April 1993 Bulletin 34.

4:4194H

4194H Series Differential Pressure Indicating


Controllers
Controller Description Features
 Easy Maintenance—Simple design of the con-
The 4194H Series differential pressure indicating con- troller allows fast, easy maintenance and minimal
trollers (figure 1) show process differential pressure spare parts inventory.
and set point on an easy-to-read process scale. These
high static pressure controllers, part of the versatile  Easy Adjustment—Adjustments of set point and
Wizard family of pneumatic instrumentation, sense zero and span of the process pointer, and switching
two different pressures and compare the difference between direct and reverse action are accomplished
between these pressures with an operator-adjusted quickly and without special tools. Also, the set point
set point. A pneumatic signal is then delivered to a and proportional band can be adjusted with no interac-
control element to change the process differential tion.
pressure toward the set point. The 4194H Series con-
 Highly Visible Display—Two red pointers on a
trollers use a differential pressure unit such as the
4-1/2 inch (114 mm) long white-on-black scale show
Barton Type 199 for differential pressure up to 75 psi
differential pressure and deviation from set point at a
(5.2 bar). The product line includes proportional-only,
glance. Two other gauges monitor supply and output
proportional-plus-reset, and differential gap controllers.
pressures.
 Low Air Consumption—Relay and nozzle de-
sign reduces steady state air consumption to as low
The controllers are also available with anti-reset wind- as 5 scfh (0.13 normal m3/hr).
up, internal auto/manual station, and remote set point
adjustability (see table 1). The 4194H Series control-  Corrosion Resistant—Tough plastic housing
lers are used throughout industry where process moni- withstands corrosive environments. Internal construc-
toring and accurate measurement of differential pres- tions are available to resist a corrosive supply pres-
sure are required. sure media.

PROCESS DIFFERENTIAL SET POINT


PRESSURE INDICATOR ADJUSTMENT

W5825/IL
SUPPLY OUTPUT
PRESSURE GAUGE PRESSURE

  
W5826–1/IL
GAUGE
 
   
 
   
 

Figure 1. 4194H Series Differential Pressure Controllers


D200049X012
Bulletin 34.4:4194H
Specifications
Available Configurations Reset(1): Adjustable from 0.01 to more than 74 min
per repeat (from 100 to less than 0.0135 repeats
See table 1
per min)
Differential Gap(1) Controllers: Adjustable from 1
Sensing Element Range (Input Signal(1)) to 100% of process scale range
See table 2 Set Point: Continuously adjustable from 0 to 100%
of the scale range.
J Internal Set Point Adjustment (standard): Internal
Process Scale adjustment knob
J Linear, J square root, or J others(2) on request J External Set Point Adjustment: External adjust-
ment knob and internal mechanism allow set point
Process Connections adjustment without opening controller case

