Air Cooled Unit Capacity

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 14

SAI COND

SALES & ENGINEERING SDN. BHD.

MODEL: MUAHM 90 150 225 300 375 450


COOLING CAPACITY,KW 10 16.5 24.8 33.4 41.2 49.4
BTU/H 34100 56400 84600 113900 140500 168700
NOMINAL AIRFLOW,CMH 1620 2700 4080 5400 6780 8100
ESP,MM H2O 19 30 32 30 33 34
WEIGHT, Kg 80 95 118 136 210 215

PART LIST
MOTOR TECO TEFC 4P FOOT-MOUNTED 415 VOLT 3PH /50HZ
KW (HP) 0.4 (1/2) 0.75 ( 1 ) 1,5 ( 2 ) 1.5 ( 2 ) 2.2 ( 3 ) 2.2 ( 3 )
MAXIMUM AMPERE 1.3 1.5 3.5 3.5 5.20 5.20
FAN BLOWER NICOTRA FORWARD CURVE CENTRIFUGAL
FAN MODEL AT-9-7S AT-9-7S AT-10-10S AT-10-10S AT-10-10G2L AT-10-10G2L
MOTOR PULLEY 1-GROOVE VERIABLE PITCH V-BELT PULLEY
TYPE UD 100-1 UD- 138-1 UD 138-1 UD-138-1 UD-138-1 UD-138-1
BUSH 1215- 14MM 1215- 19MM 1215- 24MM 1215- 24MM 1215- 28MM 1215- 28MM
PITCH DIAMETER MAX, 95 127 127 127 127 127
PICH FACTORY SET 88 110 106 112 120 120
MOTOR SPEED RPM 1390 1430 1430 1430 1430 1430
FAN PULLEY TYPE 1- SPA 1- SPA 1- SPA 1- SPA 1- SPB 1- SPB
PULLEY SIZE SPA- 125 SPA- 125 SPA- 132 SPA- 132 SPB- 150 SPB- 150
BUSH SIZE 1610- 20MM 1610- 20MM 1610- 20MM 1610- 20MM 1610- 20MM 1610- 20MM
FAN SPEED - RPM 984 1259 1144 1212 1144 1144
BANDO SIZE ( BANDO ) SPA-800 SPA - 850 SPA - 900 SPA - 900 SPB - B36 SPB - B36
CETER DISTANCE 230 225 255 250 255 255
COIL SIZE FH X FL 356 X 704 407 X 800 508 X 980 508 X 1370 456 X 1720 508 X 1720
INSULATION THICKNESS CLOSE CELL PE FOAM 13 & 5MM
SURFACE TREATMENT TYPE POWDER COATING FF160-858-CS26
INPUT / OUTPUT
NOT USER
ANALOG: INPUTS: IO DIGITAL. INPUTS. -- 12 - 14 I7
AMB. HUMIDITY --- 76 % FIRE SMOKE ---- C --
PT 1 -- 12.3 BAR --- 34.5 C OVER - L - COMP. FAN - 1 --- C
PT 2 -- BAR OVER - L - COMP. FAN - 2 --- C

ANALOG INPUTS: I1 ANALOG. OUTPUTS. -- IA


ROOM TEMP. ---- 25.5 C HUMIDIFIER --- V
SUPPLY AIR ----- ---- C MAIN FAN --- 10V
EXTERN. TEMP. ---- --- C RECOVERY --- V

ANALOG INPUTS: I2 DIGITAL. OUTPUTS. - 1 - 3 -- IB


RECOVERY ---- C MAIN FAN ---- OFF - OR - ON
TEMP. COMP. 1 ----- C COMP. NO - 1 - OFF - OR - ON
TEMP. COMP. 2 ----- C COMP. NO - 2 - OFF - OR - ON

DIG. INPUTS. 1 - 3 I3 DIGITAL. OUTPUTS. 4 - 6 -- IC


COMP. 1 ALARM ---- C HEATER - 1 -- ---- ----
COMP. 2 ALARM ---- C HEATER - 2 -- ---- ----
OVER 1 HEAT 1 ---- --- HUMIDIT. -- OFF OR ON

