COMP. AMP.
LINE. 1 59 88 139 153 145
LINE. 2
LINE. 3
COMP. VOLT.
LINE. 1 480 480 478 478 476
LINE. 2
LINE. 3
TEMP./ PRESS.
B1- INLET. EVAP. 25.5 24.5 22.5 16.2 14.2 12.1
B2- OUTLET. EVAP 24 22 19 11.3 9 6.5
B3- INLET. COND. 26 27 29.2 30.5 31 31.2
B4- OUTLET. COND. 27 30 32.7 35.6 36.3 36.4
B5- DISCH. TEMP 33 40.5 46 57 58.3 59
B7- HIGH PRESS. 14.9 15.5 16.3 17.3 19 19.1
B8- LOW PRESS. 7 5.7 5 4.3 4.2 4.2
FUNCTIONAL TEST
MECHANICAL DEVICES DESIGN ELECTRONIC DEVICES DESIGN TEST
SETTING COMP. 1 COMP. 2 PARAMETER COMP. 1
HIGH PRESSURE SW 22 BAR OK HIGH PRESS.TRANSDUCER 21 BAR OK
LOW “ “ 2.5 BAR OK LOW “ “ 2.8 BAR OK
DISCH. TEMP. SW 120 C DISCH. TEMP 90 C
ANTIFREEZE 5.5 C ANTIFREEZE 3.3 C OK
COND.FLOW SWITCH OFF MOTOR
COOLER FLOW SWITCH “
SAI COND
CHILLER TESTING REPORT
COSTOMER: DAIKIN SERIAL NO.
PROJECT: B 304 - 240 HP MUWMP BY2 MFG. NO:
CHILLER : NO. 2 DATE. 24 OCTBER 2008
FUNCTIONAL TEST
MECHANICAL DEVICES DESIGN ELECTRONIC DEVICES DESIGN COMP. 1
SETTING COMP. 1 COMP. 2 PARAMETER
HIGH PRESSURE SW 22 BAR OK HIGH PRESSURE TRANSDUCER 21 BAR OK
LOW “ “ 2.5 BAR OK LOW “ “ 2.8 BAR OK
DISCH. TEMP. SW 120 C DISCH. TEMP 90 C
ANTIFREEZE 6 ANTIFREEZE 3.3 C OK
COND.FLOW SWITCH OFF MOTOR
COOLER FLOW SWITCH “
SAI COND
CHILLER TESTING REPORT
CLIENT: DAIKIN COMPRESSOR. S/N. 8301002 MODEL/SERIAL NO:
PROJECT: B 299 MUWMP 180 BY2 CONDENSER. S/N. 1076036 MFG. NO: CO69J08 DOO97
CHILLER NO: 1 SINGLE COMP. EVAPORATOR.S/N. 3080223733 DATE: 3:30 PM 9/23/2008