phases.
To determine the causes and effects of voltage unbalance on the distribution system
and in user facilities.
To determine the accepted definitions for calculating voltage unbalance and to clarify
the related standards.
To identify mitigation techniques for the distribution system and for industries.
Such cases will be used to confirm the impacts of voltage imbalance on systems and
equipment. Voltage imbalance not only causes extra energy loss, but also causes
safety problems for a system. To prevent voltage imbalance, the balance problem
should be taken into account through all the planning, design, installation and
operation stages. This study will provide details, with theoretical analysis and
explanation, to make it easy to grasp the impacts of voltage imbalance on systems
and equipment. The results are of value to engineers for better design, operation and
maintenance of power distribution systems
Unbalanced loads are the main cause of unbalanced voltages on distribution circuits
and thus a great deal can be gained by attempting to distribute single-phase loads equally
across all three voltage phases. Electrical distrbution systems can be balanced by changing
the system configuration through manual and automatic feeder switching operations to
transfer loads among circuits. This reconfiguration can be performed to reduce losses, and
has the natural tendency to balance loading among
Unbalanced impedances, including transformers and their connections, are often the
next largest contributor to unbalanced voltages. Therefore, proper selection of distribution
transformers is a very important step in preventing voltage unbalance, paying particular
attention to the balancing of open wye and open delta transformer banks.
If the amount of unbalance tends to vary with the customer load, it is a good
possibility that the transformer is the cause of the unbalanced condition. One way to
determine the transformer banks contribution to voltage unbalance is to measure the voltages
on the primary and the voltages on the secondary and calculate the percent unbalance at
each point.
In addition, overload conditions on the power system should always be corrected as
soon as possible for a number of protection and safety reasons as well as unbalance
compensation.
Unbalance compensation can also be achieved by means of passive power filters that
balance the load impedance, where the load current is balanced by adding reactive elements
in parallel to the load.
For variable loads, voltage unbalance in ac supply systems can be corrected by means
of a shunt connected thrysitor-controlled static VAR compensator, where again the load
current is balanced by adding reactive elements in parallel to the load.
Within a user facility, all overloaded equipment should be corrected. In addition,
passive power filters and shunt connected static VAR compensators, for mitigation on power
systems, can be used for unbalance compensation in user facilities.
Mitigation of the adverse effects of unbalanced voltage on adjustable speed drives
(ASD) can be achieved through the use of properly sized ac-line and dc-link reactors as
demonstrated in. The test results showed that connecting both the ac-line and dc-link
reactors to the ASD has the greatest effect on phase-current unbalance, reducing it by more
than half.
Various relays can be introduced to protect induction motors from unbalanced
voltages, where the relay settings and applications depend on the motor horsepower, loading,
insulation class and service factor. The negative sequence current relays are more reliable
and effective because relays measuring negative sequence voltage can lack the necessary
sensitivity in some system and load configurations
ENERGY AUDITING SERVICE
The purpose of an energy audit also known as energy assessment or energy study is to
find out why, where, how and when is energy utilised in a facility, and to discover
occasions to increase efficiency. Energy auditing services are provided by energy
services companies, energy experts and engineering organisations. The energy auditor
directs the audit process but functions watchfully with staffs, building owners and
other key participants all the way through to make sure precision of data collection
and correctness of energy efficiency suggestion.
Investigation Phase
Monitoring Phase
This phase is about getting data related to the entire site and the main energy usage
groups. The function of main plant and gear is checked, and measurement of a scale
of parameters i performed where necessary, including:
This is about:
Inspect equipment lists, utility data, building diagrams, and other property
information
Auditor gathers and review at least 2 years of utility data during the energy use
analysis to account for seasonal variations and patterns of energy use (Monthly utility bill data
is most commonly used)
All forms of energy (electricity, gas, oil, water) should be included in this analysis
From this evaluation, your facility’s Energy Utilization Index (EUI) value (annual energy
use/square footage) and energy end uses (energy used by each building system) are
calculated
The Energy Utilization Index (EUI) and base energy load allow the auditor to target this
data against energy usage of similar buildings and systems to show the magnitude of energy
efficiency options and give an early estimate of potential savings
Auditor also checks for the difference in usage of energy with time and reasons for the
same
Auditor will give an initial report which contains a summary of information and graphs
and other visuals to permit easy interpretation.
