JY997D37801E Side

B
Side
A JAPANESE
Side
B ENGLISH Indications of LEDs
Manual name Manual No. Description
FX3UC Series JY997D28701 Explains the FX3UC Series PLC LED Indication ( : Off, : On)
Shielding cover
User’s Manual MODEL CODE: specifications for I/O, wiring, RUN : Normal operation
Shielded cable RUN
- Hardware Edition 09R519 installation, and maintenance. INIT. : Abnormal operation
FX3U-ENET-L
100M
JY997D38401 SD INIT. : Initial processing normal completion
FX Configurator-EN-L Describes the operation method of RD
MODEL CODE: : Initial processing not performed
operation Manual FX Configurator-EN-L. ERR.
09R929 COM.ERR.

INSTALLATION MANUAL Only this INSTALLATION MANUAL is supplied with the FX3U-ENET-L.
Wires*
EMI gasket
* These wires are used to improve the conductivity between the door and control POWER
100M : 100Mbps
: 10Mbps/When not connected
For more details regarding the FX3U/FX3UC Series hardware, PLC programming SD : Data being sent
cabinet. C1
commands, and special function blocks/units, refer to the appropriate manuals. C2
Manual Number JY997D37801  Notes for compliance with EN61131-2:2007 C3 : Data not being sent
How to obtain manuals C4
General notes on the use of the power supply cable. RD : Data being received
Revision E For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product. - The FX3U-ENET-L unit requires that the cable used for power supply is 30m or : Data not being received
Date February 2018 less.
How to obtain FX Configurator-EN-L ERR. : Abnormal setting display*
The parameter setting software, FX Configurator-EN-L is not supplied with this product. - When the cable used for power supply exceeds 30m, a noise filter (Ex. TDK-
Lambda MBS1205-22 or similar) should be placed on the 24V DC power cabling : Normal setting display
Consult with the Mitsubishi Electric dealer from who you purchased this product
as close (within 500mm) to the FX3U-ENET-L termination points as possible, COM. ERR. : Abnormal communication display
This manual describes the part names, dimensions, mounting, and specifications Certification of UL, cUL standards refer to following figure. : Normal communication display
of the product. Before use, read this manual and the manuals of all relevant FX3U-ENET-L units comply with the UL standards (UL, cUL). POWER : Power on
products fully to acquire proficiency in handling and operating the product. Make UL, cUL File Number: E95239 Exceeding 30m
sure to learn all the product information, safety information, and precautions. FX3U-ENET-L 24V DC power : Power off
Regarding the standards that comply with the main unit, please refer to either the FX 500mm or less Noise
Store this manual in a safe place so that it can be taken out and read whenever series product catalog or consult with your nearest Mitsubishi product provider. 24V DC supply C1 to C4 : TCP/IP - Connection established
Filter
necessary. Always forward it to the end user. UDP - Open
Registration: Ethernet is a trademark of Xerox Corporation. Compliance with EC directive (CE Marking) : TCP/IP - Connection not established
The company and product name described in this manual are registered 1. Outline UDP - Closed
This note does not guarantee that an entire mechanical module produced in
trademarks or the trademarks of their respective companies. FX3U-ENET-L is an Ethernet unit for the FX3U/FX3UC Series PLC that is compliant with
accordance with the contents of this note will comply with the following standards. *The ERR LED illuminates in the following cases:
100BASE-TX/10BASE-T and has the features as follows. - When a parameter setting error occurs in the Ethernet unit
Compliance to EMC directive and LVD directive for the entire mechanical module
Effective February 2018 1) Data and programs within the PLC can be sent and received via Ethernet by - When an operational error occurs in the PLC CPU
should be checked by the user / manufacturer. For more information please consult
Specifications are subject to change without notice. using GX Works2 Ver. 1.09K or later/GX Developer Ver.8.88S or later.*1 - When an error is found in the Ethernet unit (H/W error)
with your nearest Mitsubishi product provider.
 2009 Mitsubishi Electric Corporation Regarding the standards that comply with the main unit, please refer to either the FX 2) Communication between PLCs or with a general Ethernet device is possible by Pin Configuration
series product catalog or consult with your nearest Mitsubishi product provider. fixed buffer communication. (TCP/IP or UDP/IP)*1 The pin configuration of FX3U-ENET-L RJ45 type modular jack (for category 5 or
Safety Precautions (Read these precautions before use.) Requirement for Compliance with EMC directive 3) Users can develop custom software to communicate with the PLC by using MC category 3) is as follows:
The following products have shown compliance through direct testing (of the identified (MELSEC Communication) protocol (A-compatible 1E frame subset, for details,
This manual classifies the safety precautions into two categories: Pin No. Signal Direction Contents
standards below) and design analysis (through the creation of a technical construction refer to user's manual). (TCP/IP or UDP/IP)*1
and . file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when 4) E-mail can be sent. (SMTP protocol) 1 TD+ Out + side of sending data
used as directed by the appropriate documentation. 5) The FX3U-ENET-L parameters can be set easily using FX Configurator-EN-L. 2 TD Out  side of sending data
Indicates that incorrect handling may cause hazardous Attention 6) The diagnostic functions of FX Configurator-EN-L enables easy diagnostics and
conditions, resulting in death or severe injury. This product is designed for use in industrial applications. troubleshooting of the FX3U-ENET-L. 3 RD+ In + side of receiving data

Indicates that incorrect handling may cause hazardous Type: Programmable Controller (Open Type Equipment) *1 It is necessary to set up the open system by configuring open settings in 8 1 4 Not used -
conditions, resulting in medium or slight personal injury Models: MELSEC FX3U series manufactured advance.
5 Not used -
or physical damage. from October 1st, 2009 FX3U-ENET-L 1.1 Incorporated Items
6 RD In  side of receiving data
Standard Remark Included Item 7 Not used -
Depending on the circumstances, procedures indicated by may
also cause severe injury. EN61131-2:2007 C omp lia nce w ith a ll rele van t aspe cts of th e FX3U-ENET-L 1 unit 8 Not used -
It is important to follow all precautions for personal safety. Programmable controllers standard.
- Equipment requirements EMI Label for indication of special function unit/block number 1 sheet Cables to be used
Associated Manuals and tests • Radiated Emission Dust proof protection sheet 1 sheet Category 5e, shielded twisted-pair cable
• Conducted Emission
For 10BASE-T Category 5, shielded twisted-pair cable
Manual name Manual No. Description EMS Installation Manual (Japanese version, English version) 1 manual each Category 3, shielded twisted-pair cable
• Radiated electromagnetic field
FX3U-ENET-L
• Fast transient burst 1.2 External Dimensions and Part Names Category 5e, shielded twisted-pair cable
I N S TA L L AT I O N JY997D37801 This manual For 100BASE-TX
• Electrostatic discharge Category 5, shielded twisted-pair cable
MANUAL • High-energy surge 2-4.5 mounting holes [16]
Describes the specifications, • Voltage drops and interruptions [5]
FX3U-ENET-L
JY997D38001
wiring, installation, maintenance, • Conducted RF [1] [6] 2. Installation
MODEL CODE: • Power frequency magnetic field [4] [7]
User’s Manual an d op e ra ti o ns o f t h e F X 3 U - [8]
09R722 INSTALLATION

