Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9

Prepared By: ICCE Quantity: 1

Unit Overview
Chiller Model Water-Cooled Optimus (TM)
Refrigeration Capacity 125.0 tons
Cooling Efficiency 0.7498 kW/ton
Compressor Configuration B1
Evaporator Configuration B1
Condenser Configuration B1
IPLV.IP 0.4514 kW/ton
NPLV.IP 0.4815 kW/ton
Unit Voltage 380.V/60.Hz/3Ph
Refrigerant Type Refrigerant charge R134a
Oil Cooler With Oil Cooler
Agency Listing C/UL listing
Pressure Vessel Code ASME pressure vessel code
ASHRAE 90.1 Compliance ASHRAE 2010
A-weighted sound pressure 83 dBA

Evaporator Information
Fluid Properties Flow Rate Construction Features
Fluid Type Water Design Flow 186.7 gpm Number of Passes 3 pass
Fluid Concentration 0.00 % Min Flow 168.0 gpm Tube Type Water only
Freeze Point 32.00 F Fluid Pressure Drop Right hand evaporator
Connection Side
connection
Fluid Temperatures Design PD 2.97 ft H2O
0.000100 hr-sq ft-deg
Evaporator Leaving 42.00 F Min PD 2.36 ft H2O Fouling Factor
F/ Btu
Evaporator Entering 58.00 F

Condenser Information
Fluid Properties Flow Rate Construction Features
Fluid Type Water Design Flow 302.7 gpm Number of Passes 2 pass
Fluid Concentration 0.00 % Min Flow 193.0 gpm Tube Type 0.025" - enhanced
Fluid Temperatures Fluid Pressure Drop Right hand condenser
Connection Side
connection
Condenser Leaving 99.00 F Design PD 4.95 ft H2O
0.000250 hr-sq ft-deg
Condenser Entering 87.00 F Min PD 2.16 ft H2O Fouling Factor
F/ Btu

Unit Electrical
Unit Voltage 380.V/60.Hz/3Ph Run load amps/AFD input amps 153.36 A
Compressor Starter Premium AFD Min Circuit Ampacity 191.70 A
Total Power 93.72 kW Max Overcurrent Protection 300.00 A
Terminal block conn. for incoming Max RLA 241
Power Line Conn. Type
lines
Short Circuit Current Rating 10000.00 A

Physical Information
Dimensions Weights Charge
Length 124.400 in Operating Weight 10101.6 lb Refrigerant 410.0 lb
Width 71.303 in Shipping Weight 9526.2 lb Oil 7.80 gal
Height 75.594 in

Warranty
Standard Warranty

2021-01-14 20:23:13Z Page 1 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

Information for LEED Projects


ASHRAE 90.1/CSA All weights +-3%. Weights include 150 psig water boxes.
ASHRAE 2010
compliance Operating weights include refrigerant, oil, and water changes.
Rated refrigeration Sound pressure measured in accordance with AHRI Standard 575-
184.0 tons
capacity (AHRI) 94.
Rated cooling efficiency Certified in accordance with the AHRI Water-Cooled Water-Chilling
0.6844 kW/ton and Heat Pump Water-Heating Packages Certification Program,
(AHRI)
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
IPLV.IP 0.4514 kW/ton 551/591 (SI). Certified units may be found in the AHRI Directory at
Cooling Efficiency 0.7498 kW/ton www.ahridirectory.org

Refrigerant (R-134a) 410.0 lb

Trane Select Assist


243
Version Number:
Data Generation Date: 1/14/2021

2021-01-14 20:23:13Z Page 2 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 3 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 4 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 5 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 6 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 7 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 8 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 9 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

2021-01-14 20:23:13Z Page 10 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

Validation Period
Product performance, mechanical specifications and submittal data is valid for a period of 4 months
from the date of the submittal generation. If 4 months or more has elapsed between submittal
generation and equipment release, the product and submittal will need to be verified. It is the
purchaser's responsibility to request such verification.

Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to
support the applicable operating weight (i.e. including completed piping, and full operating charges of
refrigerant, oil and water). Once in place, the unit must be level within 1/4" across the length of the
unit. The Trane Company is not responsible for equipment problems resulting from an improperly
designed or constructed foundation.

General
Exposed metal surfaces are painted with air-dry beige direct to metal single component paint prior to
shipment. Each unit ships with a full operating charge of refrigerant and oil. Molded elastomeric
isolation pads are supplied for placement. Start-up and operator instruction by factory trained service
personnel is included.

Agency Listing
The chiller is UL listed to U.S. and Canadian safety standards.

Pressure Vessel Code


Chiller complies with ASME Pressure Vessel Code. ASME nameplates are attached to applicable
pressure vessels including oil separators.

Compressor - Motor
Semi-hermetic, direct-drive, rotary compressor with capacity control adaptive frequency drive, slide
valve and differential refrigerant pressure oil flow system. Four pressure lubricated rolling element
bearing groups support the rotating assembly.

