Professional Documents
Culture Documents
Product Data Sheet Rosemount 2120 Level Switch Vibrating Fork en 73576
Product Data Sheet Rosemount 2120 Level Switch Vibrating Fork en 73576
Product Data Sheet Rosemount 2120 Level Switch Vibrating Fork en 73576
March 2019
00813-0100-4030, Rev HD
Designed for operation in process “Fast drip” fork design gives a quicker response
temperatures of –40 to 302 °F (–40 to 150 °C) time, especially with viscous liquids
Increased safety, SIL2-certified to IEC 61508 Hygienically certified to 3-A® and EHEDG,
as required by IEC 61511 and SIL3 capable and complies with FDA and ASME-BPE
Adjustable switching delay for turbulent or
splashing applications
Rosemount 2120 Level Switch March 2019
When used as a low level alarm, the liquid in the tank or pipe drains
down past the fork, causing a change of natural frequency that is
detected by the electronics and switches the output state.
When the Rosemount 2120 is used as a high level alarm, the liquid
rises in the tank or pipe, making contact with the fork which then
The Quick Release kit is a new optional set of accessories.
It makes inspection, proof-testing, and servicing easier than ever
causes the output state to switch.
(see Table 2 on page 9 for accessories)
Key features and benefits
Function virtually unaffected by flow, bubbles, turbulence, foam,
vibration, solids content, coating products, liquid properties, and
product variations
There is a variety of plug-in electronics options, with A ‘heartbeat’ LED indicates its operating state. The LED also flashes
each having an adjustable mode and switching delay when the switch output is ‘off’ and is constantly lit when 'on'
(see “Electrical connections” on page 12)
Adjustable switching delay prevents false switching in turbulent or
splashing applications
‘Fast drip’ fork design gives quicker response time, especially with
viscous liquids. Rapid wet-to-dry and dry-to-wet time setting for
highly responsive switching
Contents
Overview of the Rosemount 2120 Level Switch . . page 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 10
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . page 4 Product Certifications . . . . . . . . . . . . . . . . . . . . .page 14
Spare Parts and Accessories . . . . . . . . . . . . . . . . . . . page 9 Dimensional Drawings . . . . . . . . . . . . . . . . . . . .page 17
2 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
The ‘heartbeat’ LED gives an instant visual indication that the unit is operational
Functional testing of the instrument and system is easy with a magnetic test point
Superior performance
The Rosemount 2120 is a popular choice for high and low level alarm and pump
control duties for its simplicity, ease of use, and reliability
The ‘fast drip’ design allows the liquid to be quickly drawn away from the fork tip
when mounted horizontally, making the Rosemount 2120 quicker and more
responsive in high density or viscous liquid applications
With a user-selectable time delay feature, the risk of false switching is minimized in High-temperature applications
Applications
Overfill protection
Hygienic applications
Pump control / limit detection
High-temperature applications
Wireless applications
In tank gauging systems, a Rosemount 2120
high level alarm switch can be used as an
alternative to a radar level gauge. See the
Point Level Alarm
Rosemount Tank Gauging Product Data
Sheet for additional information.
Rosemount Rosemount
2120 5900S Rosemount TankRadar
Ext. pwr
RS-232
Level
USB
Rx
On - TERM - Off
Tx
Lo - GAIN - Hi
FBM 2180
Emerson.com/Rosemount 3
Rosemount 2120 Level Switch March 2019
Ordering Information
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment.
See page 10 for more information on Material Selection.