90(3.55")
80(3.15")
ENET-L. [9]
Caution for EC Directive [17] PRECAUTIONS
[10]
Briefly describes the I/O [2] [11]
FX3U Series  Installation in Enclosure  Make sure to cut off all phases of the power supply externally before
specifications, wiring, and
H A R D WA R E JY997D50301 Programmable logic controllers are open-type devices that must be installed [14] attempting installation work.
installation of the FX 3U Series [12]
MANUAL and used within conductive control cabinets. Please use the programmable [15] Failure to do so may cause electric shock or damage to the product.
PLC.
logic controller while installed within a conductive shielded control cabinet. [3] [13]  Before attaching or replacing the main unit or extension unit, externally cut
FX3U Series JY997D16501 Explains the FX 3U Series PLC Please secure the cabinet door to the control cabinet (for conduction). off all phases of the power supply. Failure to do so may cause malfunctions
9(0.36") 4(0.16")
User’s Manual MODEL CODE: specifications for I/O, wiring, Installation within a control cabinet greatly affects the safety of the system and Top cover is or misoperations.
87(3.43") 55(2.17") removed
- Hardware Edition 09R516 installation, and maintenance. aids in shielding noise from the programmable logic controller.
 Control cabinet INSTALLATION
FX 3S /FX 3G /FX 3GC /
- The control cabinet must be conductive. Unit: mm (inches) PRECAUTIONS
FX3U/FX3UC Series JY997D16601 Describes PLC programming for
Programming Manual MODEL CODE: basic/applied instructions and - Ground the control cabinet with the thickest possible grounding cable. MASS(Weigth): Approx. 0.3 kg (0.66 lbs) DIN rail width: 35 mm (1.38”)  Use the product within the generic environment specifications described in
- Basic & Applied 09R517 devices. - To ensure that there is electric contact between the control cabinet and its door, [1] Direct mounting hole:2 holes of 4.5 mm (0.18”) PLC main unit manual (Hardware Edition).
Instruction Edition connect the cabinet and its doors with thick wires. Used when FX3U-ENET-L is directly mounted. Never use the product in areas with excessive dust, oily smoke, conductive
- In order to suppress the leakage of radio waves, the control cabinet structure Not used when DIN rail is mounted. dusts, corrosive gas (salt air, Cl 2 , H 2 S, SO 2 or NO 2 ), flammable gas,
FX3UC(D, DS, DSS) Briefly describes the I/O must have minimal openings. Also, wrap the cable holes with a shielding cover or [2] DIN rail mounting groove [3] DIN rail mounting hook vibration or impacts, or expose it to high temperature, condensation, or rain
Series specifications, wiring, and other shielding devices. [4] Extension cable [5] RUN LED and wind. If the product is used in such conditions, fire, malfunctions,
JY997D50501 [6] INIT. LED [7] 100M LED
H A R D WA R E installation of the FX3UC Series - The gap between the control cabinet and its door must be as small as possible by deterioration or damage may occur.
MANUAL PLC. [8] SD LED [9] RD LED  When tightening the terminal screws, stay within the specified torque range.
attaching EMI gaskets between them. [10] ERR. LED [11] COM.ERR. LED
Briefly describes the I/O When tightened insufficiently, short-circuit or failure may occur. When
F X 3 U C - 3 2 M T- LT- 2 [12] POWER LED [13] C1 to C4 LEDs
specifications, wiring, and tightened too much, the screws or the unit may be damaged, causing the
H A R D WA R E JY997D31601 [14] 10BASE-T/100BASE-TX connector (RJ45)
unit disposal, short-circuit, or failure.
installation of the FX3UC -32MT- [15] Top cover
MANUAL  Do not touch the conductive part or electric parts of this unit directly.
LT-2 PLC. [16] External 24VDC terminal (M3 terminal block screw)
Doing so may cause failure or malfunctions.
[17] Extension connector

INSTALLATION DESIGN Item Specifications 4.1 Grounding


PRECAUTIONS PRECAUTIONS Other Other Other
Fixed buffer PLC equipment PLC equipment PLC equipment
 Install the unit on a flat surface.  Make sure to observe the following precautions in order to prevent any damage to communica- 2 connections
Number of
If the mounting surface is rough, undue force will be applied to the PC board, the machinery or accidents due to abnormal data written to the PLC under the tion
thereby causing nonconformities. simultaneously
influence of noise: open connections Independent grounding Shared grounding Common grounding
 Install the product securely using a DIN rail or mounting screws. MELSOFT
1)Do not bundle the main circuit line together with or lay it close to the main allowed (Best condition) (Good condition) (Not allowed)
 When drilling screw holes or wiring, make sure that cutting or wire debris connection + A total of 2 connections
dose not enter the ventilation slits. circuit, high-voltage line or load line. MC protocol
Failure to do so may cause fire, equipment failures or malfunctions. Otherwise, noise disturbance and/or surge induction are likey to take place. Wiring and power supply wiring between PLC and FX3U-ENET-L
 Be sure to remove the dust proof sheet from the PLC's ventilation port when As a guideline, lay the control line at least 100mm (3.94") or more away from Trans- Fixed buffer 1023 word  2 Example usage of FX3U
installation work is completed. the main circuit or high-voltage lines. mission
Failure to do so may cause fire, equipment failures or malfunctions. data Attached file 2048 word  1 Externally power supply for FX3U-ENET-L
2)Ground the shield wire or shield of a shielded cable. However, do not ground E-mail
 Connect extension cables securely to their designated connectors. them at the same point as the high-voltage lines. storage 24V DC
*2*3
Loose connections may cause malfunctions. memory Main text 256 word  1
 Install module so that excessive force will not be applied to the unit or cables.
D Grounding
Failure to do so may result in wire damage/breakage or PLC failure. Number of I/O occupied points 8 points
2.1 Mounting (100 Ω or less)
The FX3U-ENET-L can be mounted directly using screws or on a DIN rail 24 V DC 240 mA, 24 V DC +20%, -15%,
STARTUP AND 24+
(DIN46227).
MAINTENANCE external power supply ripple (p-p) less than 5% 24- Ethernet
2.1.1 Direct Mounting PRECAUTIONS modular jack
The FX3U-ENET-L can be mounted with M4 screws by using the direct mounting Allowable FX3U
ENET-L (RJ-45)
holes.  Do not touch any terminals or connector while the PLC's power is on. Instanta- Operation can be continued upon occurrence of
Power
A space of 1 to 2 mm (0.04” to 0.08”) between each unit is necessary. Doing so may cause electrical shock or malfunctions. neous power instantaneous power failure for 1 ms or less. LAN
supply
2.1.2 DIN Rail Mounting  Before cleaning or retightening screws, externally cut off all phases of the power failure time
specifi-
The FX3U-ENET-L can be mounted on a DIN rail (DIN46227, 35 mm width). supply. cations 5 V DC of PLC is not used.
Failure to do so may cause malfunction or failure of this unit. (5 V DC is converted from 24 V DC external
1) Fit the upper edge of the DIN rail mounting 1) 5 V DC HUB
When the screws are tightened insufficiently, they may fall out and cause a short- power supply.)
groove (fig. A) onto the DIN rail. internal power supply
circuit or malfunction. When tightened too much, the screws or the unit may be Make sure to observe the power-on timing and
2) Push the unit onto the DIN rail. damaged, resulting in short-circuit, or malfunction. the procedure.
 When controlling the PLC (especially when changing data, the program or
A changing the operating conditions) during operation, ensure that it is safe to do 90(H)  55(W)  87(D) [mm] 电器电子产品有害物质限制使用标识要求」的表示方式
External dimensions
so. 3.55"(H)  2.17"(W)  3.43"(D) [inches]
MASS (Weight) Approx. 0.3 kg (0.66 lbs)
STARTUP AND
2) MAINTENANCE Number of connectable units to Note: This symbol mark is for China only.
1
PRECAUTIONS the main unit
含有有害6物质的名称,含有量,含有部品
2.1.3 Procedure for connecting with the FX3U Series PLC  Do not disassemble or modify the unit. *1 Length between a hub and a node.  本产品中所含有的有害 6 物质的名称,含有量,含有部品如下表
When connecting to an FX3U: Doing so may cause fire, equipment failures, or malfunctions. *2 Refer to the FX3U-ENET-L User's Manual of e-mail sending function 所示。
Before connections, turn off the power to the 1)  The unit case is made of resin. If dropped or subjected to strong impact, the unit specifications. 产品中有害物质的名称及含量
PLC. may be damaged.
*3 It is not possible to send an attached file and main text simultaneously.
1) Remove the extension device connector 3)  When this unit is installed or removed from the panel, make sure to externally cut 有害物质
cover of the main unit. off all phases of the power supply. Failure to do so may cause malfunction or 3.1 Applicable PLC
failure of this unit. 部件名称 多溴
2) Fold and insert the extension cable in the Model name Applicability 铅 汞 镉 六价铬 多溴联苯
corresponding connector as shown to the 2) 二苯醚
(Pb) (Hg) (Cd) (Cr(VI)) (PBB)
right. DISPOSAL
FX3U Series PLC
Ver. 2.21 and later (PBDE)
3) Reattach the extension device connector PRECAUTIONS Only one FX3U-ENET-L unit can be connected in a main unit.
cover on the main unit.  Please contact a certified electronic waste disposal company for the Ver. 2.21 and later
可编程 外壳 ○ ○ ○ ○ ○ ○
FX3UC Series PLC*1 控制器 印刷基板
environmentally safe recycling and disposal of your device. Only one FX3U-ENET-L unit can be connected in a main unit. × ○ ○ ○ ○ ○