Motor is a suction gas cooled, hermetically sealed, two-pole, squirrel cage induction-type.

Adaptive Frequency Drive


Trane's Adaptive Frequency Drive (AFD) technology is specifically designed for Trane water chillers.
AFD incorporates the Trane communication protocol enabling seamless integration with the unit
controller. The AFD data such as drive status, temperature modes, and diagnostic information are
accessible to the unit controller and through the Tracer TU service tool.

The AFD contains technology that enables the drive to last the life time of the chiller and to operate
with less down time. The technology enables operation on various power systems including
alternative energy sources. AFD will protect itself and the compressor motor from over current, low or
high line voltage, phase loss, incoming phase imbalance, and over temperature due to loss of panel
ventilation.

The AFD incorporates improved serviceability and troubleshooting tools. All AFD control circuits are
powered with class 2 low voltage - separate from main power allowing service on the controls with the
panel door open. Additionally, the main electronic control modules can be serviced with the standard
Trane screw driver.

Drive Cooling
The drive is air-cooled with a ventilation fan in the panel.

2021-01-14 20:23:13Z Page 11 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

Evaporator
Shells are carbon steel plate. Evaporator is designed, tested and stamped in accordance with ASME
Code for refrigerant side working pressure of 200 psig (1379 kPa).

All tube sheets are carbon steel. Evaporator tubes are individually replaceable. Tubes are externally
finned, internally enhanced seamless copper with lands at both tube sheets. Evaporator tubes are 1-
inch (25.4) in diameter. Tubes are mechanically expanded into tube sheets and mechanically fastened
to tube supports.

Water pass arrangements are with grooved connections 150 psig (1034.2 kPa) waterside.
Connections are right-handed. Waterside is hydrostatically tested at 1 1/2 times design working
pressure.

Condenser Connection Type


Condenser water boxes are cast with standard grooved pipe connections. Cast boxes should not be
welded.

Oil Cooler
Unit has an oil cooler incorporated into the chiller oil circuit to provide reliable operation with low
design evaporator temperatures and/or high design condenser temperatures.

Refrigerant Isolation Valves


Isolation valves are added to the refrigerant circuit to provide means of isolating the refrigerant charge
in the condenser for installation separation or servicing.

Unit Controls
All unit controls are housed in an enclosure with removable plates to allow for customer connection of
power wiring and remote interlocks. All controls, including sensors, are factory mounted and tested
prior to shipment. Microcomputer controls provide all control functions including startup and shut down,
leaving chilled water temperature control, evaporator and condenser flow proving, compressor speed
control and loading, electronic expansion valve modulation, anti-recycle logic, and load limiting.

The UC-800 unit control module, utilizing Adaptive Control microprocessor, automatically takes action
to avoid unit shut-down due to abnormal operating conditions associated with low evaporator
refrigerant temperature, high condensing temperature, or current overload. Should the abnormal
operating condition continue until a protective limit is violated, the unit will be shut down. Unit
protective functions of the UC-800 include: low evaporator refrigerant pressure, high condenser
refrigerant pressure, low oil flow, critical sensor or detection circuit faults, current overload, high
compressor discharge temperature, communications lost between modules, electrical distribution
faults, phase loss, phase imbalance, phase reversal, external and emergency stop, momentary power
loss, under/over voltage, and loss of evaporator or condenser water flow.

Unit Display
A full color TD-7 AdaptiView touch screen display indicates all important unit parameters, in logical
groupings on various screens. The parameters including chilled water set point, leaving chilled water
temperature, entering condenser water temperature, evaporator and condenser refrigerant
temperatures and pressures, compressor data, and all pertinent electrical information. The display
also provides on screen trending graphs of predefined parameters as well as customizable trend
graphs based on user defined parameters. The display also provides indication of the chiller top level
operating modes with detailed sub-mode reports available with a single key press, as well as
diagnostics annunciation and date and time stamped diagnostic history.

Under/Over Voltage Protection


Unit is provided with under/over voltage protection, with actual volts shown on the clear language
display.

Chilled Water Reset


Chilled water reset based on return water temperature is provided. This includes unit controller display
of chilled water temperature.

2021-01-14 20:23:13Z Page 12 of 13


Job Name: LB 011221-1 Unit Tag: RTHD AFD 87-9
Prepared By: ICCE Quantity: 1

Short Circuit Current Rating


Starter has a short circuit current rating of 10,000 amps.

Insulation
Low temperature surfaces are covered with factory installed 3/4 inch (19.05 mm) Armaflex II or equal
(k=0.28) insulation, including the evaporator and water boxes, suction line, and motor housing. 3/8"
foam insulation will be used on the liquid level sensor and gas pump assembly, including piping. Lifting
lugs, base plates and service valves will not include insulation.

Shipment Packaging
Unit is provided with shrink-wrapped opaque plastic, with UV protection and rust inhibitor, around
entire unit for shipment.

2021-01-14 20:23:13Z Page 13 of 13