Sop Za Makedoniju

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 7

STANDARDNA OPERATIVNA

PROCEDURA (SOP)
ZA PAKETNO
POSTROJENjE ZA PREČIŠĆAVANjE
OTPADNIH VODA
I. ISTOVAR

 OBEZBEDITI BETONSKU PODLOGU POD REZERVOAROM

• OBEZBEDITI ISPRAVNU I ISPITANU OPREMU ZA ISTOVAR PAKETNOG POSTROJENjA

II. INSTALACIJA
• PROVERITI DA LI JE REZERVOAR NIVELISAN
• PROVERITI DA LI SU INSTALIRANI DELOVI U SKLADU SA TEHNIČKIM UPUTSTVOM
• PROVERITE DA SU CEVI POVEZANE PRAVILNO
• PROVERITE DA SU SVE PUMPE POVEZANE, PRIKLjUČENE I OSIGURANE
III. OPERACIJA

Pre puštanja u rad, treba obaviti 2 tipa ispitivanja nakon povezivanja instalacije:

1. Suvi test
2. Mokri test

3.1. SUVI TEST

• PROVERITE SVE ELEKTRIČNE PRIKLjUČKE I OTKLONITE KVAROVE AKO SE


POJAVE.
• PROVERITE DA LI SVI MOTORI RADE U PRAVILNOM SMERU.
• PROVERITE RAD KOMPRESORA, DA LI PRAVILNO RADI ODAJUĆI NORMALAN NIVO
ŠUMA, BUKE I VIBRACIJA
• PROVERITE DA LI SU DIFUZORI POVEZANI I OSIGURANI
• PROVERITE DA LI SU SVI DELOVI DOBRO POVEZANI, DA NISU LABAVI I DA NE
ODAJU VIBRACIJE U TOKU RADA.
• PROVERITE DA LI IMA EVENTUALNIH CURENjANA NA CEVIMA
• PROVERITE RAD PUMPE - OBAVEZNO DA ROTIRA U PRAVILNOM SMERU.
• PROVERITE ISPRAVNOST RADA JEDINICE ZA UPRAVLjANjE PROTOKOM.
• PROVERITE DA LI SU FILTRI ZA ČISTU VODU U PRAVILNOM POLOŽAJU

3.2. MOKRI TEST

Mokro ispitivanje mora se obaviti pre puštanja u rad postrojenja:

• PROVERITE RAD KOMPRESORA, DA LI PRAVILNO RADI ODAJUĆI NORMALAN NIVO


ŠUMA, BUKE I VIBRACIJA
• PROVERITE N MERAČU PRITISKA POVRATNI PRITISAK KOMPRESORA
• POVRATNI PRITISAK NE SME BITI VIŠI OD 0,4 BARA U STANjU PUNOM VODE.
• PROVERITE PUMPE AKO D ĐE DO POJAVE BUČNIH VIBRACIJA I CURENjA.
• PROVERITE NIVO EFFLUENTA (tehnološka otpadna tekuća voda koja se ispušta u
kanalizaciju ) I KORIGUJTE GA AKO JE POTREBNO.
• SVE DELOVE DOBRO OSIGURAJTE TAKO DA NEMA VIBRACIJA NITI LABAVIH
SPOJEVA CEVIPROVERITE DA LI IMA CURENjA NA CEVIMA ZA VAZDUH I DA LI SU
PRAVILNO INSTALIRANE.
IV. POVRŠENjE I RAD

4.1. RAST BAKTERIJA

 NAPUNITE REZERVOAR KANALIZACIONOM VODOM


 NIKADA NE ISPUŠTAJTE VODU IZ MREŽE EFLUENTA, OSIM AKO IZGLEDA JASNO
ČISTA
 KONSTANTNO VIRŠTI AREACIJU I RECIRKULACIJU VODE
 MULjNA LINIJA TREBA DA RADI PUNIM KAPACITETOM
 AERATNI MINIMUM 15 DANA (Utiskivati vazduh u biološke filtere radi prečiššavanja tekućih
voda)
 NAKON 15 DANA IZDVOJITE SA DNA 5m3 MULjA U REZERVOAR/SPREMNIK ZA
DRŽANjE MULjA ILI DO EKVALAZACIONOG BAZENA.
 DODAJTE 5m3 KANALIZACIONE VODE
 SVAKODNEVNO PRATITE ISTI POSTUPAK
 PROVERITE ČISTOĆU VODE NA VRHU REZERVOARA
 AKO JE ČISTOĆA DOVOLjNA, POVEĆAJTE ULAZ KANALIZACIJE
 POGLEDAJTE ČISTOĆU EFFLUENTA
 PROVERITE FILTERE ZA ČISTU VODU AKO RUKUJETE SA FILTEROM ZA PESAK.
V. OPERACIJA