Standard: 1/4 in. NPT female stainless steel (all


Controller Performance(3)
input ranges)
Repeatability (1): 0.09% of process scale range
Optional: 1/2 in. NPT male stainless steel
Dead Band(1): Less than 0.2% of process scale
range
Output Signal(1)
Proportional or Proportional-Plus-Reset Range: Steady-State Air Consumption(1),(4),(5)
J 3 to 15 psig (0.2 to 1.0 bar) or J 6 to 30 psig (0.4
to 2.0 bar) 3 to 15 psig (0.2 to 1.0 Bar) Output: 5.0 scfh
(0.13 normal m3/hr)
Differential Gap Output: J 0 and 20 psig (0 and 6 to 30 psig (0.4 to 2.0 Bar) Output: 7.0 scfh
1.4 bar) or J 0 and 35 psig (0. 2.4 bar) (0.19 normal m3/hr)
Action: Field-reversible between J direct (increas-
ing sensed pressure increases output pressure) or Delivery Capacity(4)
J reverse (increasing sensed pressure decreases
3 to 15 Psig (0.2 to 1.0 Bar) Output: 240 scfh (6.4
output pressure)
normal m3/hr)
6 to 30 Psig (0.4 to 2.0 Bar) Output: 480 scfh
Supply and Output Connections (12.9 normal m3/hr)
1/4 in. NPT female
Exhaust Capacity(4)
Supply Pressure Requirements 3 to 15 Psig (0.2 to 1.0 Bar) Output: 170 scfh (4.6
See table 3 normal m3/hr)
6 to 30 Psig (0.4 to 2.0 Bar) Output: 260 scfh (7.0
normal m3/hr)
Remote Set Point Pressures
J 3 to 15 psig (0.2 to 1.0 bar) or J 6 to 30 psig (0.4 Operative Ambient Temperature Limits(6)
to 2.0 bar)
–40 to 160_F (–40 to 70_C)
Construction Materials
Mounting
See table 4
Controller is mounted on a pipestand
Controller Adjustments
Approximate Weight
Proportional Band(1): 5 to 500% of process scale
range 57 lb (26 kg)
1. These terms are defined in ISA Standard S51.1:1979.
2. Consult your Fisher sales office or sales representative for additional information.
3. With Barton Type 199 differential pressure unit.
4. Scfh at 60_F, 14.7 psia; (normal m3/hr at 0_ C, 1.01325 bar) absolute.
5. Without auto/manual switch. With auto/manual switch, air consumption is 10.0 scfh (0.28 normal m3/hr).
6. Also for transportation and storage limits.

2
Bulletin 34.4:4194H
Table 1. Available Configurations
CONFIGURATIONS
TYPE
Proportional– Proportional– Proportional–Plus Differential Anti-Reset Remote Set Internal Auto/
NUMBER(1)
Only Plus Reset Reset–Plus–Rate(2) Gap Windup Point Manual Station
4194HA X ––– ––– ––– ––– ––– –––
4194HAE X ––– ––– ––– ––– ––– X
4194HAM X ––– ––– ––– ––– X –––
4194HAME X ––– ––– ––– ––– X X
4194HB ––– X ––– ––– ––– ––– –––
4194HBE ––– X ––– ––– ––– ––– X
4194HBF ––– X ––– ––– X ––– –––
4194HBFE ––– X ––– ––– X ––– X
4194HBM ––– X ––– ––– ––– X –––
4194HBME ––– X ––– ––– ––– X X
4194HBFM ––– X ––– ––– X X –––
4194HBFME ––– X ––– ––– X X X
4194HC ––– ––– X ––– ––– ––– –––
4194HCE ––– ––– X ––– ––– ––– X
4194HCF ––– ––– X ––– X ––– –––
4194HCFE ––– ––– X ––– X ––– X
4194HCM ––– ––– X ––– ––– X –––
4194HCME ––– ––– X ––– ––– X X
4194HCFM ––– ––– X ––– X X –––
4194HCFME ––– ––– X ––– X X X
4194HS ––– ––– ––– X ––– ––– –––
4194HSE ––– ––– ––– X ––– ––– X
4914HSM ––– ––– ––– X ––– X –––
4194HSME ––– ––– ––– X ––– X X
1. Reverse–acting constructions are designated by an R added to the type number.
2. Consult your Fisher sales office or sales representative for information on rate.

Table 2. Process Sensor (Barton Type 199) Ranges Table 3. Supply Pressure Data
and Pressure Ratings Maximum
Normal
AVAILABLE DIFFERENTIAL STATIC PRESSURE Output Pressure
Operating
PRESSURE UNIT OPERATING RANGES OPERATING RANGE Signal to Prevent
Supply
Inch wc mbar Psig Bar Range Internal
Pressure(1)
Damage(2)
0 to 20 0 to 50
0 to 25 0 to 63 3 to 15 or 0 and 20
20 50
0 to 50 0 to 125 (differential gap)
Psig
0 to 75 0 to 188 6 to 30 or 0 and 35
35 50
0 to 100 0 to 250 (differential gap)
– – –((1)) – – –((1))
Psi Bar 0.2 to 1.0 or 0 and 1.4
1.4 3.4
(differential gap)
0 to 15 0 to 1.0 Bar
0 to 50 0 to 3.4 0.4 to 2.0 or 0 and 2.4
2.4 3.4
0 to 75 0 to 5.2 (differential gap)
1. Available in ranges of 0 to 1000 psig (0 to 70 bar), 0 to 2500 psig (0 to 172 bar), 1. If this pressure is exceeded, control stability may be impaired.
and 0 to 6000 psig (0 to 413 bar). Actual static pressure depends on differential 2. If this pressure is exceeded, damage to the controller may result.
pressure unit rating and materials.

