Error in Model of CBC Block “A” as shown in figure below

2. Error in Model of CBC Block “B” as shown in figure below


3. Live load in Roof Floor is only 0.75 KN/m2 , But it seems that roof is
accessible Live load is not sufficient.
4. In Block C of CBC Building only Water wight is assigned as load in slab but
there is no study of hydrodynamic effect and no design of shear wall in
model for swimming pool at roof top.

5. Design of Mat foundation and detail drawing of Mat foundation is different


from each other

Figure: As per Design


Figure: As per Structural Drawing Provided
6. 3D model from Etabs Model Provided and that in Report of Block A
doesnot match with each other as shown in figure

Figure: From Etabs Model Provided


Figure: From Report of Block A
7. Grade of RCC is M25 not M20 Grade but in report it is written M20 Grade
as shown in figure below

8. Grade of Rebar is Fe500 for Main Bars but it is taken as Fe415 in report as
shown below.

Figure: From Report of Block A


Figure: From Structural Drawing

9. Grade of Rebar is Fe500 for Main Bars but it is taken as Fe415 in report as
shown below.
10.There is no Detail Design Summery of Beams and Columns in Tabulated
form in report. Please include all the things in report which are essential
(only output results from ETABS is shown)