8Q Mobrey A Flange ★
9Q Mobrey G Flange ★
4 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
Emerson.com/Rosemount 5
Rosemount 2120 Level Switch March 2019
T Direct load switching (Mains 2-wire) 20 to 264 Vac 50/60Hz, 20 to 60 Vdc NA, E*, and G* ★
H 8/16 mA All ★
Available Available
Surface finish
connections housings
2(3) Hand polished (Ra < 0.4 μm) Tri Clamp only All ★
(4) ★
3 Ra < 0.76 μm, hygienically approved Tri Clamp only A, X
(4)
4 Electro-polished to 0.76 μm, hygienically approved Tri Clamp only A, X ★
7(4) Mechanically-polished to Ra < 0.1 μm, hygienically approved Tri Clamp only A, X ★
(4) ★
8 Electro-polished to Ra < 0.38 μm, hygienically approved Tri Clamp only A, X
Electronic Available
Product certifications
types allowed housings
6 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
A Glass Filled Nylon, M20 conduits/cable threads NA, I1, I2, I3, I5, I6, I7, and IP ★
1 ★
D Glass Filled Nylon, /2-in. ANPT conduits/cable threads NA, I1, I2, I3, I5, I6, I7, and IP
X Aluminum Alloy, M20 conduits/cable threads All except G5, G6, E5, E6 ★
3 ★
Y Aluminum Alloy, /4-in. ANPT conduits/cable threads All except E1, E2, E3, E7, EM, EP
S Stainless Steel, M20 conduits/cable threads All except G5, G6, E5, E6 ★
3 ★
T Stainless Steel /4-in. ANPT conduits/cable threads All except E1, E2, E3, E7, EM, EP
A Standard length 1.7 in. (44 mm) All except flanged and 2-in. NPT ★
(8) ★
H Standard length flange 4.0 in. (102 mm) All flanged options
E(9) Extended, customer specified length in tenths of inches All except 1-in. BSPP O-ring (1P) ★
(9) ★
M Extended, customer specified length in millimeters All except 1-in. BSPP O-ring (1P)
XXXX(9) Specific customer specified length in tenths of inches or millimeters (XXX.X inches or XXXX mm) ★
Material certification(8)(10)
Safety certification(11)
Hygienic certifications(13)
QA 3-A certificate ★
QE EHEDG certificate ★
ASME-BPE statement(13)
QB ASME-BPE statement ★
QH FDA statement ★
Emerson.com/Rosemount 7
Rosemount 2120 Level Switch March 2019
Special procedures(14)
Overfill
1. ECTFE copolymer coating is only available for a flanged Rosemount 2120 but excludes 1-in./DN25/25A flanges.
Flanges are dual certified 316 and 316L Stainless Steel (1.4401 and 1.4404).
2. Other process connections available upon request.
3. Hand-polished for hygienic connections to better than 0.4 μm Ra such that there are no pits, folds, crevices or cracks discernible to the naked eye (i.e. no features
larger than 75 micrometers based on resolving 1/60 degree at a distance of 250 mm).
4. Not available for explosion-proof or flameproof product certifications.
5. Includes the Technical Regulation Customs Union (EAC) ordinary location mark.
6. See “Product Certifications” on page 14. E5 includes G5 requirements. G5 is for use in unclassified, safe area locations only.
7. See “Product Certifications” on page 14. E6 includes G6 requirements. G6 is for use in unclassified, safe area locations only.
8. Not available for hand polished wet side.
9. Minimum length available for 3/4-in. threaded connection is 3.8 in. (95 mm); for 1-in. and 2-in. threaded, it is 3.7 in. (94 mm); for flanged, it is 3.5 in. (89 mm);
and for Tri Clamp, it is 4.1 in. (105 mm). Maximum length is 157.5 in. (4000 mm), except for ECTFE copolymer coating and polished process where the maximum
length is 59.1 in. (1500 mm) and 39.4 in. (1000 mm) respectively. Examples: Code E1181 is 118.1 inches. Code M3000 is 3000 millimeters.
10. Only available for process-wetted parts.
11. Not available for Direct Load or Relay (option code E) switching electronics.
12. Not available with Relay (option code V) switching electronics.
13. Available only for a Rosemount 2120 with a Tri Clamp fitting, Product Certification code NA, G*, or I*, and Surface Finish code 3, 4, 7, or 8.
14. Option limited to units with extended lengths up to 59.1-in. (1500 mm). Option is not available for ECTFE coating.
8 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
02100-1000-0001 Seal for 1-in. BSPP (G1A). Material: Non-asbestos BS7531 grade X carbon fiber with rubber binder ★
3 ★
02100-1040-0001 Seal for /4-in. BSPP (G3/4A). Material: Non-asbestos BS7531 grade X carbon fiber with rubber binder
1 ★
02100-1010-0001 Adapter boss 1-in. BSPP to 1 /2-in. (38mm) Tri Clamp. Material: 316 SST fitting. FPM/FKM O-ring
(3) ★
02100-1020-0001 2-in. (51 mm) Tri Clamp kit (vessel fitting, clamp ring, and seal). Material: 316 SST, NBR Nitrile
02100-1030-0001 Telescopic test magnet ★
(4) ★
02120-7000-0001 Replacement Cassette: Direct load switching (2 Wire) (Red)
02120-7000-0002(4) Replacement Cassette: PNP/PLC, 20 to 60 Vdc (Yellow) ★
1. Check the Electronic Type and Product Certification sections in Table 1 on page 4 for availability conditions.
2. Intrinsically Safe (IS) approved cassettes can only be replaced with the same type of IS cassette. Non-IS cassette types can be interchanged with other non-IS
cassettes, but the new label must be fitted and the original part number transferred to the new label.
