Armstrong Engineering Services Rishabh Paradise (Cloud 9)

General Technical Specifications Gautam Budh Nagar, UP


Fire Module for Basement Parking Ventilation Fans

1.00 Scope: Supply, erection, testing and commissioning & carrying out performance test at site to
these specifications and in accordance with the requirements of drawings and schedule of
quantities.
2.00 General: These specifications are to be read in conjunction with the drawings and schedule of
quantities enclosed.
3.00 Requirements:
3.01 CO Levels shall typically be maintained with in 25 ppm (29 mg/cum), with peak levels not exceeding 115
ppm (137 mg/cum). NOx Levels shall typically be maintained with in 1 ppm.
3.02 All other contaminants of the vehicle exhaust get eliminated with CO2, the levels of which shall typically be
maintained with in 1300 ppm.
4.00 Fire Module:
4.01 Fire Module shall consist of CO Sensor, CO2 Sensor (Optional - As Specified in the BOQ) integrated with a
Advanced Application Specific Controller to affect the energy savings by controlling the ventilation rates &
maintaining the required levels of the contaminants. It shall be complete with Digital Display for indicating
the levels of CO & CO2.
4.02 The controller shall be programmable type & factory programmed to meet the client's requirements and for
the conditions given in the operation logic enclosed. The controller shall be suitable to receive the
necessary numbers & types of Input Signals and provide necessary numbers & types of output signals to
meet the required operating conditions as per the operation logic enclosed.
4.03 It shall be complete with manual override option to provide maximum ventilation during pre-determined
peak loads.
4.04 It shall be complete with smoke override option to provide maximum ventilation up on receiving signal from
smoke detector or central fire alarm panel or sensing the fire conditions through the inbuilt CO sensor
signal. As such, the fire module shall provide a fail-safe smoke exhaust in case of fire & a manual override
to override the sensors to provide maximum ventilation.
4.05 CO Sensor 0 to 150 ppm 4.06 CO Sensor +/- 10 ppm
Range: Accuracy:
4.07 CO2 Sensor 0 to 2000 ppm 4.08 CO2 Sensor +/- 30 ppm
Range: Accuracy:
4.09 All components shall be housed in an attractive casing of approximate size 300 x 300 x 100 mm with all
terminals for wiring neatly arranged for easy field wiring.
4.10 Input Power 230 V +/- 10%, 50 Hz +/- 5%, 4.11 Transformer: The unit shall be complete with
Supply: Single Phase AC transformer, if required.
4.12 The fire module shall be complete with RS communication port for communication with each other to
provide proper coverage in a ventilation zone & for integration with BMS system. All manual operations
possible through the fire control module shall be possible through the BMS operating station. All displays /
information available on the fire control module shall also be displayed on the BMS operating system.

5.00 Coverage & Location of Fire Modules:


5.01 The Number / Quantity of Fire Modules required shall be calculated as below:
5.02 Number of Fire Modules = A x SQRT(L/W) / 1000
a A = Ventilation Zone Area in Sqm, L = Length of Ventilation Zone in m, W = Width of Ventilation Zone in m

5.03 Maximum Distance of any corner of the ventilation zone to the nearest fire module shall not exceed 25 m.

5.04 First 12 m from the fresh air intake shall be considered as naturally ventilated space and hence the
distance of the nearest fire module from the fresh air intake shall not be less than 12 m.
5.05 The fire modules shall be located at 1.80 m height on the column / wall face.
6.00 Master Control:
6.01 For Ventilation Zones requiring more than one fire modules, it shall be possible to make fire modules
closest to the starter panels as master modules to minimize the cabling.

GTS 1 of 8
Armstrong Engineering Services Calculations for No. of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications Gautam Budh Nagar, UP

Zone # Area Sqm Length m Width m Calculated No. of Selected No. of


Modules Modules
LB Zone 1 2091 64.60 33.80 2.89 3.00
LB Zone 2 2089 61.30 42.70 2.50 3.00
LB Zone 3 1655 42.80 37.90 1.76 2.00
LB Zone 4 1674 47.10 39.20 1.83 2.00
LB Zone 5 1577 50.90 36.70 1.86 2.00
LB Zone 6 1577 44.80 37.20 1.73 2.00
LB Zone 7 1577 63.80 40.40 1.98 2.00
UB Zone 1 2091 64.60 33.80 2.89 3.00
UB Zone 2 2089 61.30 42.70 2.50 3.00
UB Zone 3 1655 42.80 37.90 1.76 2.00
UB Zone 4 1674 47.10 39.20 1.83 2.00
UB Zone 5 1577 50.90 36.70 1.86 2.00
UB Zone 6 1577 44.80 37.20 1.73 2.00
UB Zone 7 1577 63.80 40.40 1.98 2.00
Total 32.00

