TECHNICAL PARTICULAR AND GUARANTEE

150 KV OUTDOOR CURRENT TRANSFORMER

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

C TRAFO BAY
1 Manufacturer - ALSTOM GRID
2 Type of design - Outdoor, type OSKF 170
3 Type of current transformer - Oil filled Oil filled
4 Standards - IEC 60044, 60815, etc IEC 60044, 60815, etc
5 Type of bushing Porcelain or Composite Porcelain
(silicon rubber)
6 Nominal voltage kV 150 150
7 Highest system voltage kV 170 170
8 Frequency Hz 50 50
9 Phase to earh insulation level
- Impulse withstand voltage (1.2 μs crest) kV 750 750
- Switching surge withstand test kV
10 Power frequency withstand voltage kVrms 325 325
11 Rated symmetrical short circuit current kA 31.5 31.5
12 Number of core - 4
13 Secondary resistance (Rct) for protection purpose at 75OC :
Core no. 1 Ohm < 15
Core no. 2 Ohm -
Core no. 3 Ohm < 15
Core no. 4 Ohm < 15
14 Ratio (for bay trafo) :
Core no. 1 A/A 150-300/5 150-300/5
Core no. 2 A/A 150-300/5 150-300/5
Core no. 3 A/A 2000/5 2000/5
Core no. 4 A/A 2000/5 2000/5
15 Accuracy class :
Core no. 1 - X X
Core no. 2 - 5P20 and 0.5 5P20 and 0.5
Core no. 3 - X X
Core no. 4 - X X
16 Rated burden (indicate on what ratio it is applied) :
Core no. 1 (Vkp) V required > 200
Core no. 2 (VA) VA 40 40
Core no. 3 (Vkp) V required > 250
Core no. 4 (Vkp) V required > 250
ALF>20 for Protection core and ISF<5 for
17 Accuracy limit factor at nominal burden -
metering core.
18 Instrument security factor - FS 20 FS 20
19 Creepage distance to earth according to IEC 60815 mm/kV 25 25
20 Mechanical characteristics
according to Amendment 2 / IEC 60185 : - Load class II Load class II
21 Current transformer housing material - Aluminium Aluminium
22 Consideration of earthquake factor - 0,3 g 0.3 g
23 Insulation medium - Oil Oil
24 Oil level indicator - Direct type Bellow level indicator / Direct
25 Oil compensation by corrosion-proof metallic bellow - Yes Yes
26 Weight of current transformer kg Approx. 750
27 CT shall be designed for transportation either in - Yes Yes
vertical or horizontal position without any damages
to its electrical performance.
28 Type and Routine Test Certificates - Required Yes
acc. to IEC 60185 and Amendment 2/1995-08
29 Instruction Manual shall be submitted - Yes Yes
30 Catalog, detail drawing or other references - Required Yes