TRANSPORTATION AND The version number can be checked by reading the last three digits of device D8001/ 本表格依据SJ/T 11364的规定编制。
When connecting to an FX3UC: STORAGE PRECAUTIONS D8101.
When connecting the FX3U-ENET-L,
Connector cover ○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
(A) *1 An FX2NC-CNV-IF or FX3UC-1PS-5V is necessary to connect the FX3U-ENET-L
either the FX3UC-1PS-5V or FX2NC-  The product is a precision instrument. During transportation, avoid impacts larger with the FX3UC PLC. 规定的限量要求以下。
FX3UC-1PS-5V
CNV-IF is required. than those specified in the general specifications by using dedicated packaging ×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
boxes and shock-absorbing palettes. 3.2 Related software
1) The connector cover (A) of the Failure to do so may cause failures in the product.
26572规定的限量要求。
FX3UC-1PS-5V is removed as Model name Applicability
After transportation, verify operation of the product and check for damage of the 基于中国标准法的参考规格:GB/T15969.2
shown in the figure to the right. mounting part, etc.
The FX2NC-CNV-IF does not have FX Configurator-EN-L*1 Ver. 1.00 and later
a connector cover. Items other than the following are equivalent to those of the PLC main unit. GX Works2 Ver. 1.09K and later This manual confers no industrial property rights or any rights of any other kind,
Extension cable on For general specifications, refer to the manual of the PLC main unit. nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
2) Connect the extension cable as the right side Refer to the FX3U Series User's Manual - Hardware Edition. GX Developer Ver. 8.88S and later
shown to the right. held responsible for any problems involving industrial property rights which may
Refer to the FX3UC Series User's Manual - Hardware Edition.
*1 To use FX Configurator-EN-L, either of the following software should be installed. occur as a result of using the contents noted in this manual.
Item Specifications - GX Works2(Ver. 1.09K or later)
Warranty
- GX Developer (Ver. 8.88S or later)
FX3UC-1PS-5V or Exclusion of loss in opportunity and secondary loss from warranty liability
0 to 55C (32 to 131F) when operating and -20
FX2NC-CNV-IF Ambient temperature Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
to 75C (-4 to 167F) when stored 4. Wiring (1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
General Dielectric withstand (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
3. Specification specifi- voltage
500 V AC for one minute WIRING (3) Special damages and secondary damages whether foreseeable or not, compensation for
For details on specifications, refer to the following manual. Between all PRECAUTIONS
cation accidents, and compensation for damages to products other than Mitsubishi products.
Refer to the FX3U-ENET-L User's Manual. 5 M or higher by 500 V terminals and the
ground terminal  Make sure to cut off all phases of the power supply externally before (4) Replacement by the user, maintenance of on-site equipment, start-up test run
Insulation resistance DC insulation resistance and other tasks.
DESIGN tester attempting wiring work.
PRECAUTIONS Failure to do so may cause electric shock or damage to the product.

 Make sure to include the following safety circuits outside the PLC to ensure
Data transmission
100 Mbps 10 Mbps For safe use
speed WIRING
safe system operation even during external power supply problems or PLC
PRECAUTIONS  This product has been manufactured as a general-purpose part for general
failure. Communication
Otherwise, malfunctions may cause serious accidents. Full-duplex/Half-duplex industries, and has not been designed or manufactured to be incorporated in
Trans- method  Before wiring the unit, confirm that the rated voltage and terminal allocation
1)Most importantly, have the following: an emergency stop circuit, a a device or system used in purposes related to human life.
mission of the unit are correct. An incorrect voltage supply and/or incorrect wiring
protection circuit, an interlock circuit for opposite movements (such as Transmission method Base band  Before using the product for special purposes such as nuclear power, electric
specifi- may cause fire, malfunction, or failure.
normal vs. reverse rotation), and an interlock circuit (to prevent damage power, aerospace, medicine or passenger movement vehicles, consult with
to the equipment at the upper and lower positioning limits). cations Maximum segment  Perform class D grounding (grounding resistance: 100 or less) to the
100 m (328’1”)*1 Mitsubishi Electric.
2)Note that when the PLC main unit detects an error such as a watchdog length grounding terminal on the main unit.  This product has been manufactured under strict quality control. However
timer error, during self diagnosis, all outputs are turned off. Also, when an Do not use common grounding with heavy electrical systems.
Maximum number of Cascade connection Cascade connection when installing the product where major accidents or losses could occur if the
error that cannot be detected by the PLC main unit occurs in an input/  Prevent cutting or wiring debris from entering the main unit. Failure to do so product fails, install appropriate backup or failsafe functions in the system.
output control block, output control may be disabled. nodes/connection Maximum 2 stages Maximum 4 stages
cause fire, malfunctions, or failures.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such cases.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
JY997D37801E Side
B
Side
A JAPANESE
Side
B ENGLISH Indications of LEDs
Manual name Manual No. Description
FX3UC Series JY997D28701 Explains the FX3UC Series PLC LED Indication ( : Off, : On)
Shielding cover
User’s Manual MODEL CODE: specifications for I/O, wiring, RUN : Normal operation
Shielded cable RUN
- Hardware Edition 09R519 installation, and maintenance. INIT. : Abnormal operation
FX3U-ENET-L
100M
JY997D38401 SD INIT. : Initial processing normal completion
FX Configurator-EN-L Describes the operation method of RD
MODEL CODE: : Initial processing not performed
operation Manual FX Configurator-EN-L. ERR.
09R929 COM.ERR.