Outcomes from the study is used in determining which level of audit to run and get
data for the final report
The Site Assessment
First auditor will do a physical valuation of your property and its function
The energy auditor will also conduct a visual inspection and inventory of the building’s
key elements
Construction details of the building envelope (e.g. walls, roof, windows, doors and
related insulation values)
An inventory of the heating and cooling systems (HVAC) capacities and rated efficiency
Manual, time clock or automated HVAC control methods
Lightning systems and control (both interior and exterior)
Service hot water systems
Data Analysis
After the energy auditor has collected the necessary data for your building, they will
begin the energy and cost analysis. Before starting the analysis, the energy auditor
should have a good understanding of your economic methodology and business criteria
to ensure that the analysis is fairly compared with other investment opportunities and
that cash flows match expectations.
Energy analysis methodologies vary widely. Your project goals should inform the
analysis methodology selected to avoid results that yield too much or too little detail. Typical
analysis methodologies include spreadsheet analysis based on engineering formulas that
account for variations in time of day and season, and whole-building hourly energy use
analysis for larger buildings or buildings with complex mechanical systems.
Cost analysis considers current energy costs, measure implementation costs and
potential savings over time help to determine practicality and priority of Energy Efficient
Mortgage (EEM) recommendations. You must give the economic method that auditor will
consider for determining order of EEM implementation.
Audit Report
Audit report will constitute of sufficient data to let you make updated decisions about
next stages to tally your energy savings and financial aims.
Audit reports consists of detailed descriptions including:
An catalogue of all current gears, a record of your property’s current state and energy
utilisation
A list of suggested low-cost, no-cost, and longer-term EEM suggestions depending on
studies of historical energy usage and the onsite evaluation
Existing conditions and recommended changes, including equipment specs and specific
locations of installations
How the measure will save energy and how much energy it will save
Financial analysis outcomes i.e. expenses of suggested measures
Effects on maintenance and comfort
The report should also present optimized bundles of measures, where shorter payback
EEMs are combined with longer payback EEMs to collectively meet energy savings and
financial goals. This may be of particular interest if your facility has significant
deferred maintenance items.
Motor Starting Study and Analysis recognises the probable voltage dip and
acceleration time for a motor and the consequences of motor starting on a system. It
assesses proper starting and running of motors on load with given system inertia
without causing tripping or instability in the system. Other starting methods, such as
autotransformer start, reactor, across-the-line, capacitor, or are also studied. If
system voltage dips are a concern, Carelabs will propose the appropriate solutions.
The starting current of most AC motors is several times the normal full rated load
current when starting from full line voltage. These large current requirements can
result in nuisance tripping of protection breakers, excessive running currents, drop in
terminal voltage etc. Dimming of lights as motors start up is a clear indicator that the
power system may need investigation. It may have insufficient capacity or a better
motor starting strategy may be required.
The most serious effect of a large voltage drop or brown out is an increase in current
of all devices servicing a constant load. Static power supplies such as computers and
ballasts for lighting must increase the current to deliver the same amount of power
resulting in overheating and eventually burn-out. Other induction motors operating at
sync speed will increase their current draw until it reaches maximum current and may
slip out of sync further increasing the current demand.
Motor starting studies assists in the choice of the proper motor design, the best
method of starting and the proper system design for reducing the effect of the motor
starting. Motor starting studies are essential in determining the impact on system
voltage during starting and in establishing whether the motor will start satisfactorily
and come up to speed. The result of these studies allows engineers
Load flow type solution with the observed starting impedance of the motor modelled
as part of network modelling.
Short circuit method type of calculations considering pre-fault short circuit conditions
and using voltage drop calculations considering motor starting currents. Alternatively
Where precise dynamic model of the motor electric circuit and load – torque
characteristics are existing, dynamic model of the motor can be utilised in traditional
transient stability algorithm to evaluate the impact of the motor starting.
When there is a lack of precise model information, transient stability studies can be
utilised, where the measured starting current can be applied as a nodal injection at the
motor bus as a dynamic event and the system response to this dynamic event can be
measured.
Step 1: Motor starting analysis starts at the client site to gather current and historical
information.
Step 2: Then simulations are run using these measured data and information from the
manufacturer.