DIG. INPUTS. 4-6 ----- I4 DIGITAL. OUTPUTS. 7 - 8 -- ID


OVER HEAT 2 ------ -- LIGTH ALARM --- OFF
AIR FILTER ---- C SERIOUS ALARM --- OFF
OVER 1 FAN ----- C

NOT USER
DIG. INPUTS. 7-8 I5 DIGITAL. OUTPUTS. 9 - 11 --- Ic
AIR FLOW ---- C FAN - 1 ---- OFF
REMOTE ON - OFF ---- FAN - 2 ---- ---
HUMIDIFIER --- OFF

ANALOG OUTPUTS. I9 NOT USER


COND. FAN 1 ----- 00.0V DIGITAL. OUTPUTS. 9 - 11 --- If
COND. FAN 2 ----- V NOT USED. -- DO12 -----
NOT USED. -- DO13 -----
NOT USED. -- DO14 -----
NOT USER
DIGITAL. INPUTS. --- 9 - 11 I6
LOW PRESS. --- C1 ---- C
LOW PRESS. --- C 2 ---- C
NOT USER --- IDII ----

PROGRAM :
USER --- PASS WORDS --- 1234

LIMITS SETPOINT. ---- P1 AIR TEMP. SUPPLY ---- Pa


TEMPERATURE: LIMIT ENABLE --- NO
MIN. ----- 15.0 C SET POINT --- 15.0 C
MAX ----- 30.0 C DIFFERENT --- 5.0 C

LIMITS SETPOINT. ---- P2 SEL. TYPE ALARM --- Pb


HUMIDITY: S -- SERIOUS --- N -- NOT SER.
MIN. ------ 40 % AOI -- NNNNN --- A06 -- NNNNN
MAX ------ 75 % AII -- NNNNN --- A16 -- NNNNN

TEMPERATURE: ---- P3 SEL. TYPE ALARM --- Pc


COOL - DIFFER ---- 001 C S -- SERIOUS --- N -- NOT SER.
HEAT - " ---- 001.C A21 -- NNNNN --- A26 -- NNNNN
NEUTRAL ZONE ---- 00.3 C A31 -- NNNNN --- A36 -- NNNNN

DEHUMIDITY BAND- 1.5% ---- P4 SEL. TYPE ALARM --- Pd


HUMIDITY BAND --- -- S -- SERIOUS --- N --NOT SER.
A41 -- NNNNN ---- A46 -- NNNNN
A51 -- NNNNN ---- A56 -- NNNNN
SHOW LAGUAGE -- P5
MASK AT START - UP -- NO
OFF UNIT BY KEY -- YES
EN. REMOTE - ON / OFF -- NO SEL. TYPE ALARM --- Pe
A61 -- NNNNN ---- A66 --- NNNNN
NOT USER A71 -- NNNNN ---- A76 --- NN
COMPRESTION -- P7
SET POINT: ---- 025 C
BAND ---- 003 C
OFF SET. ---- 002 C

TEMPERATURE ALARM ---- P8


LOW OFFSET --- 15.0 C
HIGH " --- 28.0 C NEW USER PASS WORDS. ---- PI

1234
HUMIDITY ALARM --- P9
THRESHOLDS
LOW OFFSETS --- 40.0 %
HIGHT " --- 70.0 %

SET POINT --- S1


TEMPERATURE ---- 20.0 C
HUMIDITY ---- 53 %

MANUFACTURER ----- ZO
PASSWORD. 1234

CONFIGURATION
CONFIGURATION HUMIDITY PROBE. -- Y -- Ci
BMS - NETWORK --- N CO TYPE: ---- CURRENT
PRINTER --- N THREHOLD MIN. --- 10 %
SELECT. OF TEMP. --- C " MAX --- 90 %

TYPE OF UNIT : ED. --- C1 PRESSURE 1 PROBE -- Y -- Cj


REFRIGERANT ---- R407C TYPE --- CURENT
TRESHOLD MIN. ---- 0 BAR
COMPRESSORE - 2 ---- C2 " MAX ---- 30 BAR
UNLOADER --- NO
HEATING MODE --- HEATERS PRESSURE 2 PROBE -- N -- Ck
" NO --- 0