INSTALLATION MANUAL Only this INSTALLATION MANUAL is supplied with the FX3U-ENET-L.
Wires*
EMI gasket
* These wires are used to improve the conductivity between the door and control POWER
100M : 100Mbps
: 10Mbps/When not connected
For more details regarding the FX3U/FX3UC Series hardware, PLC programming SD : Data being sent
cabinet. C1
commands, and special function blocks/units, refer to the appropriate manuals. C2
Manual Number JY997D37801  Notes for compliance with EN61131-2:2007 C3 : Data not being sent
How to obtain manuals C4
General notes on the use of the power supply cable. RD : Data being received
Revision E For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product. - The FX3U-ENET-L unit requires that the cable used for power supply is 30m or : Data not being received
Date February 2018 less.
How to obtain FX Configurator-EN-L ERR. : Abnormal setting display*
The parameter setting software, FX Configurator-EN-L is not supplied with this product. - When the cable used for power supply exceeds 30m, a noise filter (Ex. TDK-
Lambda MBS1205-22 or similar) should be placed on the 24V DC power cabling : Normal setting display
Consult with the Mitsubishi Electric dealer from who you purchased this product
as close (within 500mm) to the FX3U-ENET-L termination points as possible, COM. ERR. : Abnormal communication display
This manual describes the part names, dimensions, mounting, and specifications Certification of UL, cUL standards refer to following figure. : Normal communication display
of the product. Before use, read this manual and the manuals of all relevant FX3U-ENET-L units comply with the UL standards (UL, cUL). POWER : Power on
products fully to acquire proficiency in handling and operating the product. Make UL, cUL File Number: E95239 Exceeding 30m
sure to learn all the product information, safety information, and precautions. FX3U-ENET-L 24V DC power : Power off
Regarding the standards that comply with the main unit, please refer to either the FX 500mm or less Noise
Store this manual in a safe place so that it can be taken out and read whenever series product catalog or consult with your nearest Mitsubishi product provider. 24V DC supply C1 to C4 : TCP/IP - Connection established
Filter
necessary. Always forward it to the end user. UDP - Open
Registration: Ethernet is a trademark of Xerox Corporation. Compliance with EC directive (CE Marking) : TCP/IP - Connection not established
The company and product name described in this manual are registered 1. Outline UDP - Closed
This note does not guarantee that an entire mechanical module produced in
trademarks or the trademarks of their respective companies. FX3U-ENET-L is an Ethernet unit for the FX3U/FX3UC Series PLC that is compliant with
accordance with the contents of this note will comply with the following standards. *The ERR LED illuminates in the following cases:
100BASE-TX/10BASE-T and has the features as follows. - When a parameter setting error occurs in the Ethernet unit
Compliance to EMC directive and LVD directive for the entire mechanical module
Effective February 2018 1) Data and programs within the PLC can be sent and received via Ethernet by - When an operational error occurs in the PLC CPU
should be checked by the user / manufacturer. For more information please consult
Specifications are subject to change without notice. using GX Works2 Ver. 1.09K or later/GX Developer Ver.8.88S or later.*1 - When an error is found in the Ethernet unit (H/W error)
with your nearest Mitsubishi product provider.
 2009 Mitsubishi Electric Corporation Regarding the standards that comply with the main unit, please refer to either the FX 2) Communication between PLCs or with a general Ethernet device is possible by Pin Configuration
series product catalog or consult with your nearest Mitsubishi product provider. fixed buffer communication. (TCP/IP or UDP/IP)*1 The pin configuration of FX3U-ENET-L RJ45 type modular jack (for category 5 or
Safety Precautions (Read these precautions before use.) Requirement for Compliance with EMC directive 3) Users can develop custom software to communicate with the PLC by using MC category 3) is as follows:
The following products have shown compliance through direct testing (of the identified (MELSEC Communication) protocol (A-compatible 1E frame subset, for details,
This manual classifies the safety precautions into two categories: Pin No. Signal Direction Contents
standards below) and design analysis (through the creation of a technical construction refer to user's manual). (TCP/IP or UDP/IP)*1
and . file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when 4) E-mail can be sent. (SMTP protocol) 1 TD+ Out + side of sending data
used as directed by the appropriate documentation. 5) The FX3U-ENET-L parameters can be set easily using FX Configurator-EN-L. 2 TD Out  side of sending data
Indicates that incorrect handling may cause hazardous Attention 6) The diagnostic functions of FX Configurator-EN-L enables easy diagnostics and
conditions, resulting in death or severe injury. This product is designed for use in industrial applications. troubleshooting of the FX3U-ENET-L. 3 RD+ In + side of receiving data

Indicates that incorrect handling may cause hazardous Type: Programmable Controller (Open Type Equipment) *1 It is necessary to set up the open system by configuring open settings in 8 1 4 Not used -
conditions, resulting in medium or slight personal injury Models: MELSEC FX3U series manufactured advance.
5 Not used -
or physical damage. from October 1st, 2009 FX3U-ENET-L 1.1 Incorporated Items
6 RD In  side of receiving data
Standard Remark Included Item 7 Not used -
Depending on the circumstances, procedures indicated by may
also cause severe injury. EN61131-2:2007 C omp lia nce w ith a ll rele van t aspe cts of th e FX3U-ENET-L 1 unit 8 Not used -
It is important to follow all precautions for personal safety. Programmable controllers standard.
- Equipment requirements EMI Label for indication of special function unit/block number 1 sheet Cables to be used
Associated Manuals and tests • Radiated Emission Dust proof protection sheet 1 sheet Category 5e, shielded twisted-pair cable
• Conducted Emission
For 10BASE-T Category 5, shielded twisted-pair cable
Manual name Manual No. Description EMS Installation Manual (Japanese version, English version) 1 manual each Category 3, shielded twisted-pair cable
• Radiated electromagnetic field
FX3U-ENET-L
• Fast transient burst 1.2 External Dimensions and Part Names Category 5e, shielded twisted-pair cable
I N S TA L L AT I O N JY997D37801 This manual For 100BASE-TX
• Electrostatic discharge Category 5, shielded twisted-pair cable
MANUAL • High-energy surge 2-4.5 mounting holes [16]
Describes the specifications, • Voltage drops and interruptions [5]
FX3U-ENET-L
JY997D38001
wiring, installation, maintenance, • Conducted RF [1] [6] 2. Installation
MODEL CODE: • Power frequency magnetic field [4] [7]
User’s Manual an d op e ra ti o ns o f t h e F X 3 U - [8]
09R722 INSTALLATION

90(3.55")
80(3.15")
ENET-L. [9]
Caution for EC Directive [17] PRECAUTIONS
[10]
Briefly describes the I/O [2] [11]
FX3U Series  Installation in Enclosure  Make sure to cut off all phases of the power supply externally before
specifications, wiring, and
H A R D WA R E JY997D50301 Programmable logic controllers are open-type devices that must be installed [14] attempting installation work.
installation of the FX 3U Series [12]
MANUAL and used within conductive control cabinets. Please use the programmable [15] Failure to do so may cause electric shock or damage to the product.
PLC.
logic controller while installed within a conductive shielded control cabinet. [3] [13]  Before attaching or replacing the main unit or extension unit, externally cut
FX3U Series JY997D16501 Explains the FX 3U Series PLC Please secure the cabinet door to the control cabinet (for conduction). off all phases of the power supply. Failure to do so may cause malfunctions
9(0.36") 4(0.16")
User’s Manual MODEL CODE: specifications for I/O, wiring, Installation within a control cabinet greatly affects the safety of the system and Top cover is or misoperations.
87(3.43") 55(2.17") removed
- Hardware Edition 09R516 installation, and maintenance. aids in shielding noise from the programmable logic controller.
 Control cabinet INSTALLATION
FX 3S /FX 3G /FX 3GC /
- The control cabinet must be conductive. Unit: mm (inches) PRECAUTIONS
FX3U/FX3UC Series JY997D16601 Describes PLC programming for
Programming Manual MODEL CODE: basic/applied instructions and - Ground the control cabinet with the thickest possible grounding cable. MASS(Weigth): Approx. 0.3 kg (0.66 lbs) DIN rail width: 35 mm (1.38”)  Use the product within the generic environment specifications described in
- Basic & Applied 09R517 devices. - To ensure that there is electric contact between the control cabinet and its door, [1] Direct mounting hole:2 holes of 4.5 mm (0.18”) PLC main unit manual (Hardware Edition).
Instruction Edition connect the cabinet and its doors with thick wires. Used when FX3U-ENET-L is directly mounted. Never use the product in areas with excessive dust, oily smoke, conductive
- In order to suppress the leakage of radio waves, the control cabinet structure Not used when DIN rail is mounted. dusts, corrosive gas (salt air, Cl 2 , H 2 S, SO 2 or NO 2 ), flammable gas,
FX3UC(D, DS, DSS) Briefly describes the I/O must have minimal openings. Also, wrap the cable holes with a shielding cover or [2] DIN rail mounting groove [3] DIN rail mounting hook vibration or impacts, or expose it to high temperature, condensation, or rain
Series specifications, wiring, and other shielding devices. [4] Extension cable [5] RUN LED and wind. If the product is used in such conditions, fire, malfunctions,
JY997D50501 [6] INIT. LED [7] 100M LED
H A R D WA R E installation of the FX3UC Series - The gap between the control cabinet and its door must be as small as possible by deterioration or damage may occur.
MANUAL PLC. [8] SD LED [9] RD LED  When tightening the terminal screws, stay within the specified torque range.
attaching EMI gaskets between them. [10] ERR. LED [11] COM.ERR. LED
Briefly describes the I/O When tightened insufficiently, short-circuit or failure may occur. When
F X 3 U C - 3 2 M T- LT- 2 [12] POWER LED [13] C1 to C4 LEDs
specifications, wiring, and tightened too much, the screws or the unit may be damaged, causing the
H A R D WA R E JY997D31601 [14] 10BASE-T/100BASE-TX connector (RJ45)
unit disposal, short-circuit, or failure.
installation of the FX3UC -32MT- [15] Top cover
MANUAL  Do not touch the conductive part or electric parts of this unit directly.
LT-2 PLC. [16] External 24VDC terminal (M3 terminal block screw)
Doing so may cause failure or malfunctions.
[17] Extension connector