3. This is not approved to be used with a 3-A or EHEDG approved products and is not assessed for use with FDA or ASME-BPE compliant products.
4. This replacement cassette is for versions of the Rosemount 2120 shipped since June 2013.
5. The Quick Release kit is a set of accessories requiring a Rosemount 2120 with the 2-in. Tri Clamp option and an existing 2-in. NPT process connection on the vessel.
For additional information, see Rosemount 2120 Quick Release kit – Quick Start Guide.
Emerson.com/Rosemount 9
Rosemount 2120 Level Switch March 2019
3
/4–in. threaded 3.8 in. (95 mm)
1–in. and 2-in. threaded 3.7 in. (94 mm)
Flanged 3.5 in. (89 mm)
Tri Clamp 4.1 in. (105 mm)
10 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
Flanged connection:
32 (0)
Process Pressure psig (barg)
-40 (-40)
1450 (100)
-40 32 140 302
1160 (80) (-40) (0) (60) (150)
Process Temperature °F (°C)
0 (0)
-14.5 (-1.0)
-40 32 122 302 Process
(-40) (0) (50) (150) Temperature °F (°C) Liquid density requirement
Minimum of 37.5 lb/ft3 (600 kg/m3).
Emerson.com/Rosemount 11
Rosemount 2120 Level Switch March 2019
Performance Grounding
Hysteresis (water) The Rosemount 2120 must always be grounded either through
the terminals or using the external ground connection provided.
±0.039-in. (±1 mm) nominal.
Conduit plugs/cable gland
Switching point (water)
Metal housing:
0.5 in. (13 mm) from tip (vertical) / from edge (horizontal) of Conduit entries for explosion-proof areas are shipped with one
fork (this will vary with different liquid densities). Exd plug (loose in bag) and two dust caps fitted. Use suitably
rated cable glands. Unused conduit entries must be sealed with
Electrical a suitably rated blanking plug.
Switching mode Glass-filled nylon housing with direct load, PNP/PLC and IS
electronics are shipped with one PA66(1) cable gland and one
User selectable switching mode (Dry=on or Wet=on).
blanking plug.
Protection
Glass-filled nylon housing with relay electronics are shipped with
Polarity insensitive two PA66(1) cable glands.
– on Relay (except 12 Vdc version) and Direct Load electronics
Electrical connections
Over-current protection
– on Direct Load and PNP/PLC electronics Direct load switching (mains two wire) cassette
Surge protection (to IEC61326) PE R Fuse 2A(T) R = External load (must be fitted )
(Ground)
– available on all versions of the Rosemount 2120 U = 20 - 264 V ~ (ac) (50/60Hz )
DPST
IOFF < 4 mA
IL IL = 20 - 500 mA
Heartbeat LED Neutral Live IPK = 5 A, 40 ms (inrush)
U = 20 - 60 V (dc)
The Rosemount 2120 has a status-indicating ‘heartbeat’ LED, IOFF < 4 mA
IL = 20 - 500 mA
which can be seen at all times and from all angles through a lens 0V +V
IPK = 5 A, 40 ms (inrush)
The LED flashes when the output is ‘off’ and is constantly lit
NAMUR (light blue) cassette
when it is ‘on’. The LED gives a constant indication that the
Rosemount 2120 is functioning correctly (different flash rates OPERATION MODE
Dry On Mode Dry On Wet On EN 50227 / NAMUR
are used to indicate a product malfunction) and gives a local - + Dry
Wet 0.3 0.3
indication of the process state. 8V
dc
1 1
3 3
Dry 10 10
Magnetic test point Wet 30
Seconds Delay
30
1 2 Wet On Mode
A magnetic test point is located on the side of the housing, ION = 2.2 ... 2.5 mA
IOFF = 0.8 ... 1.0 mA
allowing a functional test of the Rosemount 2120 and a system Ex IFAULT < 1.0 mA
12 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
8/16 mA (dark blue) cassette DPCO dual relay cassette (12 Vdc nominal version)
OPERATION MODE
12 VDC NOM. OPERATION MODE Isolate Supply Before Removing
+ Dry On Mode Dry On Wet On 8/16 mA Seconds Delay
Dry Dry On
Wet
+ Dry On Wet On Dry NC C NO NC C NO
0.3 0.3
1 1 0.3 0.3 Wet
RELAY
3 3 1 1
Wet 10 10 3 3
Dry 30 30
10
Wet On Mode Seconds Delay 10 Dry
30
1 2 3 30 Wet
Wet On
1 2 3 4 5 6 7 8 9
I ON = 15 ... 17 mA U = 24 Vdc Nominal