CONFIGURATION OF ---- C4 ROOM TEMPERATURE --- Cl


DIGITAL OUTPUT 5 TYPE ---- NTC
AL. DIRTY FILTER SUPPLY AIR PROBE ---

CONFIGURATION OF -- C5
DIGITAL INPUT --- 12 EXT. TEM. PROBE NO. --- Cm
ALARM FIRE WORK RECOVERY PROBE ----

CONFIGURATION OF ---- C9 EXT. TEM. PROBE NO. --- Cn


ANALOG INPUT --- 2 COND. 1 TEMP. ---
PRESSURE CIRC. --- 1 COND. 2 TEMP. ---

CONFIGURATION OF --- Ca UNIT OF CONFIGURATION --- Co


ANALOG INPUT --- 3 U1 : PRESENT. NO. ROTAT
PRESSURE CIRC. --- 2 U2 : NOT PRESENT
U3 : NOT PRESENT
ANALOG OUTPUT -- 1 --- Cb
MAIN OF FAN DAMPER UNITS CONFIGURAT ---- Cp
ANALOG HUMIDIF --- NO U4 : NOT PRESENT
U5 : NOT PRESENT
CONDENSATION -- YES -- Ce U6 : NOT PRESENT
COND. TYPE: ---- SINGLE
UNITS CONFIGURAT ---- Cq
DEHUM. LOGIC : N-O --- Cg U7 : NOT PRESENT
COMPS. FOR DEHUMDI: ---- 1 U8 : NOT PRESENT

MANUFACTURER ----- ZO

PASSWORD. 1234

PARAMETER

COMPRESSOR - WITH --- GO CONDENS. FANS ---- Gj


RECOVERY VALUE HIGH SPEED ---- 10.0V
--------- NO LOW SPEED ---- 0.0V

ROTATION COMP. NO ---- GI HP. COND. PREVENT. ----- Gk


REGULATION TYPE: PROP ENABLE ---- YES
SET POINT ---- 20 BAR
DIFF. ---- 2.0 BAR
MAIN FAN DAMPER ---- G7
MIN. SPEED ---- 05.0V
MAX: SPEED ---- 10.0V MASTER CONTROL ------ Gm
DEHUMID SPEED --- 05.0V ENABLE ------ NO

LOW TEMP. LIMIT ---- G9


( STOP DEHUMIDITY ) COMPRESSORS WITH ------- GO
DIFFERENTIAL ---- 05.0 C RECOVERY VALUE ---- NO
OFFSET. ---- 04.0 C

PRESSURE PROBE ---- Gg


HIGH THRESH. ---- 22.5 BAR
DIFFER. HP ---- 0.5 BAR

CONDENSATION ---- Gh
SET POINT ---- 15.0 BAR
DIFFERENT ---- 1.0 BAR
SPEED TIME ---- 2 SEC.
TIMER

DELAY TIME ------ TO START DELAY SAME ---- T6


START FAN. ---- 05.0 SEC COMPRESSOR ---- 0020 SEC
DELAY TIME OF FAN --- 15.0 SEC START DELAY DIFF.
COMPRESSORS ---- 0010 SEC

INTEGRATION TIME. --- T1


P + 1 ONLY ---- 600 SEC DELAY TIME AMONG ---- T8
OPENING TIME RESISTORS ---- 00 5 SEC
3 P VALVE ---- 180 SEC

DELAY ALARM. LOW ---- T2


PRESSURE ---- 0005. SEC
DELAY ALARM. -- LOW / HIGH
TEMP. / HUMIDITY ---- 15 SEC

DELAY ALARM. ---- T3


RELAY -- 8 ---- 5 SEC

DELAY ALARM. ---- T4


AIR FLOW ---- 5 SEC

MIN. OFF TIME. ---- T5


COMPRESSURE ---- 60 SEC
MIN. TIME POWER ON
COMPRESSOR ---- 0180 SEC
ALARM HISTORY

1. U: O1 ------ AL 03
LOW PRESSURE CERCUIT I

2. U: O1 ------- AL 35
OVERLOAD OR HIGH PRESSURE
PRESSOSTAT COMP. 1

3. U: O1 ------ AL 07
OVERLOAD COMP.
ELET. HEATER 1

4. U: O1 ------ AL 10
FILTER AIR ALARM

5. U: O1 ------- AL 06
FAN OVERLOAD
( SERIOUS ALARM )
UNIT OFF

6. U: O1 ------ AL 05
AIR FLOW ALARM
( SERIOUS ALARM )
UNIT OFF
SAI COND SALES & ENG'G SDN. BHD.

AIRCOOLED PACKAGED - COOLING UNIT

PCO3 SETTING PROGRAM DISPLAY


TIME & DATE --- MO
TEMPERATURE ---- 26.5 C
HUMIDITY ---- 76 %
OFF BY KEY BOARD - U : 01

WORK MODE: --- M1


COOLING ----- HEATING
HUMIDIF. ----- DEHUMID.

