VAQ Station For Climate Control: Application Notes
VAQ Station For Climate Control: Application Notes
The variable air quantity station regulates the airflow within desired minimum and maximum
levels for zone-wise climate control within the specified noise levels (please specify), and
meeting the following specifications shall be furnished and installed within separate routing of
zone-wise duct or supply air outlets as shown on plan or described in schedules.
The VAQ-AL stations shall incorporate an accurate air measuring station and a motorized low
leak control damper in one assembly with the pressure independent application specific wire-
free mesh controller having multi-hop wireless self-forming, self optimizing and self healing
mesh network having real-time over the air data/firmware update. Baud rate of this network shall
be configured to 76800 bps, i.e. 8 times faster than conventional wired system.
Application Notes
1) Intelligent Climate Control for comfort
a) Variable Supply Air (master) : Shall includes high accuracy low power digital
thermostat (temperature accuracy ±0.2°C, relative humidity accuracy ±2%) with
easy set-point adjustment and large display.
b) Variable Return Air (slave) : Shall be able to receive demand from corresponding
master units through wireless gateway.
c) Constant Supply Air (master) : Shall be able to maintain an adjustable constant
supply air volume or receive potential free input to reset minimum levels during
vacancy.
d) Constant Return Air (slave) : Shall be able to receive demand from
corresponding master units through wireless gateway.
2) Adaptive Climate Control for humidity control or precise temperature control ±0.2°C
a) Adaptive Reheat Supply Air (master), Shall includes UL listed U/W type finned
heater with thyristor and adaptive PID control with auto cut during low primary
airflow.
b) Adaptive Fan Powered Supply Air (master), Shall include in room MERV13 fan
filter unit with continuous duty IE4 and sensorless adaptive PID control with
economising primary and recirculation air while controlling individual zone climate
without disturbing effective air mixing efficiency in the zone.
3) Battery powered wire-free remote module, shall includes epaper display, capacitive
touch button for remote set-point adjustment, temperature & humidity sensor
(temperature accuracy ±0.2°C, relative humidity accuracy ±2%)
Construction
These stations shall be available in custom sizes as per duct or air outlet dimensions and also
dynamically calibrated to required airflow range in a manufacturer test facility with non linear
calibration routine to provide accurate airflow measurement. It shall be available with various
mounting options or configuration. It shall include position feedback directly mounted on damper
blades with a rapid average pitot tube for end to end verification.
Duct Mounting
It shall be suitable for duct mounting having 1 inch TDF flange and installed using 4 bolt system
and bolt on cleat.
An air measuring station shall consist of 3 inch deep honeycomb patterned aluminium airflow
straightener, rapid average pressure pickups probes mounted on station, and differential
pressure transducer within a heavy gauge extruded aluminium c shaped frame. Tested and
rated for airflow measurement in accordance with AMCA standard 611 and shall accompany
calibration certificate.
A motorized low leak control damper shall be made of heavy gauge extruded aluminum airfoil
blades in c shaped frame with nylon exposed gear drive linkage; EPDM blade seals; and form fit
modulating electric actuator suitable for 20000 cycles operation and runtime of 15 seconds. It
shall include direct indication of damper through passive position feedback for proper end to end
verification of damper. Testing and ratings shall be in accordance with Class II leakage as per
AMCA standard 511.
Actuator
Damper actuators shall be factory mounted and
qualified for use with the damper and manufacturer
shall have in-house testing of elevated temperature
& cycling test in accordance with UL555S i.e. 20000
cycles operation 15 seconds fail-safe run-time.
Damper actuators shall be electric type for 24 volt
operation or pneumatic 20 psi minimum pressure.
Tested in accordance with UL555s at elevated
temperature of 177°C for 30 minutes.
The damper actuator and optional accessories are
normally externally mounted on the right hand side
of the sleeve and can be turned upside down to
overcome unforeseen clearance problems.
Optional internal mounting with access door is available upon request and shall be specified at
the time of ordering.
Actuators and optional accessories occupy space outside of the fire smoke damper sleeve and
appropriate clearances are required for inspection testing and service.
Important Note:
Sleeve thickness must not be less than the thickness of the connecting duct.
Installation
1) Install dampers in accordance with manufacturer’s Installation Instructions. Any damper
installation aspect that is not in accordance with the manufacturer’s Installation
Instructions must be approved prior to installation.
2) Dampers must be accessible to allow inspection, adjustment, and replacement of
components. The sheet metal contractor shall furnish any access doors in ductwork or
plenums required to provide this access. The general contractor shall furnish any
access doors required in walls, ceilings, or other general building construction.
3) Install dampers square and free from racking.
4) The installing contractor shall provide and install bracing for multiple section assemblies
to support assembly weight and to hold against system pressure.
5) Do not compress or stretch the damper frame into the duct or opening.
6) Attach multiple damper section assemblies together in accordance with manufacturer’s
instructions. Install support mullions for reinforcement between assemblies as required.
7) Handle dampers using the frame or sleeve. Do not lift or move dampers using blades,
actuator or jackshaft.
8) Install connections to [electric, pneumatic] actuators as specified.
9) Attach multiple damper section assemblies together in accordance with manufacturer’s
instructions. Install support mullions as reinforcement between assemblies as required.
3) Breakaway round duct collar with crimp joint bead (specify diameter)
4) Breakaway oval duct collar with crimp joint bead (specify width & height)
The VAQ-FS stations shall incorporate an accurate air measuring station and a motorised
combination of fire & smoke damper in one assembly with the pressure independent application
specific wire-free mesh controller having multi-hop wireless self-forming, self optimizing and self
healing mesh network having real-time over the air data/firmware update. Baud rate of this
network shall be configured to 76800 bps, i.e. 8 times faster than conventional wired system.