I OFF = 7.5 ... 8.5 mA NC C NO NC C NO
PE
(Ground) I FAULT < 3.7 mA PE Fuse 0.5 (T)
Ex (Ground)
Resistive Load Inductive Load
- + DPST cos = 1 ; cos = 0.4 ;
Ex A certified intrinsically safe barrier
L/R = 0 ms L/R = 7 ms
must be used to meet IS requirements IMAX = 2 A IMAX = 1 A
UMAX = 30 V
- + U = 9...30 V
I < 4 mA
(dc) UMAX = 30 V
PMAX = 60 W PMAX = 30 W
Drives 4-20 mA Analog Input
0V +V
DPCO dual relay cassette (standard version) Solid state PNP output for direct interface to a PLC
Warning OPERATION MODE Isolate Supply Before Removing OPERATION MODE PLC/PNP
Seconds Delay Dry On
Dry On Wet On Dry
Dry On Mode Dry On Wet On
N L NC C NO NC C NO Dry Isolate Supply
0.3 0.3 Wet + OUT -
Wet 0.3 0.3 Before Removing
1 1
RELAY
3 3 1 1
10 3 3
10 Dry
30 Dry 10 10
30 Wet
Wet 30 30
Wet On
1 2 3 4 5 6 7 8 9 1 2 3 4 Wet On Mode Seconds Delay
Note
The external DPST switch that is shown in the wiring diagrams is an optional local disconnect (customer supplied).
Emerson.com/Rosemount 13
Rosemount 2120 Level Switch March 2019
Product Certifications
European directive information Ordinary location certification for FM
The EU declaration of conformity for all applicable European G5 Project ID: 3021776
directives for this product can be found at
The switch has been examined and tested to determine
Emerson.com/Rosemount
that the design meets basic electrical, mechanical, and fire
protection requirements by FM, a nationally recognized
NAMUR approval testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA)
NAMUR NE95 type test report is available upon request.
Complies with NAMUR NE21. Ordinary location certification for CSA
Overfill approval G6 Certificate Number: 06 CSA 1805769
GL Germanischer Lloyd
14 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
I6 Certificate Number: 06 CSA 1786345 National Supervision and Inspection Centre for Explosion
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D Protection and Safety Instrumentation (NEPSI)
Class 1, Zone 0, Ex ia IIC flameproof and dust-proof
Non-Incendive for Class I, Div. 2, Groups A, B, C, and D
Temperature Code: T5 (Tamb –40 to 80 °C, Tproc < 80 °C) E3 Certificate number: GYJ16.1464X
Control Drawing: 71097/1179 (with NAMUR electronics) Flameproof and dust-proof:
Control Drawing: 71097/1315 (with 8/16 mA electronics) Ex d IIC T3~T6 Ga/Gb
Single process seal Ex tD A21 IP6X T85 °C~T160 °C
National Supervision and Inspection Centre for Explosion
Protection and Safety Instrumentation (NEPSI)
intrinsically safe
Emerson.com/Rosemount 15
Rosemount 2120 Level Switch March 2019
EM Certificate: TC RU C-GB.BH02.B.00175
Flameproof:
1ExdIICT6...T3 X
Ta (see table in the certificate)
IM Certificate: TC RU C-GB.BH02.B.00175
Intrinsic Safety:
0ExiaIICT5...T3 X
Ta (see table in the certificate)
KTL/KOSHA flameproof approval
EP Certificates:
13-KB4BO-0144X (SMMC, Singapore) or
13-KB4BO-0298X (Rosemount Measurement Ltd., UK)
(depends on the manufacturing location)
Zone 0/1 Ex d IIC T6...T3
Ta (see table in the certificate)
KTL/KOSHA intrinsically safe approval
IP Certificates:
13-KB4BO-0143X (SMMC, Singapore) or
13-KB4BO-0297X (Rosemount Measurement Ltd., UK)
(depends on the manufacturing location)
Ex ia IIC T5...T3
Ta (see table in the certificate)
16 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
Dimensional Drawings
Figure 3. 3/4- and 1-in. Threaded Mounting (Standard Length)
3.5 (90)
Allow 1.2 (30) Allow 1.2 (30)
to remove cover 4 (102) to remove cover 4.7 (120)
5 5.9
(127) A (151) B
C
C
D
2.7 D
2.7
(69 1.7 0.5 (13) switchpoint (69) 1.7
(44) (when mounted vertically) (44)
A. Cable entry M20 x 1.5 or 1/2-in. ANPT C. 1.6 (40) A/F hexagon
B. Cable entry M20 x 1.5 or 3/4-in. ANPT D. 3/4- or 1-in. thread
Dimensions are in inches (millimeters). See the Rosemount 2120 web page for all 1-in. BSPP threaded dimension drawings.