INSTALLATION DESIGN Item Specifications 4.1 Grounding


PRECAUTIONS PRECAUTIONS Other Other Other
Fixed buffer PLC equipment PLC equipment PLC equipment
 Install the unit on a flat surface.  Make sure to observe the following precautions in order to prevent any damage to communica- 2 connections
Number of
If the mounting surface is rough, undue force will be applied to the PC board, the machinery or accidents due to abnormal data written to the PLC under the tion
thereby causing nonconformities. simultaneously
influence of noise: open connections Independent grounding Shared grounding Common grounding
 Install the product securely using a DIN rail or mounting screws. MELSOFT
1)Do not bundle the main circuit line together with or lay it close to the main allowed (Best condition) (Good condition) (Not allowed)
 When drilling screw holes or wiring, make sure that cutting or wire debris connection + A total of 2 connections
dose not enter the ventilation slits. circuit, high-voltage line or load line. MC protocol
Failure to do so may cause fire, equipment failures or malfunctions. Otherwise, noise disturbance and/or surge induction are likey to take place. Wiring and power supply wiring between PLC and FX3U-ENET-L
 Be sure to remove the dust proof sheet from the PLC's ventilation port when As a guideline, lay the control line at least 100mm (3.94") or more away from Trans- Fixed buffer 1023 word  2 Example usage of FX3U
installation work is completed. the main circuit or high-voltage lines. mission
Failure to do so may cause fire, equipment failures or malfunctions. data Attached file 2048 word  1 Externally power supply for FX3U-ENET-L
2)Ground the shield wire or shield of a shielded cable. However, do not ground E-mail
 Connect extension cables securely to their designated connectors. them at the same point as the high-voltage lines. storage 24V DC
*2*3
Loose connections may cause malfunctions. memory Main text 256 word  1
 Install module so that excessive force will not be applied to the unit or cables.
D Grounding
Failure to do so may result in wire damage/breakage or PLC failure. Number of I/O occupied points 8 points
2.1 Mounting (100 Ω or less)
The FX3U-ENET-L can be mounted directly using screws or on a DIN rail 24 V DC 240 mA, 24 V DC +20%, -15%,
STARTUP AND 24+
(DIN46227).
MAINTENANCE external power supply ripple (p-p) less than 5% 24- Ethernet
2.1.1 Direct Mounting PRECAUTIONS modular jack
The FX3U-ENET-L can be mounted with M4 screws by using the direct mounting Allowable FX3U
ENET-L (RJ-45)
holes.  Do not touch any terminals or connector while the PLC's power is on. Instanta- Operation can be continued upon occurrence of
Power
A space of 1 to 2 mm (0.04” to 0.08”) between each unit is necessary. Doing so may cause electrical shock or malfunctions. neous power instantaneous power failure for 1 ms or less. LAN
supply
2.1.2 DIN Rail Mounting  Before cleaning or retightening screws, externally cut off all phases of the power failure time
specifi-
The FX3U-ENET-L can be mounted on a DIN rail (DIN46227, 35 mm width). supply. cations 5 V DC of PLC is not used.
Failure to do so may cause malfunction or failure of this unit. (5 V DC is converted from 24 V DC external
1) Fit the upper edge of the DIN rail mounting 1) 5 V DC HUB
When the screws are tightened insufficiently, they may fall out and cause a short- power supply.)
groove (fig. A) onto the DIN rail. internal power supply
circuit or malfunction. When tightened too much, the screws or the unit may be Make sure to observe the power-on timing and
2) Push the unit onto the DIN rail. damaged, resulting in short-circuit, or malfunction. the procedure.
 When controlling the PLC (especially when changing data, the program or
A changing the operating conditions) during operation, ensure that it is safe to do 90(H)  55(W)  87(D) [mm] 电器电子产品有害物质限制使用标识要求」的表示方式
External dimensions
so. 3.55"(H)  2.17"(W)  3.43"(D) [inches]
MASS (Weight) Approx. 0.3 kg (0.66 lbs)
STARTUP AND
2) MAINTENANCE Number of connectable units to Note: This symbol mark is for China only.
1
PRECAUTIONS the main unit
含有有害6物质的名称,含有量,含有部品
2.1.3 Procedure for connecting with the FX3U Series PLC  Do not disassemble or modify the unit. *1 Length between a hub and a node.  本产品中所含有的有害 6 物质的名称,含有量,含有部品如下表
When connecting to an FX3U: Doing so may cause fire, equipment failures, or malfunctions. *2 Refer to the FX3U-ENET-L User's Manual of e-mail sending function 所示。
Before connections, turn off the power to the 1)  The unit case is made of resin. If dropped or subjected to strong impact, the unit specifications. 产品中有害物质的名称及含量
PLC. may be damaged.
*3 It is not possible to send an attached file and main text simultaneously.
1) Remove the extension device connector 3)  When this unit is installed or removed from the panel, make sure to externally cut 有害物质
cover of the main unit. off all phases of the power supply. Failure to do so may cause malfunction or 3.1 Applicable PLC
failure of this unit. 部件名称 多溴
2) Fold and insert the extension cable in the Model name Applicability 铅 汞 镉 六价铬 多溴联苯
corresponding connector as shown to the 2) 二苯醚
(Pb) (Hg) (Cd) (Cr(VI)) (PBB)
right. DISPOSAL
FX3U Series PLC
Ver. 2.21 and later (PBDE)
3) Reattach the extension device connector PRECAUTIONS Only one FX3U-ENET-L unit can be connected in a main unit.
cover on the main unit.  Please contact a certified electronic waste disposal company for the Ver. 2.21 and later
可编程 外壳 ○ ○ ○ ○ ○ ○
FX3UC Series PLC*1 控制器 印刷基板
environmentally safe recycling and disposal of your device. Only one FX3U-ENET-L unit can be connected in a main unit. × ○ ○ ○ ○ ○

TRANSPORTATION AND The version number can be checked by reading the last three digits of device D8001/ 本表格依据SJ/T 11364的规定编制。
When connecting to an FX3UC: STORAGE PRECAUTIONS D8101.
When connecting the FX3U-ENET-L,
Connector cover ○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
(A) *1 An FX2NC-CNV-IF or FX3UC-1PS-5V is necessary to connect the FX3U-ENET-L
either the FX3UC-1PS-5V or FX2NC-  The product is a precision instrument. During transportation, avoid impacts larger with the FX3UC PLC. 规定的限量要求以下。
FX3UC-1PS-5V
CNV-IF is required. than those specified in the general specifications by using dedicated packaging ×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
boxes and shock-absorbing palettes. 3.2 Related software
1) The connector cover (A) of the Failure to do so may cause failures in the product.
26572规定的限量要求。
FX3UC-1PS-5V is removed as Model name Applicability
After transportation, verify operation of the product and check for damage of the 基于中国标准法的参考规格:GB/T15969.2
shown in the figure to the right. mounting part, etc.
The FX2NC-CNV-IF does not have FX Configurator-EN-L*1 Ver. 1.00 and later
a connector cover. Items other than the following are equivalent to those of the PLC main unit. GX Works2 Ver. 1.09K and later This manual confers no industrial property rights or any rights of any other kind,
Extension cable on For general specifications, refer to the manual of the PLC main unit. nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
2) Connect the extension cable as the right side Refer to the FX3U Series User's Manual - Hardware Edition. GX Developer Ver. 8.88S and later
shown to the right. held responsible for any problems involving industrial property rights which may
Refer to the FX3UC Series User's Manual - Hardware Edition.
*1 To use FX Configurator-EN-L, either of the following software should be installed. occur as a result of using the contents noted in this manual.
Item Specifications - GX Works2(Ver. 1.09K or later)
Warranty
- GX Developer (Ver. 8.88S or later)
FX3UC-1PS-5V or Exclusion of loss in opportunity and secondary loss from warranty liability
0 to 55C (32 to 131F) when operating and -20
FX2NC-CNV-IF Ambient temperature Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
to 75C (-4 to 167F) when stored 4. Wiring (1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
General Dielectric withstand (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
3. Specification specifi- voltage
500 V AC for one minute WIRING (3) Special damages and secondary damages whether foreseeable or not, compensation for
For details on specifications, refer to the following manual. Between all PRECAUTIONS
cation accidents, and compensation for damages to products other than Mitsubishi products.
Refer to the FX3U-ENET-L User's Manual. 5 M or higher by 500 V terminals and the
ground terminal  Make sure to cut off all phases of the power supply externally before (4) Replacement by the user, maintenance of on-site equipment, start-up test run
Insulation resistance DC insulation resistance and other tasks.
DESIGN tester attempting wiring work.
PRECAUTIONS Failure to do so may cause electric shock or damage to the product.