WORK MODE: --- M2


SUPPLY AIR LIMIT
DEHUMIDIF. LIMIT

PRESS PROGRAM MANUFACTURER


> COMFIGURATION
> MAINTENANCE > PARAMETERS
> PRINTER > CARER EXU DRIVER
> INPUT / OUTPUT > TIMER
> CLOCK > INTIALIZATION
> SET POINT
> USER
> MANUFACTURER
> BOARD SWITCH INTIALIZATION
> ON - OFF UNIT INSERT PASS WORD ---- VO
TO INSTALL DEFAULT VALUES
ON - OFF UNIT ( ENTER ) 1234

UNIT 01 STATUS M3
UNIT OFF BY KEYBOARD ERASE HISTORY ---- V1
> PRESS ( ENTER ) TO SWITCH ON ALARM ---- NO

ENTER

UNIT 01 STATUS M3
UNIT ON
> PRESS ( ENTER ) TO SWITCH OFF
MAINTENANCE ( ENTER )
CODE: FLSTDMCZOE ---- AO PROBE. SETTING ----- A8
VER: 2.4 --- 08/02/08 HUMIDITY ---- 5 %
LANGUAGE: ENGLISH PRESSURE 1 ---- 1.0 BAR
ENTER TO CHANGE. " 2 ---- ---- ---

A SYSTEM IMFORMAT ---- A1 PROBES SETTING --- A9


BIOS. 04.30 ---- 22/12/08 AMBIENT TEMP. --- 00.0 C
BIOS. 04.30 ---- 03/07/06 EXTERNAL TEMP. ---- 00.0 C
SUPPLY AIR ---- -- -- C

PROGRAM: FLSTDmCZO-2-4
UPDATE: 15/09/2010 MANUAL PROCEDURE --- Ab
DOUT 01 ---- OFF
DOUT 02 ---- OFF
RUNNING HOURS ---- A2 DOUT 03 ---- OFF
MAIN FAN ---- 00.5HR
HUMIDIFIER ---- ------
MANUAL PROCEDURE --- Ac
DOUT 04 ---- ----
RUNNING HOURS ---- A3 DOUT 05 ---- ----
COMP. 1 ---- 00.08 HR DOUT 06 ---- OFF
COMP. 2 ---- 00.08 HR

MANUAL PROCEDURE --- Ad


PRESS ALARM TO JAMP. ---- A4 DOUT 07 ---- OFF
THE ALARM HISTORY. DOUT 08 ---- OFF

PASSWORD: ----- A5 MANUAL PROCEDURE --- Af


MAINTENANCE 1234 A OUT - 01 ---- AUT -- 00.0V
A OUT - 02 ---- AUT -- 00.0V

MODIFY RUNNING HOURS. --- A6


COMPRSSORE 1 ---- 00.03HR MANUAL PROCEDURE --- Ag
COMPRSSORE 2 ----- 00.03HR A OUT - 03 ---- AUT -- 00.0V
A OUT - 04 ---- AUT -- 00.0V

MODIFY. RUNNING HOURS. --- AN


MAIN FAN ----- 00.05 HR NEW MAINTENANCE ----- AM
HUMIDIFIER ----- --- PASSWORD.
HOURS RESET --- NO 1234

TRANSHOLD --- RUNNING ---- A7


HOURS ALARM . ( X 1000 )
MAIN FAN - 99 -- COMP. 1 -- 99
HUMIDIFIER -- COMP. 2 -- 99

LIST OF CONFIGURATION

DIRECT EXPANSION AIR - CONDITIONERS - ED

PCO1 - PCO2 - PCO3 -- SMALL

DIGITAL OUTPUTS ANALOGUE OUTPUTS

DD 1 OUTLET FAN AD 1 OUTLET FAN / RECOVERY VALVE


DD 2 COMPRESSOR NO. 1 AD 2 HEATING VALVE / HUMIDIFICATION
DD 3 COMPRESSOR. NO. 2 AD 3 CONDENSER FAN 1
DD 4 HEATER 1 / OPEN HEATING VALVE AD 4 CONDENSER FAN 2
DD 5 HEATER 2 / CLOSE HEATING VALVE
DD 6 DEHUMIDIFICATION
DD 7 RECOVERY
DD 8 GENERAL ALARMS