Step 3: From our computer models, we will be able to predict the operation for new
installations and to diagnosis problems and offer solutions for existing motor
installations.
Step 4: We utilise both static and dynamic techniques to create the starting sequence
of motors and normally depend on dynamic analysis to recreate observed and
measured starting conditions.
SERVICES
Search
Search for:
DUTY OF CARE
MANAGEMENT
Owing to working with the complete Electrical Engineering sector since the
establishment, together with the oil & gas industry, commercial building, infra
structure developers, CareLabs has maintained discipline, in quality standards,
customer management, process management, just in time delivery system and started
to gain an important place in the market.
Within the frame of world standards, one of our main target is to lead to new ideas
and meet the requirements of sector also being professional consultant by taking
advantage of newer technologies. CareLabs establishes itself by abiding
with principles and improve ourselves continuously by taking into account our
environmental responsibilities.
AREA OF SERVICE
Carelabs providing electrical testing, calibration services, inspection services and
testing equipment for electrical projects. Process control instruments, electrical &
linear instruments, calibration & certification,
installation, pressure calibration , temperature calibration, dimension calibration, ma
ss calibration, power quality, thermography test, cable & wire fault, UPS/battery
testing services.
Our services cater to major clients which includes utility generation, transmission and
distribution substations, district cooling plants, sewage treatment plants, data
centers, pumping stations, malls and commercial buildings, super/hyper markets and
infrastructure developers.
CareLabs consistently has field crews deployed in various locations so whether your
need is routine or emergency; our specialists are always nearby. This expertise and
exposure, efficient access to comprehensive historical data, and highly trained field
and office technical staffs, allow for the most complete and cost effective project
management solutions.
CareLabs has been a part of various prestigious projects in the globe. In a very short
span of time, CareLabs has been established as an ISO 9001:2008 certified
organization and has acquired a reputed client base with excellent feedback from the
clients.
Our subsidiaries and global associates have expertise in management systems, product
testing, electrical safety, medical device certification, and explosion & process
safety. CareLabs believes in conducting business with highest ethical standards by
providing quality services with commitment, building knowledge, transforming ideas
by respecting our clients and customers values and principles. We are ductile to your
requirement and can work on more than one type of contract simultaneously. Our
major service areas are UAE, Saudi Arabia, Oman, Qatar, Kuwait, Bahrain, India,
Middle East & Africa.
Calibration
Calibration increases the precision of the measuring device. There are unseen
expenses and dangers associated with un-calibrated gears. Carelabs is an authorized
provider of Electrical Calibration Services in UAE.
Inspection
Third party inspection is essential to verify that installations are safe when connected
to a source and should be performed according to the Standards. Carelabs performs
inspection of entire wiring, electrical equipment, transformers, alarm systems,
emergency turn-on, lighting etc. Carelabs is an authorized provider of Electrical
Inspection Services in UAE.
Thermography
With time, electrical connections in your building becomes slack from cycling
temperature differences, because of loading variations and pulsation, along with
many other factors. These loses can be identified using infrared thermography
inspection. Carelabs is an authorized provider of Electrical Infrared Thermography
Inspection Services in UAE.
EPSS – that’s the “emergency power supply system”- it’s the entire system: the emergency generator, the
transfer switch and the distribution panel for the emergency power. It is the complete package of the entire
emergency system which supplies power to the building when called upon.
For more information on emergency power supply, you can request a quote for an EPSS or other
services. You can also give us a call at 1-800-899-3931
A 22KW generator is a smaller piece of equipment that may be used at a small nursing home, small business or
maybe a telecommunications site. They are really small as far as load capacity goes. That’s what we see out in
the field.
The 2000 KW (generator) is a large generator that you would see at facilities such as data centers, large
hospitals or maybe multiple centers at a hospital. These generators usually are involved in the fire life safety of
the of the building. They are large units and sometimes come in shipping cargo container type housings.
The size of a generator is dictated by the customer’s load, and it varies depending on the customer’s
requirements.
For example at a customers location they may require an air conditioner, some refrigeration, some test lab
powering – it just depends on which items they want to have on the emergency backup system (so that when
they lose power these items are powered up).
What we typically do is come out for a visit at a customers location. During that visit we would go over the
items that you’d want to back up during an outage. We would then calculate that load into the generator sizing.