Principle of Operation creases the output pressure (delivery) of the control-


ler. Output pressure is fed back to the proportional
bellows. The action of the proportional bellows count-
4194H Series Controllers ers the flapper movement that resulted from the pro-
cess differential pressure change, and backs the flap-
Refer to the proportional-only control diagram in figure per away from the nozzle. Set point adjustment also
2. The input element is connected to the process changes the proximity of the nozzle and flapper; how-
pointer and flapper by a connecting linkage. As the ever, when the set point is changed, the nozzle moves
process differential pressure increases in a direct-act- with respect to the flapper. When the controller is in
ing controller, the flapper moves toward the nozzle, the reverse-acting mode (see flapper detail in figure
restricting flow through the nozzle and increasing 2), an increase in process differential pressure causes
nozzle pressure. When this occurs, relay action in- a decrease in output pressure.

3
Bulletin 34.4:4194H
Table 4. Construction Materials
Product Part Standard Material Optional Material
Case and cover Polyester plastic –––
Exterior tubing Copper  Aluminum,  stainless steel,  steel,  polyethylene
Exterior fittings C36000 (brass)  Aluminum,  stainless steel,  steel,  polyethylene
Interior tubing Copper S30400 (304 stainless steel)
Nozzle S30300 (303 stainless steel) –––
Flapper S31600 (316 stainless steel) –––

4194H Series
Relay springs  S30200 (302 stainless steel),  steel –––
Controllers Relay O-rings Nitrile –––
Relay diaphragms Nitrile –––
Other relay metal parts  Aluminum,  stainless steel –––
Feedback bellows
C51000 (bronze) S32100 (321 stainless steel)
assembly
Supply and output
Brass (wetted parts only) Stainless steel (wetted parts only)
gauges
Remote set point bellows N09902 (Nickel alloy) –––
Mounting plates Zinc-plated steel –––
Barton Ty
Type
e 199
Differential Bellows Stainless steel –––
Pressure Unit Housing Steel Stainless steel

In addition to the Type 4194HA (proportional-only) ver- AUTO position, the output of the relay is channelled
sion, the Type 4194HB controller is available for pro- through the switch to become the output of the control-
portional-plus-reset control. In this controller, output ler.
pressure is fed back to the reset bellows as well as to
the proportional bellows. Remote set point is available Before the auto/manual switch is operated, the output
on all controllers. Anti-reset windup is available on all of the relay must equal the output of the manual load-
controllers with reset. er to avoid bumping the process. Adjusting the set
point varies the pressure on the left-hand side of the
The Type 4194HS controller provides differential gap plastic tube. Adjusting the manual loader knob varies
control. In this version, feedback pressure is piped the pressure on the right-hand side. When the pres-
directly to the reset bellows, reinforcing the change in sures are equal, the metal ball is centered in the tube.
flapper position rather than the counteracting it. This Pressure imbalance will force the ball to one end of
construction causes the controller output to switch the tube where it forms a seal, blocking air flow
from full supply pressure to zero pressure or vice through the tube.
versa.

