Protection Application Example

380 kV OHL

40

35

30
50
25 40
Alpha Angle

20
30
20
15
10
10

0
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
R1/X1

Figure 30: Curves for selection of Alpha Angle setting


From Table 2 the maximum “Transmission Angle “ for this application is given
as 35ْ , if this is checked in Figure 30 together with the R1/X1 setting value of
0.8 (see above 2.830/3.537 = 0.8), then the required “Alpha Angle” setting is
less than 15ْ (by using the TA = 40 curve). A setting of 15ْ is therefore
applied.

11.2. Zone Z1B

Figure 31: Settings for Zone Z1B


1351 Operating mode Z1B (overreach zone): The zone Z1B will be used for the
teleprotection scheme POTT in this application. For this the zone Z1B must
be applied as forward overreach zone.
1352 R(Z1B), Resistance for ph-ph faults: As was the case for the Zone 1 settings,
this setting must cover all internal arc faults. The minimum setting therefore
equals the R(Z1) setting, 2.830 Ohm. However, additional reach is set for the

7SA522/7SA6 Application Example Page 43 of 82


Version 1.0