Part of the equation includes seeing if there are any elevators that would require motor starting, air
conditioning sizing or lighting requirements.
These are just examples of what we would look at that go into sizing of a generator.
For more information on a new generator or to find the required size, you can request a quote or give us a call
at 1-800-899-3931
Generators are powerful industrial machines that will keep your site operational when you need them most.
However, you need to ensure that your generators are in reliable working order if you want them to operate at
full capacity. Downtime can be easily avoided if owners, building engineers, maintenance personnel, and
factory managers service generators properly. Here are the most commonly-encountered generator
maintenance mistakes you should avoid to keep your keep your site up and running in an emergency situation.
1: Lack of Servicing
The most obvious generator maintenance mistake you can make is to neglect to service your generator
regularly. Performing regular preventative maintenance ensures that you identify issues before they become
major problems, and it keeps your equipment in good running order.
4: Fuel Quality
When you’re not regularly using your generator, it’s common for fuel to develop problems within the tank. If
you don’t maintain good fuel quality, condensation will cause microbes to thrive and eventually contaminate
the tank. This contamination will lead to damage to the fuel injection system. Injection pumps can be very
costly to replace.
Commonly, running too light a load through your generator causes wet stacking which is an accumulation of
unburned fuel in the exhaust system which can be a fire hazard.
10: Insufficient Lubrication
Undertaking tasks such as oil changes keeps your generator’s components moving properly. A lack of
lubrication inside the generator causes corrosion and unnecessary wear and tear on the parts.
At Duthie Power, we know that generators most often fail because they’ve been improperly maintained.
Through regularly-scheduled generator maintenance, our expert team takes the hassle out of servicing for your
complete peace of mind. Stop worrying about whether your generator will fire up when you need it–contact
us today to see how we can help.
The truth is that power outages affect business’s revenue streams. ITIC reports that 98% of all organizations
say just one hour of downtime costs their firm over $100,000.
According to a study by Inside Energy, the five-year annual average of outages doubled every five years from
2000 to 2014.
So, how can you protect your business from power outage interruptions? If you don’t already have a back-up
generator for your building, you can do the next best thing. Install a generator docking station, also known as a
TAP box, so a portable generator can be quickly hooked up.
Generator tap boxes are usually installed at the side of a building, on its exterior. The “quick connection” of a
docking station is a cost-effective method because it avoids the need to connect temporary power from the
portable generator to the main breaker during an outage because it has already been done.
The sheer flexibility of the generator docking station, coupled with a portable generator, allows power support
for:
HVAC systems
Lights
Hot Water Heaters
Refrigerators
Security Systems
Electronics
Often, customizations include features like Cam-Lok snap covers for a “quick connection” to portable
generators. Other options include short circuit protection, custom enclosure doors, phase rotation protection
and more.
Generally speaking, a business or building will have to write down or estimate the number of times a year they
experience power outages. They should also note the location of the temporary generator and the size of the
electrical load (which could end up being quite high). Critical, priority systems and the overall budget must
also be considered.
After having evaluated how many times a year an outage occurs, businesses should focus on creating a plan. It
must identify risks and show how those risks will impact operations. Having a docking station in place can be
part of a continuity plan that helps to mitigate those risks.
Of course, even the best laid plans require stress tests and practice. Businesses should be testing the
effectiveness of their generator tap boxes and keep up with preventative maintenance. That way they can make
sure everything is up-to-date.
The effects of power outages on businesses usually go unconsidered. This holds true until it happens, and a
business is caught, like a sitting duck, in the dark throughout all of the outage.
Today, practically every business increasingly relies on networks and web-based technologies. That’s why
setbacks of an outage cause so many widespread problems.
A few of the consequences could include the following:
Lost Customers
Decreased Revenue
Effect on Reputation
Unturned Inventory
Spoilage
Decreased Employee Productivity
Damaged Equipment
All these risks sound pretty scary to most businesses. The good news is that power outages are catastrophes
that can be planned for.
The key is preparedness and forethought. And you already know how important it is to have a business plan.
Now, focus on your power plan by including a generator docking station and electrical tap box.
Contact one of our qualified sales engineers to discuss how Duthie Power Services can install your Docking
Station at your facility to better prepare your business for your next power outage.