GTS 2 of 8
Armstrong Engineering Services Zone Wise Details of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications for Basement Ventilation Gautam Budh Nagar, UP

S. No. Description
1.00 Ventilation Zone: Lower Basement Zone # 01
Qty. of Normal Duty Fixed Speed F/A Fans 2 Qty. of Fresh Air Fan Starter Panels 1 CO2 Sensor Reqd. No
Qty. of Fire Duty Fixed Speed F/A Fans 0 Qty. of Exhaust Air Fan Starter Panels 1 Fire Signal from Fire Alarm Panel No
Qty. of Normal Duty Fixed Speed E/A Fans 2 Qty. of Jet Fan Starter Panels 1
Qty. of Fire Duty Fixed Speed E/A Fans 2 FA Fans to Shut Off in case of Fire Yes
Selected No. of Fire Modules 3.00 Integration with BMS No

Description Qty. Analog Analog Digital Digital Operation Logic Cabling Cabling To Cable Size
Input Output Input Output From
1.01 Number of Fire Modules 3 Modules to communicate Module 1 Module 2 1 x 2 C x 26 AWG Cu Shielded Twisted Type
with each other Wire in MS Conduit
Module 2 Module 3 1 x 2 C x 26 AWG Cu Shielded Twisted Type
Wire in MS Conduit

1.02 Power Supply to Fire Modules 3 Client to provide 1x 15A (230V AC) Switch with Socket at
High Level near each Module
1.03 Integration with BMS Not Applicable Not App. Not App.

1.04 CO Sensor 3 3 CO Levels to be sensed by Not App. Not App. No External Wiring. Wiring from CO Sensor to Controller
Modules inbuilt in Module.
1.05 CO2 Sensor Not Applicable Not App. Not App. Not Applicable

1.06 Operational Inputs:


a Fire Signal from External Source / Not Applicable Not Applicable
Fire Alarm Panel

1.07 Operational Outputs:


a On / Off Signal to Normal Duty 1 Fans to operate based on Nearest FA Fans 1 x 2 C x 1.0 Cu Twisted Type Wire in MS
Fresh Air Fans Signal from Module Module Starter Sqmm Conduit
Panels
b On / Off Signal to Fire Duty Fresh 0 Not Applicable Not App. Not App.
Air Fans

c On / Off Signal to Normal Duty 1 Fans to operate based on Nearest EA Fans 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
Exhaust Air Fans Signal from Module Module Starter Sqmm Conduit
Panels
d On / Off Signal to Fire Duty 1 Fans to operate based on Nearest EA Fans
Exhaust Air Fans Signal from Module Module Starter
Panels
e Low / High Speed Operation Signal 2 Fans to operate based on Nearest Jet Fan 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
to Jet Fans Signal from Module Module Starter Sqmm Conduit
Panels

Page 3 of 8
Armstrong Engineering Services Zone Wise Details of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications for Basement Ventilation Gautam Budh Nagar, UP

S. No. Description
2.00 Ventilation Zone: Lower Basement Zone # 02
2.01 Details shall be same as : Ventilation Zone: Lower Basement Zone # 01

S. No. Description
3.00 Ventilation Zone: Lower Basement Zone # 03
Qty. of Normal Duty Fixed Speed F/A Fans 2 Qty. of Fresh Air Fan Starter Panels 1 CO2 Sensor Reqd. No
Qty. of Fire Duty Fixed Speed F/A Fans 0 Qty. of Exhaust Air Fan Starter Panels 1 Fire Signal from Fire Alarm Panel No
Qty. of Normal Duty Fixed Speed E/A Fans 2 Qty. of Jet Fan Starter Panels 1
Qty. of Fire Duty Fixed Speed E/A Fans 2 FA Fans to Shut Off in case of Fire Yes
Selected No. of Fire Modules 2.00 Integration with BMS No

Description Qty. Analog Analog Digital Digital Operation Logic Cabling Cabling To Cable Size
Input Output Input Output From
3.01 Number of Fire Modules 2 Modules to communicate Module 1 Module 2 1 x 2 C x 26 AWG Cu Shielded Twisted Type
with each other Wire in MS Conduit

3.02 Power Supply to Fire Modules 2 Client to provide 1x 15A (230V AC) Switch with Socket at
High Level near each Module
3.03 Integration with BMS Not Applicable Not App. Not App.