 Make sure to include the following safety circuits outside the PLC to ensure
Data transmission
100 Mbps 10 Mbps For safe use
speed WIRING
safe system operation even during external power supply problems or PLC
PRECAUTIONS  This product has been manufactured as a general-purpose part for general
failure. Communication
Otherwise, malfunctions may cause serious accidents. Full-duplex/Half-duplex industries, and has not been designed or manufactured to be incorporated in
Trans- method  Before wiring the unit, confirm that the rated voltage and terminal allocation
1)Most importantly, have the following: an emergency stop circuit, a a device or system used in purposes related to human life.
mission of the unit are correct. An incorrect voltage supply and/or incorrect wiring
protection circuit, an interlock circuit for opposite movements (such as Transmission method Base band  Before using the product for special purposes such as nuclear power, electric
specifi- may cause fire, malfunction, or failure.
normal vs. reverse rotation), and an interlock circuit (to prevent damage power, aerospace, medicine or passenger movement vehicles, consult with
to the equipment at the upper and lower positioning limits). cations Maximum segment  Perform class D grounding (grounding resistance: 100 or less) to the
100 m (328’1”)*1 Mitsubishi Electric.
2)Note that when the PLC main unit detects an error such as a watchdog length grounding terminal on the main unit.  This product has been manufactured under strict quality control. However
timer error, during self diagnosis, all outputs are turned off. Also, when an Do not use common grounding with heavy electrical systems.
Maximum number of Cascade connection Cascade connection when installing the product where major accidents or losses could occur if the
error that cannot be detected by the PLC main unit occurs in an input/  Prevent cutting or wiring debris from entering the main unit. Failure to do so product fails, install appropriate backup or failsafe functions in the system.
output control block, output control may be disabled. nodes/connection Maximum 2 stages Maximum 4 stages
cause fire, malfunctions, or failures.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such cases.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
JY997D37801E Side
B
Side
A JAPANESE
Side
B ENGLISH Indications of LEDs
Manual name Manual No. Description
FX3UC Series JY997D28701 Explains the FX3UC Series PLC LED Indication ( : Off, : On)
Shielding cover
User’s Manual MODEL CODE: specifications for I/O, wiring, RUN : Normal operation
Shielded cable RUN
- Hardware Edition 09R519 installation, and maintenance. INIT. : Abnormal operation
FX3U-ENET-L
100M
JY997D38401 SD INIT. : Initial processing normal completion
FX Configurator-EN-L Describes the operation method of RD
MODEL CODE: : Initial processing not performed
operation Manual FX Configurator-EN-L. ERR.
09R929 COM.ERR.

INSTALLATION MANUAL Only this INSTALLATION MANUAL is supplied with the FX3U-ENET-L.
Wires*
EMI gasket
* These wires are used to improve the conductivity between the door and control POWER
100M : 100Mbps
: 10Mbps/When not connected
For more details regarding the FX3U/FX3UC Series hardware, PLC programming SD : Data being sent
cabinet. C1
commands, and special function blocks/units, refer to the appropriate manuals. C2
Manual Number JY997D37801  Notes for compliance with EN61131-2:2007 C3 : Data not being sent
How to obtain manuals C4
General notes on the use of the power supply cable. RD : Data being received
Revision E For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product. - The FX3U-ENET-L unit requires that the cable used for power supply is 30m or : Data not being received
Date February 2018 less.
How to obtain FX Configurator-EN-L ERR. : Abnormal setting display*
The parameter setting software, FX Configurator-EN-L is not supplied with this product. - When the cable used for power supply exceeds 30m, a noise filter (Ex. TDK-
Lambda MBS1205-22 or similar) should be placed on the 24V DC power cabling : Normal setting display
Consult with the Mitsubishi Electric dealer from who you purchased this product
as close (within 500mm) to the FX3U-ENET-L termination points as possible, COM. ERR. : Abnormal communication display
This manual describes the part names, dimensions, mounting, and specifications Certification of UL, cUL standards refer to following figure. : Normal communication display
of the product. Before use, read this manual and the manuals of all relevant FX3U-ENET-L units comply with the UL standards (UL, cUL). POWER : Power on
products fully to acquire proficiency in handling and operating the product. Make UL, cUL File Number: E95239 Exceeding 30m
sure to learn all the product information, safety information, and precautions. FX3U-ENET-L 24V DC power : Power off
Regarding the standards that comply with the main unit, please refer to either the FX 500mm or less Noise
Store this manual in a safe place so that it can be taken out and read whenever series product catalog or consult with your nearest Mitsubishi product provider. 24V DC supply C1 to C4 : TCP/IP - Connection established
Filter
necessary. Always forward it to the end user. UDP - Open
Registration: Ethernet is a trademark of Xerox Corporation. Compliance with EC directive (CE Marking) : TCP/IP - Connection not established
The company and product name described in this manual are registered 1. Outline UDP - Closed
This note does not guarantee that an entire mechanical module produced in
trademarks or the trademarks of their respective companies. FX3U-ENET-L is an Ethernet unit for the FX3U/FX3UC Series PLC that is compliant with
accordance with the contents of this note will comply with the following standards. *The ERR LED illuminates in the following cases:
100BASE-TX/10BASE-T and has the features as follows. - When a parameter setting error occurs in the Ethernet unit
Compliance to EMC directive and LVD directive for the entire mechanical module
Effective February 2018 1) Data and programs within the PLC can be sent and received via Ethernet by - When an operational error occurs in the PLC CPU
should be checked by the user / manufacturer. For more information please consult
Specifications are subject to change without notice. using GX Works2 Ver. 1.09K or later/GX Developer Ver.8.88S or later.*1 - When an error is found in the Ethernet unit (H/W error)
with your nearest Mitsubishi product provider.
 2009 Mitsubishi Electric Corporation Regarding the standards that comply with the main unit, please refer to either the FX 2) Communication between PLCs or with a general Ethernet device is possible by Pin Configuration
series product catalog or consult with your nearest Mitsubishi product provider. fixed buffer communication. (TCP/IP or UDP/IP)*1 The pin configuration of FX3U-ENET-L RJ45 type modular jack (for category 5 or
Safety Precautions (Read these precautions before use.) Requirement for Compliance with EMC directive 3) Users can develop custom software to communicate with the PLC by using MC category 3) is as follows:
The following products have shown compliance through direct testing (of the identified (MELSEC Communication) protocol (A-compatible 1E frame subset, for details,
This manual classifies the safety precautions into two categories: Pin No. Signal Direction Contents
standards below) and design analysis (through the creation of a technical construction refer to user's manual). (TCP/IP or UDP/IP)*1
and . file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when 4) E-mail can be sent. (SMTP protocol) 1 TD+ Out + side of sending data
used as directed by the appropriate documentation. 5) The FX3U-ENET-L parameters can be set easily using FX Configurator-EN-L. 2 TD Out  side of sending data
Indicates that incorrect handling may cause hazardous Attention 6) The diagnostic functions of FX Configurator-EN-L enables easy diagnostics and
conditions, resulting in death or severe injury. This product is designed for use in industrial applications. troubleshooting of the FX3U-ENET-L. 3 RD+ In + side of receiving data