If utility power goes out, the (ATS) Automatic Transfer Switch is going to tell the generator start. The
generator will start (come up to speed) and the ATS will monitor it verify voltage and frequency and then it
will transfer over. This will typically happen within 10 seconds.
For more information on generator start times, request a quote or give us a call at 1-800-899-3931
If I Have an ATS Why is There a Time Delay When the Power Goes Off?
There’s a system of time delays just in case power goes off and comes right back on – you don’t want your
generator switching to emergency power at that point.
So after a certain amount of time, 1 to 2 seconds of a voltage dip, the generator will get a crank signal from
your automatic transfer switch.
When the generator comes up to voltage, (which is sensed by your automatic transfer switch) it then transfers
power from utility to the generator.
For more information about automatic transfer switches (ATS), request a quote or give us a call at 1-800-899-
3931.
This is not a trick question. But the answer might surprise you.
All five of these are businesses and/or public services that require a continuous application of power.
Consider what might happen, for example, if a hospital were to suddenly shut down and lose power while
patients are in surgery, in MRI machines, or giving birth?
While it may sound extreme, the only reason this hasn’t happened yet is probably because big businesses and
public services use a small component that has been installed on a generator. Small but powerful, that’s the
automatic transfer switch.
What is an ATS?
“ATS” stands for “automatic transfer switch”. Transfer switches come in either automatic or manual and they
are the mechanisms that kick-start a generator into gear.
As you might imagine, an automatic transfer switch sends a signal to your generator to kick in without
interrupting the flow of electricity. There might be a few seconds of darkness, but the transfer gets handed off
nearly seamlessly.
Manual transfers require an individual to head outside where the generator is located and connect the transfer
switch to manually start the generator.
Naturally, the choice between the two, in terms of convenience, is pretty clear: automatic seems like a clear
winner, right?
Well, choosing between an automatic transfer switch and a manual transfer switch depends on a variety of
factors including your personal budget, your electrical demands and what your energy is actually powering.
There’s one other thing to consider as well, however: Where you live.
If your area, town or country is prone to seasonal loss of power (because of heat in the summer, for example)
or you live in a more rural area, choosing a trusted generator service company to professionally install an
automatic transfer switch would be worth the investment.
Automatic transfer switches also require maintenance, after your service provider has accurately sized the
transfer switch, according to your backup generator’s load.
A manual transfer switch costs less and is easier to install, but the trade-off is a prolonged period of power
interruption. While this option still requires professional installation, the simplicity of the job knocks down the
price.
Businesses and public services that could rely on a smooth flow of electricity
There are five types of businesses and public services that could benefit from choosing automatic transfer
switches instead of the manual option.
These are government services and buildings, hospitals and medical centers, restaurants and hotels, factories
and manufacturing plants, and schools.
These kinds of services and businesses require a smooth and uninterrupted flow of power. Since an ATS
automatically senses a loss of electricity, it allows the changeover to occur without a break in business.
For commercial centers, hospitality-based businesses and retail or commercial businesses, the choice of an
automatic transfer switch is less of a “life-and-death” situation and more one of perception and guest services.
Continuing uninterrupted might not be a dire need but it greatly affects a patron’s experience of your
establishment.
Manufacturing plants and factories fall under more of a need since their operations are often a workflow or a
process. Assembly lines, robots and programs intended to put together products, print, and run general
operations, when interrupted, could have their own built-in safety mechanisms.
These mechanisms might trigger at a loss of power. This means that even if power were restored, the loss of
power and downtime could affect the process negatively or require another manual intervention from a
specialist who must then come in and reset these machines.
If you run or work at an institution or organization that comes under these five types of places, you might
consider making a switch. Automatic transfer switches come with clear advantages but there’s no such thing as
a free lunch, as the saying goes.
Reduced downtime: having to head out to where your generator is located makes ATS electrical equipment
much less time-consuming. Additionally, if your generator is located somewhere that’s hard to reach, an
automatic transfer switch is not a choice, it’s a necessity.
Safety first: Using an ATS means you pay more but you also reduce your own financial liability when it
comes to patrons and those who access social services like hospitals. In terms of restaurants, hotels and retail
centers, this becomes a matter of customer service and the risk of a loss of business. But there’s one more
aspect to the benefit of an ATS. Using an automatic transfer switch means you’re not putting an employee in
harm’s way or risking them toying with electrical equipment while on the clock.
