REFRIGERATION CYCLE BASICS

This is a basic overview of the refrigeration circuit

CONFUSION

1. The Word “Condenser” Can Mean two Different Things Many in the industry will refer to
the outside unit on a split air conditioner, heat pump or refrigeration unit as a “condenser” even
though it will often contain the condenser, compressor, and other parts. It’s better to call the
outside component the “condensing unit” or simply the “outside unit” to reduce confusion.
2. Cold and Hot are Relative terms Cold and Hot are both an experience, a description, a
comparison or an emotion. Cold is a way to describe the absence of heat in the same way that
dark describes the absence of light. We will often use the words cold and hot to compare two
things “Today is colder than yesterday” or to communicate comfort “It feels hot in here”. These
are useful communication tools, but they are comparisons not measurements.
3. Heat and Absolute Zero Can be Measured We can measure heat in BTUs and light in
lumens, we cannot measure cold or dark. Absolute cold is the absence of all heat. -460°F(-
273.3°C) (cold) is known as absolute zero, -460°F(-273.3°C) is the temperature at which all
molecular movement stops. Any temperature above that has a measurable level of heat. While
this is a known point at which all molecular movement stops, it has not (and likely cannot) be
achieved.
4. Boiling Isn’t Always Hot When we say it’s “boiling outside” we mean it’s hot outside. This
is because when we think of boiling we immediately think of water boiling in a pot at 212°F
(100°C) at atmospheric pressure, which is 14.7 PSI (Pounds Per Square Inch)(1.01 bar) at sea
level. Boiling is actually just a change of state from liquid to vapor, and the temperature that
occurs varies greatly based on the substance being boiled and the pressure around the
substance. In an air conditioner or a refrigeration system, refrigerant is designed to boil at a
low temperature that corresponds to the design of the system. On an average air conditioning
system running under normal conditions with a 75°(23.88°C) indoor temperature, the
evaporator coil will contain refrigerant boiling at around 40°F(4.44°C). In air conditioning
and refrigeration when we refer to “boiling”, “flashing” or “evaporating of refrigerant” we are
talking about the process of absorbing heat, otherwise known as cooling.
5. Cooling and Heating Cannot be “Created” We are not in the business of making heat or
creating cool; it cannot be done. We simply move heat from one place to another or change it
from one form to another. When we “cool” a room with an air conditioner, we are simply
absorbing heat from the air into an evaporator and then moving that heat outside to the
condenser where it is “rejected” or moved to the outdoors.
6. Heat and Temperature Aren’t the Same Imagine a shot glass of water boiling away at
212°F(100°C). Now imagine an entire lake sitting at 50°F(10°C). Which has a higher (hotter)
temperature? That answer is obvious-I just told you the shot glass had 212°F(100°C water in
it so it is CLEARLY hotter. But, which contains more heat? The answer is the lake. You see,
heat is simply energy and energy at its basic form is movement. When we measure heat we are
measuring molecular movement; the movement of molecules–atoms stuck together to make
water or oxygen or nitrogen. When molecules move FASTER they have a HIGHER
temperature and when they move SLOWER they have a LOWER temperature. Temperature
is the average speed (velocity) of molecules in a substance, while heat is the total amount of
molecular movement in a substance. The lake has more heat because the lake has more water
(molecules).
7. Compressing Something Makes it Get Hotter (Rise in Temperature) When you take
something and put pressure on it, it will begin to get hotter. As you pack those molecules that
make up whatever you are compressing, they get closer together and they start moving faster.
If you drop the pressure the molecules will have more space and will move slower causing the
temperature to go down.
8. Changing the State of Matter Moves Heat Without Changing Temperature When you
boil pure water at atmospheric pressure it will always boil at 212°F(100°C). You can add more
heat by turning up the burner, but as long as it is changing state (boiling), it will stay
at 212°F(100°C). The energy is changing the water from liquid (water) to vapor (steam) and
the temperature remains the same. This pressure and temperature at which a substance changes
state instead of changing temperature is called its “boiling point”, “condensing temperature”
or more generally “saturation” point.
9. Superheat, Subcool, Boiling, and Saturation Aren’t Complicated If water is boiling at
sea level it will be 212°F(100°C). If water is 211°F(99.44°C) at sea level we know it is fully
liquid and it is 1°F(-17.22°C) subcooled. If water is 213°F(100.55°C) at sea level we know it
is vapor and superheated. If something is fully liquid it will be subcooled, if it is fully vapor it
will superheated, and if it is in the process of change (boiling or condensing) it is at saturation.