3.04 CO Sensor 2 2 CO Levels to be sensed by Not App. Not App. No External Wiring. Wiring from CO Sensor to Controller
Modules inbuilt in Module.
3.05 CO2 Sensor Not Applicable Not App. Not App. Not Applicable

3.06 Operational Inputs:


a Fire Signal from External Source / Not Applicable Not Applicable
Fire Alarm Panel

3.07 Operational Outputs:


a On / Off Signal to Normal Duty 1 Fans to operate based on Nearest FA Fans 1 x 2 C x 1.0 Cu Twisted Type Wire in MS
Fresh Air Fans Signal from Module Module Starter Sqmm Conduit
Panels
b On / Off Signal to Fire Duty Fresh 0 Not Applicable Not App. Not App.
Air Fans

c On / Off Signal to Normal Duty 1 Fans to operate based on Nearest EA Fans 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
Exhaust Air Fans Signal from Module Module Starter Sqmm Conduit
Panels
d On / Off Signal to Fire Duty 1 Fans to operate based on Nearest EA Fans
Exhaust Air Fans Signal from Module Module Starter
Panels
e Low / High Speed Operation Signal 2 Fans to operate based on Nearest Jet Fan 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
to Jet Fans Signal from Module Module Starter Sqmm Conduit
Panels

Page 4 of 8
Armstrong Engineering Services Zone Wise Details of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications for Basement Ventilation Gautam Budh Nagar, UP

S. No. Description
4.00 Ventilation Zone: Lower Basement Zone # 04
4.01 Details shall be same as : Ventilation Zone: Lower Basement Zone # 03

S. No. Description
5.00 Ventilation Zone: Lower Basement Zone # 05
5.01 Details shall be same as : Ventilation Zone: Lower Basement Zone # 03

S. No. Description
6.00 Ventilation Zone: Lower Basement Zone # 06
6.01 Details shall be same as : Ventilation Zone: Lower Basement Zone # 03

S. No. Description
7.00 Ventilation Zone: Lower Basement Zone # 07
7.01 Details shall be same as : Ventilation Zone: Lower Basement Zone # 03

S. No. Description
8.00 Ventilation Zone: Upper Basement Zone # 01
8.01 Details shall be same as : Ventilation Zone: Lower Basement Zone # 01

Page 5 of 8
Armstrong Engineering Services Zone Wise Details of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications for Basement Ventilation Gautam Budh Nagar, UP

S. No. Description
9.00 Ventilation Zone: Upper Basement Zone # 02
Qty. of Normal Duty Fixed Speed F/A Fans 0 Qty. of Fresh Air Fan Starter Panels 0 CO2 Sensor Reqd. No
Qty. of Fire Duty Fixed Speed F/A Fans 0 Qty. of Exhaust Air Fan Starter Panels 1 Fire Signal from Fire Alarm Panel No
Qty. of Normal Duty Fixed Speed E/A Fans 2 Qty. of Jet Fan Starter Panels 1
Qty. of Fire Duty Fixed Speed E/A Fans 2 FA Fans to Shut Off in case of Fire Yes
Selected No. of Fire Modules 3.00 Integration with BMS No

Description Qty. Analog Analog Digital Digital Operation Logic Cabling Cabling To Cable Size
Input Output Input Output From
9.01 Number of Fire Modules 3 Modules to communicate Module 1 Module 2 1 x 2 C x 26 AWG Cu Shielded Twisted Type
with each other Wire in MS Conduit
Module 2 Module 3 1 x 2 C x 26 AWG Cu Shielded Twisted Type
Wire in MS Conduit

9.02 Power Supply to Fire Modules 3 Client to provide 1x 15A (230V AC) Switch with Socket at
High Level near each Module
9.03 Integration with BMS Not Applicable Not App. Not App.

9.04 CO Sensor 3 3 CO Levels to be sensed by Not App. Not App. No External Wiring. Wiring from CO Sensor to Controller
Modules inbuilt in Module.
9.05 CO2 Sensor Not Applicable Not App. Not App. Not Applicable

9.06 Operational Inputs:


a Fire Signal from External Source / Not Applicable Not Applicable
Fire Alarm Panel

9.07 Operational Outputs:


a On / Off Signal to Normal Duty 0 Not Applicable Not App. Not App.
Fresh Air Fans

b On / Off Signal to Fire Duty Fresh 0 Not Applicable Not App. Not App.
Air Fans

c On / Off Signal to Normal Duty 1 Fans to operate based on Nearest EA Fans 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
Exhaust Air Fans Signal from Module Module Starter Sqmm Conduit
Panels
d On / Off Signal to Fire Duty 1 Fans to operate based on Nearest EA Fans
Exhaust Air Fans Signal from Module Module Starter
Panels
e Low / High Speed Operation Signal 2 Fans to operate based on Nearest Jet Fan 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
to Jet Fans Signal from Module Module Starter Sqmm Conduit
Panels

