Type 4100Z WizardR I Gauge Pressure Controller


The Type 4100Z Wizardr I pneumatic controller com-
bines a simple principle of operation and few moving
parts with a rugged construction to make an ideal
pressure controller for demanding installations.
Features
D Corrosion Resistant Latch and Hinges—Nylon
shoulder bearings and stainless steel hinge pins elimi-
nate metal-to-metal contact and prevent corrosion of
moving parts

D Easy to Maintain—Deep-shelled cover allows


easy access to all parts for adjustment or routine main-
tenance inspection

D Easy to Adjust—Controlled pressure setting is a


single knob adjustment. The proportional band is ad-
justed by moving the fulcrum pin along a graduated W5595 / IL

scale.
Figure 1. Type 4100Z Controller
D Easy to Reverse—Just move the orifice block
and fulcrum pin to the opposite side of the flapper and
rotate each 180 degrees

COVER

NYLON BEARINGS
CASE

DETAIL A
ENLARGED VIEW OF
A1133 / IL HINGE CONSTRUCTION

W7937 / IL

Figure 2. Type 4100Z Controller with the Cover Open


D200045X012
Bulletin 34.3:4100Z
Specifications
Input Signal(1) Maximum Static Pressure: Same as maximum
Type: Positive pressures from process gas or liquid Bourdon tube rating as shown in table 1
Input Span(1): Maximums range from 3.4 to 517 Operative Ambient Temperature Limits(1)(3)
bar (50 to 7500 psig). See table 1.
–40 to 71_C (–40 to 160_F)
Lower Range Limit(1): 0 psig
Upper Range Limit(1): Maximums range from 3.4 Construction Materials
to 517 bar (50 to 7500 psig). See table 1. Controller Case: Aluminum
Controller Cover: Aluminum
Controller Output Signal(1) Cover Gasket: Foam elastomer
Gauges: Steel case with brass wetted parts
J 0.2 to 1.0 bar (3 to 15 psig) or J 0.4 to 2.0 bar (6 Bourdon Tube(4): J 316 SST or J K-Monel
to 30 psig) Controlled Pressure Block(4): Stainless steel
Action: Field reversible between J direct (increas- Controlled Pressure Block Gasket: Neoprene
ing sensed pressure increases output pressure) or Supply & Output Tubing: Stainless steel
J reverse (increasing sensed pressure decreases Controlled Pressure Tubing(4): Stainless steel
output pressure). The suffix letter R is added to the Nozzle: Stainless steel
type number of a construction specified for reverse Orifice Block: Aluminum
action.
Connections
Control Modes(1) Input Signal Connection
Size: J 1/4 inch NPT female or J optional 1/2 inch
Proportional-Only NPT female for nipple mounting
Location: On back side of case
Supply Pressure Requirements Supply Pressure and Output Signal Connec-
tions
Type: Clean, non-corrosive gas(2) or air Size: 1/4 inch NPT female
Minimum Pressure Location: On back side of case
Proportional: J 1.4 bar (20 psig) for 0.2 to 1.0 bar
(3 to 15 psig) output signal or J 2.4 bar (35 psig) for Mounting
0.4 to 2.0 bar (6 to 30 psig) output signal J Yoke, J Panel, J Surface, J Pipestand, or
J Nipple
Steady-State Air Consumption Weight
See table 2 Approximately 3.1 kg (6.75 lbs)
Options
Supply and Output Pressure Indicators Supply Regulator: Type 67CFR regulator
J 0 to 30 psig/0 to 0.2 MPa/0 to 2.0 bar triple scale Auxiliary Regulator: Type 1301F regulator to re-
gauges for 0.2 to 1.0 bar (3 to 15 psig) output signal duce high pressures to Type 67CFR range (system
or J 0 to 60 psig/0 to 0.4 MPa/0 to 4.0 bar triple must include overpressure protection)
scale gauges for 0.4 to 2.0 bar (6 to 30 psig) output Bourdon Tube Protectors: To prevent corrosive or
signal clogging fluids from entering bourdon tubes; welded
diaphragm seal and flexible tubing factory-welded to
control connection of controller; rated for input sig-
Inlet Pressure Capability nal to 172 bar (2500 psig)
Maximum Working Pressure: Same as maximum Dual Scale Gauges: J 0 to 30 psig/0 to 2 kg/cm2
Bourdon tube rating as shown in table 1 or J 0 to 60 psig/0 to 4 kg/cm2
1. Term defined in ISA Standard S51.1.
2. If supply gas is flammable or noxious, the controller must be located in a well-ventilated, non-hazardous area.
3. Also for transportation and storage limits.
4. Process wetted part