Application Notes
1) Demand Control Ventilation Economiser Unit (Normal or Free Cooling and Smoke
Extraction) with primary 74°C and secondary override 177°C heat responsive device,
appropriate damper position feedback sensor mounted on the blades, airflow monitoring
station for end to end verification and other requirements
a) Supply Air (master), regulates constant airflow during normal or free cooling and
fail-safe closure during smoke extraction shall provide fan speed control signal
analog (0-10 VDC), etc.
b) Mixed Air (on/off), complete closure during normal or free cooling and fail-safe
open during smoke extraction.
c) Return Air (slave), regulates the airflow within minimum and maximum level and
thus economise demand during low enthalpy level and fail-safe closure during
smoke extraction.
d) Optimum Fresh Air, optimise the required fresh with eq.CO2 & tVOC sensor.
Additional multiple slave battery powered wire-free indoor air quality modules
shall be used in the critical variable occupancy zone. It shall includes epaper
display, capacitive touch button for remote set-point adjustment, temperature,
humidity sensor (temperature accuracy ±0.2°C, relative humidity accuracy ±2%)
and low power indoor air quality sensor shall be suitable for 10 years of operation
in an indoor environment with 1.3% long term drift. It shall include high accuracy
airflow monitoring station for proper fresh air delivery monitoring and suitable
alarm shall be raised if actual flow is ±10% from the required airflow.
e) Optimum Exhaust Air (slave), Shall be able to receive demand from
corresponding master units through smart wireless mesh network.
f) Complete Fresh Air (master), regulates the airflow within minimum and maximum
level and thus economise demand during low enthalpy level, free cooling and air-
tight closure during normal cooling or smoke extraction with outdoor IP65
enthalpy sensor (temperature accuracy ±0.2°C, relative humidity accuracy ±2%).
It shall incorporate extruded aluminum drainable louver
g) Complete Exhaust Air, Shall be able to receive demand from corresponding
master unit through smart wireless mesh network
h) Pressurisation, Shall be able to provide dynamic airflow regulation to provide
pressurisation within safe limits during staircase/liftwell pressurisation.
Construction
These stations shall be available in custom sizes as per duct or air outlet dimensions and also
dynamically calibrated to required airflow range in a manufacturer test facility with non linear
calibration routine to provide accurate airflow measurement. It shall be available with various
mounting options or configuration. It shall include position feedback directly mounted on damper
blades with a rapid average pitot tube for end to end verification.
Actuator
Damper actuators shall be factory mounted and
qualified for use with the damper and manufacturer
shall have in-house testing of elevated temperature
& cycling test in accordance with UL555S i.e. 20000
cycles operation 15 seconds fail-safe run-time.
Damper actuators shall be electric type for 24 volt
operation or pneumatic 20 psi minimum pressure.
Tested in accordance with UL555s at elevated
temperature of 177°C for 30 minutes.
The damper actuator and optional accessories are
normally externally mounted on the right hand side
of the sleeve and can be turned upside down to
overcome unforeseen clearance problems.
Optional internal mounting with access door is available upon request and shall be specified at
the time of ordering.
Actuators and optional accessories occupy space outside of the fire smoke damper sleeve and
appropriate clearances are required for inspection testing and service.
Sleeve Thickness
Damper size and rigid or breakaway duct to sleeve connections determine the thickness of
sleeve required
Important Note:
Sleeve thickness must not be less than the thickness of the connecting duct.
Installation
1) Install dampers in accordance with manufacturer’s Installation Instructions. Any damper
installation aspect that is not in accordance with the manufacturer’s Installation
Instructions must be approved prior to installation.
2) Dampers must be accessible to allow inspection, adjustment, and replacement of
components. The sheet metal contractor shall furnish any access doors in ductwork or
plenums required to provide this access. The general contractor shall furnish any
access doors required in walls, ceilings, or other general building construction.
3) Install dampers square and free from racking.
4) The installing contractor shall provide and install bracing for multiple section assemblies
to support assembly weight and to hold against system pressure.
5) Do not compress or stretch the damper frame into the duct or opening.
6) Attach multiple damper section assemblies together in accordance with manufacturer’s
instructions. Install support mullions for reinforcement between assemblies as required.
7) Handle dampers using the frame or sleeve. Do not lift or move dampers using blades,
actuator or jackshaft.
8) Install connections to [electric, pneumatic] actuators as specified.
9) Attach multiple damper section assemblies together in accordance with manufacturer’s
instructions. Install support mullions as reinforcement between assemblies as required.
7) Breakaway round duct collar with crimp joint bead (specify diameter)
8) Breakaway oval duct collar with crimp joint bead (specify width & height)
These monitors shall incorporate an accurate multi criteria temperature, humidity, CO2 & tVOC
sensor for more comprehensive indoor air quality details with the advanced application specific
controller suitable for integration within VAQ station/VAV Terminal thermostat and having self
optimizing wireless mesh network or wired RS-485 daisy chain network. Baud rate shall be
configured to 76800 bps for faster connectivity.
It shall integrate a metal oxide gas sensor to detect a wide range of VOCs and NDIR CO2
sensor technology for reliability.
Each module shall be factory calibrated with Nitrogen(Zero) calibration for better accuracy and
repeatability (±10) within the measurement range
CO2 : 400 ppm – 10000 ppm (Accuracy: ±50 ppm)
tVOC : 0 - 500 µg/m3
It shall have long term stability and a lifetime of 15 years with operating conditions of 0-50°C, 0-
90% RH
Response and Warm Up time should not exceed more than 30s.