COMPONENTS

Compressor > Discharge line > Condenser > Liquid Line > Metering Device > Expansion
Line > Evaporator > Suction line and then back to the Compressor

These four refrigerant components and four lines listed above make up the basic circuit that
every compression refrigeration system follows. Many more parts and controls may be added,
but these basics are the cornerstone on which everything else you will learn is based. Once you
have these memorized we can move on to describing each.
Compressor

The compressor is the heart of the refrigerant circuit. It is the only mechanical component in a
basic refrigeration system. The compressor is like the heart that pumps the blood in the body or
like the sun that provides the earth its energy. Without the compressor to move the refrigerant
through compression, no work would be done and no heat would be moved.

The compressor creates a pressure differential, resulting in high pressure on the high side
(discharge line, condenser & liquid line) and low pressure on the low side (suction line,
evaporator and expansion line).

There are many different types of compressors, but you will most likely see Scroll and
Reciprocating type compressors most often. A reciprocating type compressor uses pistons,
valves, and a crankshaft. Reciprocating compressors operate much like car engines; pulling in
suction vapor on the down-stroke and compressing that vapor on the up-stroke. A scroll
compressor does not have any up-down motion like a reciprocating compressor. A scroll
compressor uses an oscillating motion to compress the low-pressure vapor into high-pressure
vapor.

The compressor pressurizes low-pressure vapor into high-pressure vapor, but it also causes the
temperature of the gas to increase. As stated in the gas laws, an increase in pressure causes an
increase in temperature and a decrease in volume. In the case of refrigerant cooled compressors,
heat is also added to the refrigerant off of the kinetic (bearings, valves, pistons) and electrical
(motor windings) mechanisms of the compressor. Compressors require lubrication; this is
accomplished through oil that is in the compressor crankcase, as well as oil that is carried with
the refrigerant. Liquid entering the compressor through the suction line is a very serious
problem. It can cause liquid slugging, which is liquid refrigerant entering the compression
portion of the compressor. Liquid slugging will most likely cause damage to the compressor
instantly. Another problem is bearing washout or “flooding”. This occurs when liquid
refrigerant dilutes the oil in the compressor crankcase and creates foaming, and it will greatly
reduce the life of the compressor because it will not receive proper lubrication and too much oil
will be carried out of the compressor and into other parts of the system. The compressor also
(generally) relies on the cool suction gas from the evaporator to cool the compressor properly,
so it’s a delicate balance to keep a compressor from being flooded and also keep it cool.
Condenser

Condensers come in all different types, shapes, and sizes. Regardless, they all perform the same
function: rejecting heat from the refrigerant. The refrigerant entering the condenser was just
compressed by the compressor, and this process increased the temperature by packing the
molecules together which added heat to the vapor refrigerant due to the motor and mechanical
workings of the compressor. This process in the compressor also greatly increased the pressure
from a low-pressure in the suction line entering the compressor, to a high-pressure vapor leaving
the compressor.

The condenser has three jobs:

1. Desuperheat the refrigerant (Drop the temperature down to the condensing temperature)
2. Condense (saturate) the refrigerant (Reject heat until all the refrigerant turns to liquid)
3. Subcool the refrigerant (Drop the temperature of the refrigerant below the condensing /
saturation temperature)

The condenser’s job is to reject heat (drop the temperature) of the refrigerant to its condensing
(saturation) temperature, then to further reject heat until the refrigerant fully turns to liquid. The
reason it must fully turn to liquid is that, in order for the refrigerant to boil in the evaporator, it
must first have liquid to boil.

