Steam Turbine Unloading and Shut-Down of Operation Turbine/Generator Shut-Down Diagram (General)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Steam Turbine Unloading and Shut-Down of

Operation Turbine/Generator
Shut-Down Diagram (General)

(01) + TURBINE/GENERATOR UNLOAD REF. TO 6.2-0320


OR
+ FGA (TURBINE -CONTROL STANDSTILL) START

(02) + START OF BYPASS OPERATION OBSERVE REF. TO 6.2-0320

(03) + GENERATOR BREAKER TO BE OPENED OBSERVE REF. TO 6.2-0320


REVERSE POWER PROTECTION INITIATED

(04) + TEST PROGRAM (SHUTDOWN) CARRY OUT REF. TO 6.3.0060

(05) + TURBINE TRIP INITIATE REF. TO 6.2-0320


OR WITH FGA (TURBINE-CONTROL)
*+ TURBINE TRIP INITIATED REF. TO 6.2-0320

(06) + START OF AUXILIARY OIL PUMP OBSERVE REF. TO 6.2-0320

(07) + TURNING GEAR OPERATION START REF. TO 6.2-0320


+ SHAFT LIFT OIL SUPPLY SYSTEM IN OPERATION
+ TURNING GEAR OIL SYSTEM IN OPERATION
OR WITH SUBLOOP CONTROL
*+ SHAFT LIFT OIL PUMP ON
*+ TURNING GEAR OIL VALVE OPEN

(08) + STEAM -GENERATOR NOT IN SERVICE


+ BYPASS -OPERATION COMPLETED
+ CONDENSING PLANT SHUT DOWN REF. TO 6.2-0330
+ VACUUM PUMPS OFF
+ SEAL -STEAM SUPPLY SHUT -DOWN
+ CONDENSATE PUMPS OFF
+ CIRCULATION WATER SUPPLY NOT IN SERVICE
OBSERVE

(09) + CONTROL FLUID PUMPS SHUT -DOWN REF. TO 6.2-0320

(10) + OIL SYSTEM WITH FGA (OIL SUPPLY) SHUT -DOWN REF. TO 6.2-0340
OR
MANUAL OPERATION AT OPER. CONSOLE
+ SHAFT STANDSTILL
+ OIL SYSTEM NOT IN SERVICE

BHEL, Hardwar 6.2-0310-01