2
Bulletin 34.3:4100Z
Table 1. Bourdon Tube Ranges
Bar Psig
0 to 3.4 0 to 50
0 to 6.9 0 to 100
0 to 17.2 0 to 250
0 to
t 34.5
34 5 0 to
t 500
68 9
0 to 68.9 0 to 1000
0 to 103 0 to 1500
0 to 172 0 to 2500
0 to 345 0 to 5000
0 to 517 0 to 7500

Table 2. Steady-State Air Consumption (1)


SUPPLY WITH SMALL WITH LARGE
PRESSURE ORIFICE(2) ORIFICE(3)
Bar Psig 3
m /h Scfh 3
m /h Scfh
1.4 20 0.40 15 0.94 35
2.4 35 0.54 20 1.3 50
1. m3/h—cubic meters per hour (0_C and 1.01325 bar, absolute); Scfh—standard
cubic feet per hour (60_F and 14.7 psia)
2. Use orifice size 72–60 when controller is used with actua tors up to size 50.
3. Use orifice size 60–50 when controller is used with actua tors size 50 and larger.

Construction Features
Refer to figure 3.

This proportional controller, when used with suitable


control valves, maintains a controlled pressure within a
set range. This control range is called the proportional
band and may be defined as the change in controlled
pressure required to cause a full change in controller 32A1473–A
output pressure. For example, a controller with a Bour- A1136–1/IL

don tube rated at 6.9 bar (100 psig) is yoke-mounted


Figure 3. Type 4100Z Operation Schematic
on a direct-acting control valve which is maintaining
downstream pressure at 3.4 bar (50 psig). A propor- clean, dry air or non-corrosive gas. If the supply gas is
tional band adjustment of 2 percent causes the valve flammable or noxious, the controller must be located in
plug to close at 3.5 bar (51 psig) and completely open a well-ventilated non-hazardous area.
at 3.3 bar (49 psig). With proportional band set at 50
percent, the valve plug reaches the closed position at
5.2 bar (75 psig) controlled pressure and the wide Ordering Information
open position at 1.7 bar (25 psig).
When ordering, please specify the following:

Overpressure Protection 1. Complete controller type number


To avoid personal injury and equipment damage, do 2. Bourdon tube material
not exceed the pressure limitations stated for each
respective unit in the system. Pressure ratings are 3. Process pressure range
stamped on the instruction plate and Bourdon tube.
The regulator pressure ratings are stamped on the 4. Process set point
regulator spring case. If supply or inlet pressures can
exceed any of the pressure limitations, overpressure 5. Desired output signal and action
protection, such as a relief valve, is necessary.
6. Orifice size (if actuator requirements are known)
Installation
7. Type of mounting (yoke, pipestand, panel, surface,
Controller dimensions are shown in figure 4. The con- or nipple)
troller can be remote-mounted or ordered as part of a
control valve assembly. The supply medium must be 8. Optional equipment desired

3
Bulletin 34.3:4100Z

57.2
(2.25)
28.4
(1.12)

219
(8.62)

203
(8.00) 50.8
(2.00)
50.8
(2.00)

95 150
(3.75) (5.91)

195.1
(7.68)

160.3
(6.31)

31A6840-B mm
B0601-3 / IL (INCH)

Figure 4. Dimensions

Wizard, Fisher and Fisher-Rosemount are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
All other marks are the property of their respective owners.
EFisher Controls International, Inc. 1990, 2000; All Rights Reserved

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express