Keep the essentials going: The ATS option allows businesses and services to pick and choose which aspects
of your power supply are impacted and which are automatically switched over. For example, if you work in an
office building that specializes in digital and data security and some of your data towers are housed within the
building, the ATS could ensure that the towers are protected, first and foremost, while the lights or lunchroom
refrigerator can be less of a priority.
While ATSs have clear advantages, they’re only machines and have been known to error, responding to false
signals. This wastes generator power, but it’s not as though the entire system trips or overloads.
In the grand scheme of things, having an ATS, though entailing great upfront cost, expert installation and
maintenance, is the right solution if your business is in the business of serving people.
That’s what is at the core of these five businesses — yes, including factories and plants. While machines have
reached a state of automation, they, like an ATS, still require help and input from humans.
So make your decision wisely, considering these factors, but perhaps giving the human element the greatest
weight.
Duthie Power Services is proud to help with all your ATS needs. Give us a call today if you have more
questions or would like more information. 1-800-899-3931 or request a quote by filling out this
form: https://duthiepower.com/request-a-quote
Continuing our series on the ATS a lot of our new customers always ask – Where is the Automatic Transfer
Switch Located?
They can be near each other or the generator can be on the ground and your transfer switch can be on the roof
of a 50-story building – it really doesn’t matter. Generally wherever the emergency power (that dedication) is
located that’s where the transfer switch is going to be. It’s a it’s a matter of logistics more than anything.
What goes wrong with an ATS?
Continuing our series on the ATS let us help answer the question – What goes wrong with an ATS?
On a transfer switch service almost anything can go wrong. Generally it’s wire connections or a coil relay
(something that has malfunctioned). some micro switches that are involved in travel on the mechanism will get
stuck from lying dormant ( unused ) for months at a time. That’s why we recommend at least a monthly
transfer switch test.
For more information about automatic transfer switches ( ATS ) – or – to request a quote click
here https://duthiepower.com/request-a-quote or give us a call at 1-800-899-3931
When you are servicing an Automatic Transfer Switch the first thing you should do is a visual inspection.
Look for telltale signs of a loose cable which would be discolored on the lux (you don’t need an infrared gun to
tell that).
Tighten up all the connections. We want to go through the mechanism to make sure that there is no binding,
everything works as expected.
All lubricating points if necessary they will be done again. All connections are tightened everything is
analyzed as far as the manufacturer spec and the operation (all time delays are checked). Then we’ll do a test
(using a test feature) on the transfer switch and finally we will do a drop power test to make sure everything
functions as normal.
All transfer switches are different. Generally a relay or coil may burn and that could be due to a micro switch
that gets stuck from idle/non-use.
That’s why a monthly test on your transfer switch really recommend. An annual transfer switch service test
will give you peace of mind it will work every time.
ATS: The Heart of Emergency Power
The Automatic Transfer Switch (ATS) is the heart of emergency power. The National Fire Protection
Association has codes dictating that it does require at least a monthly inspection (especially
Healthcare/Hospitals). The normal high rises are not really listed in the code for a monthly inspection but they
strongly suggest it. “NFPA 110” is very direct about ATS inspections and ATS operations.
The ATS, or automatic transfer switches, are basically the go-between utility power and generator power.
There is a common load fed from the transfer switch usually to all your emergency panels. During a test or an
actual power failure, there is a time delay before the ATS sends a signal to your generator, starting it. When
the voltage and frequency of your generator is acceptable by the voltage sensing network, it sends a signal over
to the mechanism. It will open up normal power and then close the generator. Now you’re online and
everything is stable at this point. When normal power, or utility comes back online there is a time delay
preventing the generator from switching back – just in case normal power is unstable for a while (usually 10
minutes is a good number).
After 10 minutes of voltage sensing in your digital display is acceptable for utility it will send a signal to the
mechanisms once again. It will open generator first, close normal power, and now you’re back on utility. The
generator will cool down for a certain amount of time and then you’re ready for the next power failure.
The ATS is the heart of emergency power. Your generator has to be in good shape for the transfer switch to
accept the power and it also has to be up to snuff for utility to be accepted by the power – but nothing happens
without it.