DIGITAL INPUTS ANALOGUE OUTPUTS


ID 1. ALARM C1 / LOW PRESS. C1 B 1 AMBIENT HUMIDITY
ID 2 ALARM C2 / LOW PRESS. C1 B 2 HIGH PRESS. C1 / COND. TEMP. C1
ID 3 HEATER 1 OVERLOAD ALARM OUTLET TEMPERATURE
ID 4 HEATER 2 OVERLOAD ALARM B 3 HIGH PRESSURE C2
ID 5 FILTER AIR COND. TEMP. C2
ID 6 FAN THERMAL OVERLOAD ALARM RECOVERY TEMPERATURE
ID 7 AIR FLOW SWITCH ALARM B 4 OUTSIDE TEMPERATURE
ID 8 REMOTE ON/OFF B 5 ROOM TEMPERATURE
B 6 OUTLET "
PROCEDURE FOR SETTING THE ADDRESS OF THE CONTROLLER & TERMINAL. PCO3

SETTING THE ADDRESS OF THE CONTROLLER.


> the PCO3 controller does NOT have dipswitch for setting the plan address.
the address must be set by software,as for the PCO

> the procedure is as follows


1. switch the pco3 off
2. prepare a standard carel terminal with the address set to O ( not necessary if the pco3 built in terminal
is used. ) for the operation, see the following paragraph:
3. connect the terminal to the pco3,
4. disconnect any others device connected in the plan from the pco3 ( terminal J11 )
5. switch the pco3 ON, pressing the UP + ALARM bottons at the same time. This combination of botton is
the same on the built in terminal.
6. after a few seconds, the following screen will be displyed.
PLAN ADDRESS: O To 2
UP: ---- INCREASE
DOWN ---- DECREAS
ENTER: SAVE & EXIT
7. to modify the address simply use the UP & DOWN bottons and the press ENTER to confirm.
8. now set the plan address of the terminal and configure the plan network.

SETTING THE ADRESS OF THE TERMINAL PCO3

the default value of the address is 32


the address of the terminal can only set after having connected the power supply via telephone connector.
to enter configuration mode press the bottons at the same time ( even when the terminal is
already on ) in all the version, for atleast 5 second: the follwing screen will be displayed, with the cursor
flashing in the top left cornner.
DISPLAY ADRRESS:
SETTING:---------- 32
I / O BOARD ADDRESS: 01
>tomodify the address of the terminal ( display address setting ) press the botton once : the cunsor
will move to the address field ( nn )
>use the bottons to select to desired value, and comfirm by pressing the botton.if the value is
different than the value saved previously, the screen shown below will be displayed,and the new value will
be saved to permanent memory.
DISPLAY ADRRESS:
CHANGED
if the field nn is set the value 0, the terminal will communacate with the pco3 controller using the "point-to
point " protocol ( not plan ) and the ' I/O board address: xx" field will not be displayed.

PCO3: ASSIGNING THE LIST OF PRIVATE AND SHARED TERMINALS.


at this stage, to modify the list of terminals associated with each individual pco3 board, proceed as follows,
> enter the configuration mode by pressing bottons,as described in the privious pfaragrafh;
> press the botton until the cursor reaches the field xx ( I/O address )
> use the bottons to select the desired address of pco3 board. The value that can be selected refer to
the pco3 board that are effectively on line. If the plan network is not operating correctly,or alternatively no
pco3 board is connected,the field will not be able to be modified and will only show.
> press the botton again displays the following screen in sequence:

TERMINAL CONFIG.
PRESS ENTER
TO CONTINUE

PCO3 SETTING PROGRAM

DISPLAY ADDRESS

SETTING --------- 32
I / O BOARD ADDRESS: 01

ENTER

TERMINAL CONFIG.
PRESS. ENTER . TO CONTINUE

ENTER

P: 01 ADR. PRIV. / SHARED

TERMINAL: 1. -- 25 -- PR
TERMINAL: 2. -- 32 -- SP
TERMINAL: 3 NONE -- OK ? NO / YES ENTER

TIME: > DATE: > MO.

TEMPERATURE --- 22.5 C


HUMIDITY --- 040.0%
OFF. BY KEY BOARD -- U: 01