Page 6 of 8
Armstrong Engineering Services Zone Wise Details of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications for Basement Ventilation Gautam Budh Nagar, UP

S. No. Description
10.00 Ventilation Zone: Upper Basement Zone # 03
Qty. of Normal Duty Fixed Speed F/A Fans 0 Qty. of Fresh Air Fan Starter Panels 0 CO2 Sensor Reqd. No
Qty. of Fire Duty Fixed Speed F/A Fans 0 Qty. of Exhaust Air Fan Starter Panels 1 Fire Signal from Fire Alarm Panel No
Qty. of Normal Duty Fixed Speed E/A Fans 2 Qty. of Jet Fan Starter Panels 1
Qty. of Fire Duty Fixed Speed E/A Fans 2 FA Fans to Shut Off in case of Fire Yes
Selected No. of Fire Modules 2.00 Integration with BMS No

Description Qty. Analog Analog Digital Digital Operation Logic Cabling Cabling To Cable Size
Input Output Input Output From
10.01 Number of Fire Modules 2 Modules to communicate Module 1 Module 2 1 x 2 C x 26 AWG Cu Shielded Twisted Type
with each other Wire in MS Conduit

10.02 Power Supply to Fire Modules 2 Client to provide 1x 15A (230V AC) Switch with Socket at
High Level near each Module
10.03 Integration with BMS Not Applicable Not App. Not App.

10.04 CO Sensor 2 2 CO Levels to be sensed by Not App. Not App. No External Wiring. Wiring from CO Sensor to Controller
Modules inbuilt in Module.
10.05 CO2 Sensor Not Applicable Not App. Not App. Not Applicable

10.06 Operational Inputs:


a Fire Signal from External Source / Not Applicable Not Applicable
Fire Alarm Panel

10.07 Operational Outputs:


a On / Off Signal to Normal Duty 0 Not Applicable Not App. Not App.
Fresh Air Fans

b On / Off Signal to Fire Duty Fresh 0 Not Applicable Not App. Not App.
Air Fans

c On / Off Signal to Normal Duty 1 Fans to operate based on Nearest EA Fans 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
Exhaust Air Fans Signal from Module Module Starter Sqmm Conduit
Panels
d On / Off Signal to Fire Duty 1 Fans to operate based on Nearest EA Fans
Exhaust Air Fans Signal from Module Module Starter
Panels
e Low / High Speed Operation Signal 2 Fans to operate based on Nearest Jet Fan 1 x 4 C x 1.0 Cu Twisted Type Wire in MS
to Jet Fans Signal from Module Module Starter Sqmm Conduit
Panels

Page 7 of 8
Armstrong Engineering Services Zone Wise Details of Fire Modules Rishabh Paradise (Cloud 9)
Particular Technical Specifications for Basement Ventilation Gautam Budh Nagar, UP

S. No. Description
11.00 Ventilation Zone: Upper Basement Zone # 04
11.01 Details shall be same as : Ventilation Zone: Upper Basement Zone # 03

S. No. Description
12.00 Ventilation Zone: Upper Basement Zone # 05
12.01 Details shall be same as : Ventilation Zone: Upper Basement Zone # 03

S. No. Description
13.00 Ventilation Zone: Upper Basement Zone # 06
13.01 Details shall be same as : Ventilation Zone: Upper Basement Zone # 03

S. No. Description
14.00 Ventilation Zone: Upper Basement Zone # 07
14.01 Details shall be same as : Ventilation Zone: Upper Basement Zone # 03

OL Operation Logic: Normal Fire Duty F/A Normal Fire Duty Jet Fans
Duty F/A Fans Duty E/A E/A Fans
Fans Fans
NM Normal Mode Operation Logic:
a CO Level less than 5 PPM and CO2 Level less than 400 PPM (In ALL of the Fire Modules of the Zone) Off Off Off Off Off
b CO Level 6 to 20 PPM and / or CO2 Level 401 to 800 PPM (In ANY ONE of the Fire Modules of the Zone) On Off On Off Low Speed
c CO Level 21 PPM or More and / or CO2 Level 801 PPM or More (In ANY ONE of the Fire Modules of the Zone) On Off On Off High Sp'd
FM Fire Mode Operation Logic:
a CO Level 125 PPM or More and / or Fail Safe Mode and / or Fire Signal from Fire Alram Panel (In ANY ONE of the Fire Modules of the Off Off On On High Sp'd
Zone)

Page 8 of 8