• POSTUPNO IZ DANA U DAN POVEĆAVAJTE


KOLIČINU ULAZNE VODE KAKO BISTE POSTIGLI
PROJEKTOVANI NIVO PROTOKA.
• KONSTANTNO PRAĆENjE LINIJE POVRATNOG
MULjA, DVA PUTA NA DAN
• PROVERITE MLSS VREDNOST (mešavine čvrste
suspendovane tečnosti) AREACIONOG
REZERVOARA/CISTERNE
• POSLE 30 MINUTA KONSTANTNOG RADA
TREBALO BI DA BUDE 40% IMHOFOVOG KONUSA
ISPUNjENO MULjEM (dno rezervoara/cisterne )

5.1 UKLANjANjE MULjA

•UKLANjANjE MULjA JE GLAVNI KRITERIJUM ZA NESMETAN


RAD I ODRŽAVANjE POSTROJENjA U DOBROM STANjU.
•KOLIČINA MULjA RAZLIKOVAĆE SE OD KAPACITETA RADA
POSTROJENjA.
• AKO POSTROJENjE IMA AUTOMATSKE VENTILE, MERI
KOLIČINU OTPADNOG MULjA PO MINUTU I UREĐUJE TAJMER
VENTILA PREMA TOME.
• VENTILE TREBA OTVORITI BAR 2 PUTA DNEVNO KAKO BI
OTPADNI MULj BIO ISCRPLjEN.
5.2 KONTROLA TOKA
• POKUŠAJTE DA USPOSTAVITE STALNI TOK SISTEMA U TOKU 24 ČASA.
• PROVERITE ULAZNI PROTOK.
• NIKADA NE PUSTITE DA SISTEM FLUKTUIRA.
• OVO JE VRLO VAŽNO ZA USKLAĐEN I EFIKASAN RAD.

5.3 AUTOMATSKI OKRETNI EKRAN


• NjIME UPRAVLjA TAJMER.
• ZAVISNO OD KVALITETA ULAZNE VODE USKLADITI TAJMER I PUSTITE DA EKRAN
RADI PO POTREBI.

5.4 VERTIKALNI MEŠAČ SA MALOM BRZINOM


• TREBA DA RADI NEPREKIDNO.

5.5 KOMPRESORI
• KOMPRESORIMA UPRAVLjA TAJMER.
• UREDITE TAJMER TAKO DA POSTOJENjE IMA VAZDUH SVE VREME.
• NE DOZVOLITE DA SISTEM OSTAJE BEZ VAZDUHA VIŠE OD 30 MINUTA.

5.6 VAZDUŠNI VENTILI


• KORISTITE VENTILACIJSKE DIFUZORE DA STABILIZUJU PROTOK U SVAKOM DELU
AERACIONOG REZERVOARA.
• NE ZATVARATI VENTILE POTPUNO I UVEK PROVERITI NIVO INDIKATORA
PRITISKA U KONTROLNOJ SOBI, MAKSIMALNO 0,4 BARA.
• PROVERITE DA LI VENTIL ZA SMANjENjE PRITISKA RADI I ISPUSTITE VAZDUH NA
0,5 BAR.

5.7 PRIKUPLjANjE SKRAME


• PROVERITE KOLIČINU SKRAME I UREDITE NIVO ZA PRIKUPLjANjE.
• PROVERITE PROTOK VAZDUHA I RASPOREDITE AKO JE POTREBNO PREMESTITI
SKRAMU OD MESTA TALOŽENjA DO AERACIONOG REZERVOARA

5.8 ČIŠĆENjE FILTERA ZA VODU


• TO SU VITALNI ELEMENTI KOJI ŠTITE PUMPE ZA ČISTU VODU I FILTRE ZA PESAK.
• NE UKLANjATI ČISTE FILTERE ZA VODU.
• AKO VODA PROLAZI OTVORITE VENTIL ISPOD REZERVOARA ZA ČISTU VODU.
• FILTERE ZA ČISTU VODU TREBA ČISTITI KADA SU ZAČEPLjENI/ZAPUŠENI.

5.9 ZAČEPLjENI FILTERI ČISTE VODE


• STAVITE FILTERE U VODU KOJA SADŽI 5% OZONA,
• NEKA OSTANU 1 SAT U RASTVORU,
• IZVADITE IH I OPERITE VODOM POD PRITISKOM

You might also like