Just starting the engine and running it at the rated RPM is better than nothing at all, but you’re not building any
horsepower.
What you have to do is actually put a load on the generator, that requires the transfer switch to shift from
normal power to emergency power. That will interrupt all emergency circuits momentary, but it’s the best way
to exercise the engine.
Wondering how often you should be exercising the engine on the generator? Visit this post to see what we
recommend.
At Duthie Power, we offer Load Bank testing as a service to your generator. To learn more about the details of
what exactly a Load Bank does, you can visit this blog post and watch the video for more information.
To prepare for these occasions, it’s important that your unit stays in good shape with these generator
maintenance tips – even if you have not used it for a while.
Keep it Clean
The first major check you will want to make on a regular basis is whether or not your generator is clean. It
should be clear of leaves and grass, or anything else that might be swept onto it by the wind. There should not
be anything on top of it – whether permanently, or even for a few moments.
Make sure you check the air flow vents and the radiator in particular. It’s important to check your generator
regularly, but even more so when the weather report begins to suggest a storm or a heat wave. When winds
pick up, debris can block those air flow vents and cause overheating.
Make Visual Checks
There are some other checks that you should be doing regularly, too. These include monitoring the fluid levels,
such as your oil, fuel, coolant, and lubricants. Set up a schedule so that the employee or employees who are
responsible for the generator need to sign off on all of these checks once a week.
You should check the battery charging rate, and ensure that the electrolyte level is correct on serviceable
batteries. If your batteries aren’t working, you could be in trouble next time you need the generator.
Visual inspections also need to be done across all of the fuel lines and connections. You should be looking for
leaks in the lines, kinks, and loose connections, which need to be repaired or replaced as soon as possible.
Get it Running
You should also make sure your generator still runs on a regular basis. To be safe, once a month, this should be
added to your scheduled checks. Turn the generator on and make sure all of the indicator lights and gauges
work properly. Ensure that the system is doing the weekly exercise tests that it has been set up to complete.
Make sure to check the natural gas or propane pressure, oil pressure, frequency, temperature, and fuel pressure,
comparing it alongside the specifications in your user manual. If they don’t match up, something is wrong.
You can also check the voltage to ensure your generator has the right output. If you see anything at all during
your checks which does not look right, call in maintenance for help. Any of these flaws could stop it from
working properly when you do need it.
Keep it Going
When your generator does end up running and the power comes back on you shouldn’t just let it run and leave
it alone. This is the time when checks and inspections are most important. You still need to keep things in good
shape. After it has been running for eight hours, change the oil and the filters to ensure everything is still
working fine. Once you have done that, your user manual will tell you how often your particular generator
needs to be exercised.
It’s important to check your generator regularly and to keep it in good working shape for when it needs to kick
in. You will be rewarded with smooth running and no disruption to your power, which may be essential to
keeping your business running. In addition, make sure to have regular maintenance visits and services from
trained professionals who know how to spot the more complex problems. This will ensure your generator
works in the event of a power emergency.
On our semi annual service we basically run through a checklist (a criteria of minor maintenance). We look at
your belts, hoses, battery – we look for cracking in the hoses and wear on the belts. We will run the unit, check
the generator for proper output and check the engine for leaks. Anything that can be detected with a visual
scan.
We will open panels and check for tightness of connections and look for anything that can inhibit the generator
from operating properly.
This includes the operation of block heaters, the basic engine coolant heater and the battery charger that’s
supposed to keep your battery at a perfection level.
There is a criteria for engine cranking. It’s called an over crank test where your generator will crank for certain
amount of time (rest) and then re-crank until the set point has been reached. If the engine does not start you’ll
get an alarm for “over-crank”. That basically protects your engine starter and allows the fire control (what
should be an alarm) to alert your engineering staff.
If utility power goes out, the (ATS) Automatic Transfer Switch is going to tell the generator start. The
generator will start (come up to speed) and the ATS will monitor it verify voltage and frequency and then it
will transfer over. This will typically happen within 10 seconds.
Types of Automatic Transfer Switches and
How They Work
Providing power to your home or business in the event of a power outage or
other electrical problems can be useful or even critical depending on your
industry. The best way to do this is to use a generator. Generators are
devices that generate electricity for some amount of time using a source of
fuel like natural gas in order to replace power from the city or utility plant.