The way in which the condenser removes the heat from the refrigerant varies. Most modern
condensers flow air over the tubing where the refrigerant is flowing. The heat transfers out of
the refrigerant and into the air. The cooling medium can also be water. In the case of a water
source system, water is circulated across the refrigerant in a heat exchanger.

In either case, the condenser relies on the removal of heat to another substance (air, water, glycol
etc..). For instance, if you turned off the condenser fan so that no air was flowing over the
condenser coil, the condenser would get hotter and hotter. This would cause the pressures to get
higher and higher. If it kept going that way it would trip the internal overload on the compressor
or cause other damage.

The hot vapor from the compressor enters the condenser and the superheat (temperature above
condensing temperature) is then removed. The refrigerant then begins to change state from
vapor to liquid (Condense). The refrigerant maintains a constant temperature until every
molecule of vapor is condensed. The temperature of the liquid again starts to fall. This is known
as subcooling. When we measure subcooling we are measuring degrees of temperature rejected
once the refrigerant has turned completely to liquid.

Temperature above the saturation temperature is called superheat. Temperature below


the saturation temperature is called subcool or subcooling. So when something is fully
vapor (like the air around us) it will be superheated, and when it is fully liquid (like the
water in a lake) it is subcooled.

Metering Device

The metering device is a pressure differential device that creates a pressure drop to facilitate
refrigerant boiling in the evaporator coil.

The metering device is located between the liquid line and the evaporator. The liquid line is full
of high-pressure liquid refrigerant. When the high-pressure liquid hits the small restrictor in the
metering device, the pressure is immediately reduced. This drops the pressure of the refrigerant
to such a degree, that the saturation temperature is lower than the temperature of the air
surrounding the tubing that the refrigerant is in. This causes the refrigerant to start changing
from liquid to vapor. This is called “boiling” or “flashing”. This “flashing” brings the refrigerant
down from the liquid line temperature to the boiling (saturation) temperature in the evaporator,
and in this process a percentage of the refrigerant is immediately changed from liquid to vapor.
The percentage of the refrigerant that changes during flashing depends on how great the
difference is. A larger difference between the liquid line temperature and the evaporator boiling
temperature results in more liquid lost to flashing and reduces the efficiency of operation.

There are a few different types of metering devices. The most common ones being the
Thermostatic Expansion Valve (TXV/ TEV) and the Fixed Orifice (often called a piston)– as
well as electronic expansion valves, capillary tubes, and others.
Evaporator

The evaporator is also known as the cooling coil, because the purpose of the evaporator is to
absorb heat. It accomplishes this through the refrigerant changing from liquid to vapor (boiling).
This boiling process begins as soon as the refrigerant leaves the metering device, and it
continues until the refrigerant has absorbed enough heat to completely finish the change from
liquid to vapor. As long as the refrigerant is boiling it will remain at a constant temperature; this
temperature is referred to as saturation temperature or evaporator temperature. As soon as the
refrigerant is done boiling, the temperature starts to rise. This temperature increase is known as
superheat.

When the indoor air temperature or the air flow going over the coil is higher, the evaporator
pressure and temperature will also be higher because more heat is being absorbed into the coil.
When the air temperature or airflow over the coil is lower, it will have lower pressure and
temperature in the coil due to less heat being absorbed in the coil.

The refrigerant leaves the evaporator, travels down the suction line and heads back to the
compressor where the cycle starts all over again.

Refrigerant Lines

Suction Line = Line Between the Evaporator and the Compressor

The suction line should contain low-pressure superheated suction vapor. Cool to the touch on
an air conditioning system, and cold to the touch in refrigeration.
Discharge Line = Line Between the Compressor and the Condenser

The discharge line should contain high temperature, high pressure superheated vapor

Liquid Line = Line between the Condenser and the Metering Device

The liquid line should be high pressure, slightly above outdoor temperature subcooled liquid

Expansion Line (When applicable) = Line Between the Metering Device and the
Evaporator

On most systems, the metering device will be mounted directly to the evaporator making the
expansion line a non-factor. Some ductless mini-split units will mount the metering device in
the outside unit making the second, smaller line and expansion line. The expansion line is full
of mixed vapor/liquid flash gas.