Indicates that incorrect handling may cause hazardous Type: Programmable Controller (Open Type Equipment) *1 It is necessary to set up the open system by configuring open settings in 8 1 4 Not used -
conditions, resulting in medium or slight personal injury Models: MELSEC FX3U series manufactured advance.
5 Not used -
or physical damage. from October 1st, 2009 FX3U-ENET-L 1.1 Incorporated Items
6 RD In  side of receiving data
Standard Remark Included Item 7 Not used -
Depending on the circumstances, procedures indicated by may
also cause severe injury. EN61131-2:2007 C omp lia nce w ith a ll rele van t aspe cts of th e FX3U-ENET-L 1 unit 8 Not used -
It is important to follow all precautions for personal safety. Programmable controllers standard.
- Equipment requirements EMI Label for indication of special function unit/block number 1 sheet Cables to be used
Associated Manuals and tests • Radiated Emission Dust proof protection sheet 1 sheet Category 5e, shielded twisted-pair cable
• Conducted Emission
For 10BASE-T Category 5, shielded twisted-pair cable
Manual name Manual No. Description EMS Installation Manual (Japanese version, English version) 1 manual each Category 3, shielded twisted-pair cable
• Radiated electromagnetic field
FX3U-ENET-L
• Fast transient burst 1.2 External Dimensions and Part Names Category 5e, shielded twisted-pair cable
I N S TA L L AT I O N JY997D37801 This manual For 100BASE-TX
• Electrostatic discharge Category 5, shielded twisted-pair cable
MANUAL • High-energy surge 2-4.5 mounting holes [16]
Describes the specifications, • Voltage drops and interruptions [5]
FX3U-ENET-L
JY997D38001
wiring, installation, maintenance, • Conducted RF [1] [6] 2. Installation
MODEL CODE: • Power frequency magnetic field [4] [7]
User’s Manual an d op e ra ti o ns o f t h e F X 3 U - [8]
09R722 INSTALLATION

90(3.55")
80(3.15")
ENET-L. [9]
Caution for EC Directive [17] PRECAUTIONS
[10]
Briefly describes the I/O [2] [11]
FX3U Series  Installation in Enclosure  Make sure to cut off all phases of the power supply externally before
specifications, wiring, and
H A R D WA R E JY997D50301 Programmable logic controllers are open-type devices that must be installed [14] attempting installation work.
installation of the FX 3U Series [12]
MANUAL and used within conductive control cabinets. Please use the programmable [15] Failure to do so may cause electric shock or damage to the product.
PLC.
logic controller while installed within a conductive shielded control cabinet. [3] [13]  Before attaching or replacing the main unit or extension unit, externally cut
FX3U Series JY997D16501 Explains the FX 3U Series PLC Please secure the cabinet door to the control cabinet (for conduction). off all phases of the power supply. Failure to do so may cause malfunctions
9(0.36") 4(0.16")
User’s Manual MODEL CODE: specifications for I/O, wiring, Installation within a control cabinet greatly affects the safety of the system and Top cover is or misoperations.
87(3.43") 55(2.17") removed
- Hardware Edition 09R516 installation, and maintenance. aids in shielding noise from the programmable logic controller.
 Control cabinet INSTALLATION
FX 3S /FX 3G /FX 3GC /
- The control cabinet must be conductive. Unit: mm (inches) PRECAUTIONS
FX3U/FX3UC Series JY997D16601 Describes PLC programming for
Programming Manual MODEL CODE: basic/applied instructions and - Ground the control cabinet with the thickest possible grounding cable. MASS(Weigth): Approx. 0.3 kg (0.66 lbs) DIN rail width: 35 mm (1.38”)  Use the product within the generic environment specifications described in
- Basic & Applied 09R517 devices. - To ensure that there is electric contact between the control cabinet and its door, [1] Direct mounting hole:2 holes of 4.5 mm (0.18”) PLC main unit manual (Hardware Edition).
Instruction Edition connect the cabinet and its doors with thick wires. Used when FX3U-ENET-L is directly mounted. Never use the product in areas with excessive dust, oily smoke, conductive
- In order to suppress the leakage of radio waves, the control cabinet structure Not used when DIN rail is mounted. dusts, corrosive gas (salt air, Cl 2 , H 2 S, SO 2 or NO 2 ), flammable gas,
FX3UC(D, DS, DSS) Briefly describes the I/O must have minimal openings. Also, wrap the cable holes with a shielding cover or [2] DIN rail mounting groove [3] DIN rail mounting hook vibration or impacts, or expose it to high temperature, condensation, or rain
Series specifications, wiring, and other shielding devices. [4] Extension cable [5] RUN LED and wind. If the product is used in such conditions, fire, malfunctions,
JY997D50501 [6] INIT. LED [7] 100M LED
H A R D WA R E installation of the FX3UC Series - The gap between the control cabinet and its door must be as small as possible by deterioration or damage may occur.
MANUAL PLC. [8] SD LED [9] RD LED  When tightening the terminal screws, stay within the specified torque range.
attaching EMI gaskets between them. [10] ERR. LED [11] COM.ERR. LED
Briefly describes the I/O When tightened insufficiently, short-circuit or failure may occur. When
F X 3 U C - 3 2 M T- LT- 2 [12] POWER LED [13] C1 to C4 LEDs
specifications, wiring, and tightened too much, the screws or the unit may be damaged, causing the
H A R D WA R E JY997D31601 [14] 10BASE-T/100BASE-TX connector (RJ45)
unit disposal, short-circuit, or failure.
installation of the FX3UC -32MT- [15] Top cover
MANUAL  Do not touch the conductive part or electric parts of this unit directly.
LT-2 PLC. [16] External 24VDC terminal (M3 terminal block screw)
Doing so may cause failure or malfunctions.
[17] Extension connector