Emerson.com/Rosemount 17
Rosemount 2120 Level Switch March 2019
3.5 (90)
Allow 1.2 (30)
to remove cover 4 (102) Allow 1.2 (30)
to remove cover 4.7 (120)
5.9
(151) A B
6.7
(171)
C
C
D
D
Ø1.14 (29) for 1-in. thread 0.5 (13) 0.5 (13) switchpoint
Ø0.9 (23) for 3/4-in. thread switchpoint (when
(when mounted vertically)
mounted horizontally)
1.7 0.5 (13) switchpoint
(44) (when mounted vertically)
0.5 (13)
switchpoint (when
mounted horizontally)
A. Cable entry M20 x 1.5 or 1/2-in. ANPT C. 1.6 (40) A/F hexagon
B. Cable entry M20 x 1.5 or 3/4-in. ANPT D. 3/4- or 1-in. thread
Dimensions are in inches (millimeters). See the Rosemount 2120 web page for all 1-in. BSPP threaded dimension drawings.
Table 6. Fork Length for 3/4- and 1-in. Threaded Rosemount 2120
Process Standard length Minimum length Maximum length
connection fork length code A fork length code E (M) fork length code E (M)
3
/4-in. thread 1.7 in. (44 mm) 3.75 in. (95 mm) 157.5 in. (4000 mm)
1-in. thread 1.7 in. (44 mm) 3.74 in. (94 mm) 157.5 in. (4000 mm)
18 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
3.5 (90)
Allow 1.2 (30)
to remove lid 4 (102) Allow 1.2 (30)
to remove lid 4.7 (120)
6.1
(154) A B
6.9
(175)
C
C
D
D
E(M)
Ø1.14 (29)
E(M) 1.7
(44)
Ø1.14 (29)
0.5 (13)
0.5 (13)
Switchpoint (when
mounted horizontally) Switchpoint (when
1.7 0.5 (13) mounted vertically)
(44) Switchpoint (when
mounted vertically)
0.5 (13)
Switchpoint (when
mounted horizontally)
2-in. thread 3.74 in. (94 mm) 157.5 in. (4000 mm)
Emerson.com/Rosemount 19
Rosemount 2120 Level Switch March 2019
Figure 6. Tri Clamp Mounting (Standard Length, Surface Finish Codes 1 and 2)
Glass-filled nylon housing Aluminum/stainless steel housing
(and not hygienically approved) (and not hygienically approved)
4 (102) 4.7 (120)
Allow 1.2 (30)
Allow 1.2 (30) 3.5 (90) to remove cover
to remove cover
A B
5.2 6.1
(132) (155)
C D C
D
Ø0.9 (23)
2.5 Ø0.9 (23)
(64) 1.7 2.5
0.5 (13) switchpoint 1.7
(44) (64) 0.5 (13) switchpoint
(when mounted vertically) (44)
(when mounted vertically)
0.5 (13) switchpoint
0.5 (13) switchpoint
(when mounted horizontally)
(when mounted horizontally)
A. Cable entry M20 x 1.5 or 1/2-in. ANPT C. 1.6 (40) A/F hexagon
B. Cable entry M20 x 1.5 or 3/4-in. ANPT D. 11/2-in. (38 mm) or 2-in. (51 mm) Tri Clamp, surface finish codes 1 and 2
Dimensions are in inches (millimeters).
