Performance Summary For 5990: Unit Information
Performance Summary For 5990: Unit Information
Unit Information
Tag Name: ............................................................................................................................................. 5990
Model Number:............................................................................................................................... 50UC-125
Quantity:....................................................................................................................................................... 1
Refrigerant: ........................................................................................................................................ R-410A
No of Circuits / No of Compressors: .......................................................................................................... 2/4
Shipping Weight (with options): .............................................................................................................. 2524 kg
Operating Weight (with options): ............................................................................................................ 2474 kg
Unit Length (without options): ................................................................................................................ 4445 mm
Unit Width (without options): .................................................................................................................. 2210 mm
Unit Height without options): .................................................................................................................. 2108 mm
Altitude: ........................................................................................................................................................ 0 m
Cooling Mode
Cooling Capacity: .................................................................................................................................. 125.6 kW
EER:........................................................................................................................................................ 3.18
Energy Class-Cooling: .................................................................................................................................A
SEER: ..................................................................................................................................................... 4.55
Ns,c: ...................................................................................................................................................... 179.0 %
Performance Information
Cooling Mode
Gross Cooling Capacity: ....................................................................................................................... 109.3 kW
Net Cooling Capacity (with supply fan): ................................................................................................ 104.6 kW
Net Sensible Cooling Capacity: ............................................................................................................... 76.4 kW
Packaged Rooftop Builder EMEA 1.18 Page 1 of 4
Performance Summary For 5990
Project: Renovation Work - Al Udeid Air Base 12-02-2020
Prepared By: 03:58PM
Acoustic Information
Center Frequency Indoor Supply (dB) Indoor Return (dB) Outdoor (dB)
125 Hz 77.2 73.2 85.7
250 Hz 75.9 73.7 87.9
500 Hz 77.9 69.3 79.8
1000 Hz 77.3 72.0 79.9
2000 Hz 75.2 71.2 75.2
4000 Hz 77.4 75.0 70.4
Electric Information
Nominal Power Supply: 400-3-50 V-ph-Hz
Minimum Voltage: 360 V
Maximum Voltage: 440 V
Max Input Power**: 98.44 kW
Max Input Current**: 164.4 A
Power Factor**: 0.86
Max Start Up Current (ICF)*: 232.8 A
Standby Power: 0.35 kW
* Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + fan
current + locked rotor current of the largest compressor.
** Compressors, fans and options at their operating limits and nominal voltage of 400 V (data given on the unit nameplate).