INSTALLATION DESIGN Item Specifications 4.1 Grounding


PRECAUTIONS PRECAUTIONS Other Other Other
Fixed buffer PLC equipment PLC equipment PLC equipment
 Install the unit on a flat surface.  Make sure to observe the following precautions in order to prevent any damage to communica- 2 connections
Number of
If the mounting surface is rough, undue force will be applied to the PC board, the machinery or accidents due to abnormal data written to the PLC under the tion
thereby causing nonconformities. simultaneously
influence of noise: open connections Independent grounding Shared grounding Common grounding
 Install the product securely using a DIN rail or mounting screws. MELSOFT
1)Do not bundle the main circuit line together with or lay it close to the main allowed (Best condition) (Good condition) (Not allowed)
 When drilling screw holes or wiring, make sure that cutting or wire debris connection + A total of 2 connections
dose not enter the ventilation slits. circuit, high-voltage line or load line. MC protocol
Failure to do so may cause fire, equipment failures or malfunctions. Otherwise, noise disturbance and/or surge induction are likey to take place. Wiring and power supply wiring between PLC and FX3U-ENET-L
 Be sure to remove the dust proof sheet from the PLC's ventilation port when As a guideline, lay the control line at least 100mm (3.94") or more away from Trans- Fixed buffer 1023 word  2 Example usage of FX3U
installation work is completed. the main circuit or high-voltage lines. mission
Failure to do so may cause fire, equipment failures or malfunctions. data Attached file 2048 word  1 Externally power supply for FX3U-ENET-L
2)Ground the shield wire or shield of a shielded cable. However, do not ground E-mail
 Connect extension cables securely to their designated connectors. them at the same point as the high-voltage lines. storage 24V DC
*2*3
Loose connections may cause malfunctions. memory Main text 256 word  1
 Install module so that excessive force will not be applied to the unit or cables.
D Grounding
Failure to do so may result in wire damage/breakage or PLC failure. Number of I/O occupied points 8 points
2.1 Mounting (100 Ω or less)
The FX3U-ENET-L can be mounted directly using screws or on a DIN rail 24 V DC 240 mA, 24 V DC +20%, -15%,
STARTUP AND 24+
(DIN46227).
MAINTENANCE external power supply ripple (p-p) less than 5% 24- Ethernet
2.1.1 Direct Mounting PRECAUTIONS modular jack
The FX3U-ENET-L can be mounted with M4 screws by using the direct mounting Allowable FX3U
ENET-L (RJ-45)
holes.  Do not touch any terminals or connector while the PLC's power is on. Instanta- Operation can be continued upon occurrence of
Power
A space of 1 to 2 mm (0.04” to 0.08”) between each unit is necessary. Doing so may cause electrical shock or malfunctions. neous power instantaneous power failure for 1 ms or less. LAN
supply
2.1.2 DIN Rail Mounting  Before cleaning or retightening screws, externally cut off all phases of the power failure time
specifi-
The FX3U-ENET-L can be mounted on a DIN rail (DIN46227, 35 mm width). supply. cations 5 V DC of PLC is not used.
Failure to do so may cause malfunction or failure of this unit. (5 V DC is converted from 24 V DC external
1) Fit the upper edge of the DIN rail mounting 1) 5 V DC HUB
When the screws are tightened insufficiently, they may fall out and cause a short- power supply.)
groove (fig. A) onto the DIN rail. internal power supply
circuit or malfunction. When tightened too much, the screws or the unit may be Make sure to observe the power-on timing and
2) Push the unit onto the DIN rail. damaged, resulting in short-circuit, or malfunction. the procedure.
 When controlling the PLC (especially when changing data, the program or
A changing the operating conditions) during operation, ensure that it is safe to do 90(H)  55(W)  87(D) [mm] 电器电子产品有害物质限制使用标识要求」的表示方式
External dimensions
so. 3.55"(H)  2.17"(W)  3.43"(D) [inches]
MASS (Weight) Approx. 0.3 kg (0.66 lbs)
STARTUP AND
2) MAINTENANCE Number of connectable units to Note: This symbol mark is for China only.
1
PRECAUTIONS the main unit
含有有害6物质的名称,含有量,含有部品
2.1.3 Procedure for connecting with the FX3U Series PLC  Do not disassemble or modify the unit. *1 Length between a hub and a node.  本产品中所含有的有害 6 物质的名称,含有量,含有部品如下表
When connecting to an FX3U: Doing so may cause fire, equipment failures, or malfunctions. *2 Refer to the FX3U-ENET-L User's Manual of e-mail sending function 所示。
Before connections, turn off the power to the 1)  The unit case is made of resin. If dropped or subjected to strong impact, the unit specifications. 产品中有害物质的名称及含量
PLC. may be damaged.
*3 It is not possible to send an attached file and main text simultaneously.
1) Remove the extension device connector 3)  When this unit is installed or removed from the panel, make sure to externally cut 有害物质
cover of the main unit. off all phases of the power supply. Failure to do so may cause malfunction or 3.1 Applicable PLC
failure of this unit. 部件名称 多溴
2) Fold and insert the extension cable in the Model name Applicability 铅 汞 镉 六价铬 多溴联苯
corresponding connector as shown to the 2) 二苯醚
(Pb) (Hg) (Cd) (Cr(VI)) (PBB)
right. DISPOSAL
FX3U Series PLC
Ver. 2.21 and later (PBDE)
3) Reattach the extension device connector PRECAUTIONS Only one FX3U-ENET-L unit can be connected in a main unit.
cover on the main unit.  Please contact a certified electronic waste disposal company for the Ver. 2.21 and later
可编程 外壳 ○ ○ ○ ○ ○ ○
FX3UC Series PLC*1 控制器 印刷基板
environmentally safe recycling and disposal of your device. Only one FX3U-ENET-L unit can be connected in a main unit. × ○ ○ ○ ○ ○

TRANSPORTATION AND The version number can be checked by reading the last three digits of device D8001/ 本表格依据SJ/T 11364的规定编制。
When connecting to an FX3UC: STORAGE PRECAUTIONS D8101.
When connecting the FX3U-ENET-L,
Connector cover ○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
(A) *1 An FX2NC-CNV-IF or FX3UC-1PS-5V is necessary to connect the FX3U-ENET-L
either the FX3UC-1PS-5V or FX2NC-  The product is a precision instrument. During transportation, avoid impacts larger with the FX3UC PLC. 规定的限量要求以下。
FX3UC-1PS-5V
CNV-IF is required. than those specified in the general specifications by using dedicated packaging ×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
boxes and shock-absorbing palettes. 3.2 Related software
1) The connector cover (A) of the Failure to do so may cause failures in the product.
26572规定的限量要求。
FX3UC-1PS-5V is removed as Model name Applicability
After transportation, verify operation of the product and check for damage of the 基于中国标准法的参考规格:GB/T15969.2
shown in the figure to the right. mounting part, etc.
The FX2NC-CNV-IF does not have FX Configurator-EN-L*1 Ver. 1.00 and later
a connector cover. Items other than the following are equivalent to those of the PLC main unit. GX Works2 Ver. 1.09K and later This manual confers no industrial property rights or any rights of any other kind,
Extension cable on For general specifications, refer to the manual of the PLC main unit. nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
2) Connect the extension cable as the right side Refer to the FX3U Series User's Manual - Hardware Edition. GX Developer Ver. 8.88S and later
shown to the right. held responsible for any problems involving industrial property rights which may
Refer to the FX3UC Series User's Manual - Hardware Edition.
*1 To use FX Configurator-EN-L, either of the following software should be installed. occur as a result of using the contents noted in this manual.
Item Specifications - GX Works2(Ver. 1.09K or later)
Warranty
- GX Developer (Ver. 8.88S or later)
FX3UC-1PS-5V or Exclusion of loss in opportunity and secondary loss from warranty liability
0 to 55C (32 to 131F) when operating and -20
FX2NC-CNV-IF Ambient temperature Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
to 75C (-4 to 167F) when stored 4. Wiring (1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
General Dielectric withstand (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
3. Specification specifi- voltage
500 V AC for one minute WIRING (3) Special damages and secondary damages whether foreseeable or not, compensation for
For details on specifications, refer to the following manual. Between all PRECAUTIONS
cation accidents, and compensation for damages to products other than Mitsubishi products.
Refer to the FX3U-ENET-L User's Manual. 5 M or higher by 500 V terminals and the
ground terminal  Make sure to cut off all phases of the power supply externally before (4) Replacement by the user, maintenance of on-site equipment, start-up test run
Insulation resistance DC insulation resistance and other tasks.
DESIGN tester attempting wiring work.
PRECAUTIONS Failure to do so may cause electric shock or damage to the product.

 Make sure to include the following safety circuits outside the PLC to ensure
Data transmission
100 Mbps 10 Mbps For safe use
speed WIRING
safe system operation even during external power supply problems or PLC
PRECAUTIONS  This product has been manufactured as a general-purpose part for general
failure. Communication
Otherwise, malfunctions may cause serious accidents. Full-duplex/Half-duplex industries, and has not been designed or manufactured to be incorporated in
Trans- method  Before wiring the unit, confirm that the rated voltage and terminal allocation
1)Most importantly, have the following: an emergency stop circuit, a a device or system used in purposes related to human life.
mission of the unit are correct. An incorrect voltage supply and/or incorrect wiring
protection circuit, an interlock circuit for opposite movements (such as Transmission method Base band  Before using the product for special purposes such as nuclear power, electric
specifi- may cause fire, malfunction, or failure.
normal vs. reverse rotation), and an interlock circuit (to prevent damage power, aerospace, medicine or passenger movement vehicles, consult with
to the equipment at the upper and lower positioning limits). cations Maximum segment  Perform class D grounding (grounding resistance: 100 or less) to the
100 m (328’1”)*1 Mitsubishi Electric.
2)Note that when the PLC main unit detects an error such as a watchdog length grounding terminal on the main unit.  This product has been manufactured under strict quality control. However
timer error, during self diagnosis, all outputs are turned off. Also, when an Do not use common grounding with heavy electrical systems.
Maximum number of Cascade connection Cascade connection when installing the product where major accidents or losses could occur if the
error that cannot be detected by the PLC main unit occurs in an input/  Prevent cutting or wiring debris from entering the main unit. Failure to do so product fails, install appropriate backup or failsafe functions in the system.
output control block, output control may be disabled. nodes/connection Maximum 2 stages Maximum 4 stages
cause fire, malfunctions, or failures.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such cases.