Figure 7. Tri Clamp Mounting (Standard Length, Surface Finish Codes 3, 4, 7, and 8)
Glass-filled nylon housing Aluminum steel housing
(and hygienically approved) (and hygienically approved)
B
A
6.1
5.2 (155)
(132)
D
Ø1.65 (42) D Ø1.65 (42)
A. Cable entry M20 x 1.5 or 1/2-in. ANPT C. 1.6 (40) A/F hexagon
B. Cable entry M20 x 1.5 or 3/4-in. ANPT D. 11/2-in. (38 mm) or 2-in. (51 mm) Tri Clamp, surface finish codes 3, 4, 7, and 8
Dimensions are in inches (millimeters).
20 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
Figure 8. Tri Clamp Mounting (Extended Length, Surface Finish Codes 1 and 2)
A
B
5.2
(132) 6.4
(162)
C
Ø1.56 (39)
C
Ø1.56 (39)
E(M)
E(M)
Ø1.14 (29)
Ø1.14 (29)
1.7
0.5 (13) switchpoint
(44)
1.7 (when mounted vertically)
0.5 (13) switchpoint
(44) (when mounted vertically)
0.5 (13) switchpoint
(when mounted
0.5 (13) switchpoint horizontally)
(when mounted horizontally)
A. Cable entry M20 x 1.5 or 1/2-in. ANPT C. 11/2-in. (38 mm) or 2-in. (51 mm) Tri Clamp, surface finish codes 1 and 2
3
B. Cable entry M20 x 1.5 or /4-in. ANPT
Table 8. Fork Lengths for Tri Clamp Rosemount 2120 (Not Hygienically Approved)
Process Standard length Minimum length Maximum length
connection fork length code A fork length code E (M) fork length code E (M)
Tri Clamp
1.7 in. (44 mm) 4.13 in. (105 mm) 157.5 in. (4000 mm)
(surface finish code 1)
Tri Clamp
1.7 in. (44 mm) 4.13 in. (105 mm) 39.4 in. (1000 mm)
(surface finish code 2)
Emerson.com/Rosemount 21
Rosemount 2120 Level Switch March 2019
Figure 9. Tri Clamp Mounting (Extended Length, Surface Finish Codes 3, 4, 7, and 8)
4 (102)
Allow 1.2 (30)
Allow 1.2 (30) to remove cover 4.7 (120)
3.5 (90)
to remove cover
A
B
5.2
(132) 6.1
(155)
Ø1.65 (42) C
C
Ø1.65 (42)
A. Cable entry M20 x 1.5 or 1/2-in. ANPT C. 11/2-in. (38 mm) or 2-in. (51 mm) Tri Clamp, surface finish codes 3, 4, 7, and 8
3/4-in. ANPT
B. Cable entry M20 x 1.5 or
Table 9. Fork Length for Tri Clamp Rosemount 2120 (Hygienically Approved)
Process Standard length Minimum length Maximum length
connection fork length code A fork length code E (M) fork length code E (M)
Tri Clamp
1.7 in. (44 mm) 4.13 in. (105 mm) 39.4 in. (1000 mm)
(surface finish codes 3, 4, 7, and 8)
22 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
4.8
(121) A B
6
(154)
Emerson.com/Rosemount 23
Rosemount 2120 Level Switch March 2019
6
(154)
4.8 B
(121)
A
0.5 (13)
0.5 (13) switchpoint
Switchpoint (when
1.7 0.5 (13) mounted horizontally) (when mounted vertically)
(44) switchpoint (when
mounted vertically)
0.5 (13)
switchpoint (when
mounted horizontally)
24 Emerson.com/Rosemount
March 2019 Rosemount 2120 Level Switch
4 off Ø0.55 (Ø14) holes equi-spaced 4 off Ø0.55 (Ø14) holes equi-spaced
on 3.62 (92) PCD on 3.97 (98.4) PCD
3.62 (92)
3.62 Ø5.00
Ø
Ø
2. 8)
(Ø
2. 8)
(92)
68
(Ø127)
(Ø
68
6
6
Emerson.com/Rosemount 25
Rosemount 2120 Level Switch Product Data Sheet
00813-0100-4030, Rev HD March 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office Standard Terms and Conditions of Sale are available upon request.
The Emerson logo is a trademark and service mark of Emerson
Emerson Automation Solutions Electric Co.
Emerson FZE P.O. Box 17033, Rosemount is a mark of one of the Emerson family of companies.
All other marks are the property of their respective owners.
Jebel Ali Free Zone - South 2 © 2019 Emerson. All rights reserved.
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
RFQ.RMTMEA@Emerson.com