The schematic diagram (figure 2) emphasizes detail of


construction variations between control modes. Refer Construction Features
to table 1 for a complete description of type number
suffixes. Simplified Relay Maintenance
A clean-out wire provides a fast, easy means of clean-
Auto/Manual Option ing the relay primary orifice during service.
Controllers with the auto/manual option have piping on
the output side of the relay as shown in figure 3. Sup-
Pressure Protection for the Case
ply pressure to the relay is also applied to the manual
loader. The manual loader, functioning as a regulator, A rubber plug in the plastic case pops out to prevent
applies pressure to one side of the plastic tube and to excessive pressure buildup inside the case, thus pre-
the auto/manual switch. Output pressure from the venting structural damage.
relay registers on the other side of the plastic tube as
well as in the auto/manual switch.
Easy Direct/Reverse Switching
When the auto/manual switch is in the MAN position, Controller action can be switched from direct to re-
the output of the manual loader, which is adjustable by verse or vice versa by simply loosening the screws on
the manual loader knob, is channelled through the the proportional band cover and moving the cover out
auto/manual switch and becomes the output of the to rotate the proportional band knob to the desired ac-
controller. When the auto/manual switch is in the tion (see figure 5).

4
Bulletin 34.4:4194H

C0742/IL

Figure 2. Operational Schematic of 4194H Series Differential Pressure Controllers

Easy Mode Conversion Remote Set Point


Conversion from proportional to proportional-plus-reset The capability of adjusting the set point from a remote
control requires the addition of a reset valve and two location is available as an option on the 4194H Series
pieces of tubing. Conversion from proportional to dif- controllers.
ferential gap control requires the addition of one piece
of tubing.
Auto/Manual Capability
An internal auto/manual station is available for smooth
Anti-Reset Windup bumpless transfer from automatic to manual and
manual to automatic control of the controller output.
Anti-reset windup is available with proportional-plus-re- The two-position switch, showing either automatic or
set controllers. Relief valve may be installed to limit manual mode, is clearly visible with the controller cov-
reset windup in either direction. er closed.

5
Bulletin 34.4:4194H

48A5230-A
A2927-1/IL

Figure 3. Schematic of Auto/Manual Option

47A0975-A
A3238-1/IL

Figure 4. Schematic of External Feedback Option

6
Bulletin 34.4:4194H

W3679/IL




 

CONNECTING LINK

2 ZERO ADJUSTMENT
PROPORTIONAL W3439/IL 1
BAND
ADJUSTMENT
2 SPAN ADJUSTMENT
W5826/IL

NOTES:
1 WHITE PORTION OF ADJUSTMENT ENABLES DIRECT CONTROLLER ACTION; BLACK PORTION ENABLES REVERSE
CONTROLLER ACTION
2 FOR THE PROCESS POINTER

Figure 5. Controller Construction Details

Manual Set Point Adjustment (External and option is available only with the two-mode (4194HB
Internal) Series) controllers.
This option permits adjusting the controller set point by
turning a knob. With the external adjustment, the cov-
er need not be opened.

Installation
A 4194H Series controller mounts on a pipestand and
External Feedback must be installed with the vent opening facing down.
The coupling is secured to the pipestand by set
In controller override applications, this option mini- screws. Figure 6 shows controller dimensions includ-
mizes reset windup in the secondary controller. This ing those necessary for installation.

7
Bulletin 34.4:4194H

18A5903-D
A2926–1/IL

Figure 6. Dimensions

Ordering Information Construction


When ordering, specify: Refer to the specifications on page 2 and the
Construction Features section. Carefully review each
Application specification and feature, indicating your choice when-
ever a selection is to be made. Refer to table 1 for
1. Description of the service, such as throttling or on- type numbers; and R to any type number if reverse
off action is desired.
2. Pressure range, composition, and temperature of
process fluid
3. Ambient temperature

Wizard, Fisher, Fisher-Rosemount, and Managing The Process Better are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
All other marks are the property of their respective owners.
Fisher Controls International, Inc. 1991, 1993; All Rights Reserved



  



 
  



 










 






  
   





  
 
  




       


   
        
  


For information, contact Fisher Controls:


Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461

8
Printed in U.S.A.

You might also like