Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

SANELAC CONSULTANTS PVT. LTD.

SL NO. DESCRIPTION UNIT QTY

D) VARIABLE AIR VOLUME DAMPER WITH THERMOSTAT :

Supply,Installation, Testing & Commission of floowing size Pressure Independent double skin VAV Boxes. The VAV
shall be complete with damper, airflow measurement, DP port across the VAV and solid-state electronic actuator
with inbuilt controller which measure air flow and modulate the box to achieve the set air flow automatically. The
Actuator shall have response time of 90 Sec for 90deg travel and capable of operating via I/O provision to take
external input to vary the airflow + it should have additional capability of automatically assign device instance
numbers to BACnet MS/TP controllers (Which means manual assigning VAV should never occur). The rate shall
including the thermostat, minimum 2.5mtr of power cable with plug top. (UPS Power socket shall be provided by
Electrical vendor at ceiling)
VAV Box shall be equipped with acoustic with 25 mm thick fibre glass of minimum 32 kg/m density or 10mm
armasound CO2 & temperature sensor signal/power cabling from VAV to junction box for thermostate will be
taken through the VAV controller and the VAV's should have the provision to accept the signal
1.1
It shall communicate with other VAV controllers through Zigbee/Modbus/Bacnet protocol.
VAV shall be with all necessary support arrangement. VAV shall be actuated by thermostat. CO2 sensor shall be
wired type and CO2 level can be monitored through BMS. The VAV price to include all wired for CO2 sensor and
temperature sensor.
HVAC Contractor should do the following without any extra charge to client :
# Engineering and Documentation shall includes the developing shop drawings, Technical submittal for approval,
DQ, IQ, OQ, As built drawing And Handing over documents with test certificates.
# Site Calibration certificate of all above sensors.
Necessary design, engineering, testing & training , O & M documentation to be included in VAV cost.
Below model number is indicative only, this will be changed as per the final vendor selection to meet the
requirement .

1.1.1
1.1.1.1 VAV-1 :- 1321CFM, 10inch, Circular type, model ST-50010 and Thermostat set 1
1.1.1.2 VAV-2 :- 970CFM, 10inch, Circular type, model ST-50010 and Thermostat set 1
1.1.1.3 VAV-3 :-809CFM, 10inch, Circular type, model ST-50010 and Thermostat set 1
1.1.1.4 VAV-4 :-446CFM, 6inch, Circular type, model ST-5006 and Thermostat set 1
1.1.1.5 VAV-5 :-128CFM, 6inch, Circular type, model ST-5006 and Thermostat set 1
1.1.1.6 VAV-6 :-1694CFM, 12inch, Circular type, model ST-50012 and Thermostat set 1

HBQ-1
SANELAC CONSULTANTS PVT. LTD.

1.1.1.7 VAV-7 :-1180CFM, 10inch, Circular type, model ST-50010 and Thermostat set 1
1.1.1.8 VAV-8 :-1330CFM, 10inch, Circular type, model ST-50010 and Thermostat set 1
1.1.1.9 VAV-9 :-3955CFM, 24inch, Circular type, model ST-50024 and Thermostat set 1
1.1.1.10 VAV-10 :-340CFM, 6inch, Circular type, model ST-5006 and Thermostat set 1

2 CABLES & CONDUITS

2.1 Supply and laying of following cables including end termination for below listed ATC Shielded armoured cable with copper lugs, brass/PVC cable glands, ta

2.1.1 2 Core 1.0 SQ. mm multistrand Annealed Tinned Copper Shielded Armoured cable. Mtr 20
2.1.2 3 Core 1.0 SQ. mm multistrand Annealed Tinned Copper Shielded Armoured cable. Mtr 400
2.1.3 2 Core 1.0 SQ. mm multistrand Annealed Tinned Copper Shielded Flexible cable. (For VAV to Thermostat) Mtr 150
Supply & Laying of Heavy duty 2mm thickness FRLS Conduit of 32mm dia with accessories like bends, collors, T
2.1.4 joint, saddles etc complete set to fix it on the wall, Clean room panel. The rate shall include chipping along the wall Mtr 570
fixing chicken mesh and making good surface of wall as required at site.
SITC of Bacnet integrator with web based user interface suitable for operation with any computer or with
3 independent touch screen to allow viewing of VAV boxes. Bacnet wiring to be brought to BMS room. The device
shall support to Zigbee/Modbus/Bacnet protocol.
Lot
3.1 Bacnet Integrator(Minimum 1 at each floor) (Number as 1
required)
Cables & Conduit quantities are tentative. Contractor should verify the quantities from the drawings & as per site
requirement before quoting the job. Any discrepancy shall be brought to the notice of the Project Manager/Client. If
the same is brought to the notice of the Client/Project Manager after the award of work, any increase in quantity
shall be provided by the vendor free of cost. HVAC vendor is suggested to check/revarify the sizes as per
Notes:
manufaturer standard before quoting the job.
All cables & conduits to be FRLS.
Contractor should include cost for all the wires, cable etc. which is required to sucessfully commissioned the VAV
System.

TOTAL OF VARIABLE AIR VOLUME DAMPER WITH THERMOSTAT CARRIED OVER TO SUMMARY

HBQ-2
SANELAC CONSULTANTS PVT. LTD.

RATE AMOUNT
(Rs.) (Rs.)

HBQ-3
SANELAC CONSULTANTS PVT. LTD.

rass/PVC cable glands, tapping, crimping,ferruling etc. complete, to be included.

HBQ-4