What many people don’t know about generators is that they are not the only
piece you need. There is another piece that must be considered called an
Automatic Transfer Switch, or ATS. An ATS is a device that acts as a brain
between utility and secondary power. It acts in the event of power interruption
to switch over to secondary power and control the system with little or no input
from you.
After reading this guide about ATS systems, you will be more prepared to
understand your power needs and decide what solution is best for your
business.
There are four types of ATS systems that can be installed depending on the
needs of the building(s). All types of switches have the same ultimate goal of
managing electricity in a safe and expedient way; however, each design
meets different criteria and is used for different applications. The electrical
power professionals at Buckeye Power Sales can help you determine exactly
what type of ATS you need and how to design it for your specific needs.
Given the complexity and sensitivity of businesses that need this level of
protection, there are many codes and standards that govern these devices
and their use. Standby power systems can be very complex, especially when
connected in parallel with utility power. Buckeye Power Sales and their highly
trained staff are experts at handling the selection and sizing of ATS and
generator systems.
The team at Buckeye Power Sales can help you and your business
understand every regulatory and legal compliance standard such as
Underwriters Laboratories, National Electric Code and National Fire Protection
Association standards, not to mention all local laws on these topics.
If you need legally mandated backups systems or are interested in having the
security and peace of mind that comes with power backup systems, contact
Buckeye Power Sales today to make an appointment. Our highly capable staff
can help you understand and work through your needs while maintaining the
strictest security and legal standards in the business.
Many businesses use a single, large generator to meet their power needs.
However, these businesses may be missing out on the benefits of paralleling
two or more systems, or paralleling their generator to the utility.
1.
1. Redundancy: Having more than one generator connected at all
times delivers greater reliability and flexibility, particularly in the event
another generator goes out or during scheduled maintenance.
2. Efficiency: Choosing multiple smaller generators connected in
parallel, instead of one large generator, allows you to turn generators on
and off as necessary to meet the varying needs of the load.
3. Value: In some cases, multiple small generators can actually cost
less than a single large generator.
4. Power Needs: If the largest available generator won’t meet your
power needs, multiple generators can be connected in parallel to
provide the necessary power.
5. Space Constraints: If space is limited and a large generator
won’t fit, multiple smaller generators can be used without sacrificing
power capacity.
6. Future Growth: As your power requirements expand, you can
add new generators to the paralleled system.
When it comes to paralleling power, it’s all about the controls. Choosing the
right system and switchgear for your business’ needs is crucial. KOHLER
Paralleling Switchgear will help you meet your synchronization and load
management requirements and will be configured to the specific transition
type you need.
Here are some of the reasons to choose KOHLER Paralleling Switchgear:
Work with Buckeye Power Sales to Fully Integrate Your Paralleling System
We work with you to choose the KOHLER system that provides the operating
modes that meet the needs of your facility—whether you require simple
standby power or multiple-utility paralleling and emergency power, prime
power or peak shaving.
We’re happy to work with you to choose the right generator for your
commercial needs. But building a good understanding of their capabilities
beforehand will save you time, effort, and resources. Here’s what you need to
know.
Not all generators are created equal. Generators used as backup, or standby
power for a typical home are generally smaller, portable, and can cope with
the light-to-moderate power needs that your home would demand.
We’ve put together a handy information sheet to walk you through all of the
details, which we recommend you download and read. But in the meantime,
here are a few of the critical factors that go into your decision.
Voltage Dip
Different pieces of equipment have different tolerances for voltage dip, and
the starting load of an electric motor can be as much as six times its running
load.
Since that starting load can affect your generator’s regulator system by
reducing the available voltage, you need a generator large enough to handle
the maximum allowable voltage drop. You’ll need to consult the
manufacturer’s spec sheet for your equipment to determine what the
allowable drop in input voltage is.
Frequency Dip
Ambients
Application
Once you’ve assessed your system’s needs, our pros can walk you through
which products will make the best fit for your business.
You can view more about the generators we offer here on our website, and
make sure to reference our extended generator sizing information sheet as a
reference. With the right knowledge ahead of time, keeping production up and
running during the next power outage will be no problem.
A matter of seconds is all it takes for Kohler generators to have your business
automatically powered, so you won’t suffer from downtime.