Technical Specification For Fire Detection and Alarm System
Technical Specification For Fire Detection and Alarm System
Technical Specification For Fire Detection and Alarm System
GENERAL: This General Technical Specification covers the technical requirement for
Microprocessor Based Analogue Addressable Type Intelligent Fire Detection and Alarm System
(FDAS) for Utility building and Vashi Zonal Store Building at BRIT Vashi Complex, Mumbai.
SCOPE OF WORK:
1. The FDA system shall cover design, engineering, supply, erection, installation,
testing & commissioning of the FDA system.
2. The FDA system shall consist of minimum following equipment: Smoke detectors,
Heat detectors, and Multi criteria detectors combination of rate of rise heat detector
& photo electric smoke detector, other types of detectors as per the design criteria.
3. Two MAIN FIRE ALARM CONTROL PANEL (FACP) along with accessories to
integrate with the firefighting system for automatic actuation.
4. Break glass type microprocessor based addressable manual call points with chain
& hammer.
5. Hooters.
6. Transponders/ Interface Modules.
7. Response indicators where required for above false ceiling detectors & normally
closed rooms.
8. Power supply equipment.
9. U.P.S system with Battery back - up for 24 hours, in case of power failure, shall be
provided.
10. Siren and Accessories.
11. All types of cables (FRLS) and cabling accessories.
12. Erection materials
13. Earthing Materials & Earthing.
14. Minor civil works required for installing FDA System equipment as required.
15. GI pipes /GI conduits /PVC rigid conduits and other accessories wherever required
for laying of cables. Trench work, if required, for cabling.
16. All erection accessories, consumables and miscellaneous material not indicated in
specification but required for completing the job in all respects.
17. Preparation of Design and detailed engineering drawings and documentation, bill
of materials with specification.
18. Testing and Training for operation and maintenance of the system, manuals, as-
built drawings, Commissioning spares till handing over of the system
19. One year onsite comprehensive warranty.
LIST OF ITEMS:
Panel shall monitor the status of all devices on the addressable loop for fire, short
circuit fault, open circuit fault, incorrect addressing, unauthorized device removal
or exchange.
Max. PSU Rating : 2.5A total, comprising Battery Charger: 0.5 Amp
Internal & External Loads : System Load: 1.8A @ 24V nominal, Max Loop Load:
460mA
Standby Batteries :24V sealed lead acid batteries, 2x 12V 12Ah
Mechanical Specifications
Dimensions (Height) : 51 mm installed in B501
Weight : 170 gr. (6 oz)
Operating temperature : - 10°C to 60°C
Humidity : 10% to 93%, non-condensing
Compatible bases : B501, B524IEFT, B524RLY
Electrical Specifications
Operating voltage : 15 to 32 Vdc
Alarm Current (LED on) : 7mA maximum
Stand by current : 200 μA maximum
Terminals : SEMS screws with clamping plates for up
to 2.5 mm2 (13 AWG) wire
Environmental Specifications: Temperature Range -30°C ... +70°C
Humidity 10 ... 93% relative humidity (non-condensing)
APPROVALS: M-RHSE: EN54-5: 2000 Class A1R (and EN54-17: 2005 for -I) HM-
FHSE: EN54-5: 2000 Class A1S (and EN54-17: 2005 for -I) EN54-5
states that Class A1 has a maximum application temperature of 50°C,
Class B has a maximum application temperature of 65°C.
Detectors: HM/FHSE Fixed 58° thermal detector
HM/RHSE Rate of Rise thermal detector
Accessories: Sensor and AV standard base, deep base, remote indicator for HM Series
detectors
4. Analogue Addressable Multisensory (Heat + Photo) Detector With Base For Below Ceiling:-
The Multi Sensor Detector shall be deployed as a smoke detector, heat detector or as a combination
detector, as per the site requirement. • Principle of function shall be “Scattered light” and “NTC
sensor”. • Smoke detection shall also always involve temperature evaluation. • In the event of a
rapid increase in temperature, it should get annunciate without the formation of smoke. • Smoke
and temperature sensors would be able to be activated and disabled separately. • Automatic
changeover based on time of day /season to season. • The highest degree of safety should be
maintained by detecting smoke particles of all sizes. • Detectors should have in-built integrated
short circuit isolator which shall ensure, in the event of a wire break or a short circuit, the fault is
localised and that the operation the loop circuit continues unimpeded. • The detectors should
constantly monitor their surrounding conditions with regard to absolute highest temperature and
relative temperature increase and should calculate the optimum smoke and heat sensitivity for the
area it is deployed in based on these factors. The sensitivity should always remain within the range
set out in standards. • Detectors should be capable of constant self-tests and should have resistant
against environmental influences. • Detectors shall have in-built over voltage protection
Features: -
Specifications: -
Mechanical Specification
Dimensions (mm) : 400 x 400 x 135 (H x W x D)
Weight : 115g
Colour : Pantone warm grey 1C
Material : Bay blend FR110
Terminal wire gauge : 2.5mm2 max.
Operating temperature: -20ºC to +60ºC
Relative humidity : 10% to 93 %( non-condensing)
Electrical Specification
Voltage : +15 to +32Vdc
Standby current:
No communication : 250μA @ 24Vdc maximum
One communication every 5 seconds,
LED blink : 300μA @ 24Vdc maximum
Alarm current : 7mA @ 24Vdc maximum
Sensitivity modes
1 High (1%/ft.)
2 Medium to high - auto adjusting (1-2%/ft.)
3 Medium (2%/ft.)
4 Low to Medium - auto adjusting (2-3%/ft.)
5 Low (3.5%/ft.)
6 Thermal only - Class A1R (58ºC)
Environmental Specifications:
Temperature Range -30°C ... +70°C
Humidity 10 ... 93% relative humidity (non-condensing)
APPROVALS: EN54-5:2000+A1:2002 EN54-17 : 2005 CEA 4021:2003 EN54-
7 : 2000+A1:2002+A2:2006 EN54-29:2015 6,1 to 9,4% variable
Obs./m + Class A1R Alarm Level 1 3% Obs./m + Class A1R Alarm
Level 2 3% ... 6.1% variable Obs./m + Class A1R Alarm Level 3
6.1% Obs./m + Class A1R Alarm Level 4 6.1 ... 9.4% variable
Obs./m + Class A1R Alarm Level 5 9.4% Obs./m + Class A1R
Alarm Level 6 Class A1R
Detectors: HM/PTSE Optical-thermal smoke detector
Accessories: Sensor and AV standard base, deep base, remote indicator for HM
Series detectors
5. Addressable Manual Call Point With Back Box: - The addressable Manual Call Point (MCP)
should be capable to manually trigger a fire alarm and should be suitable for connecting to OEMs
loop technology. The MCPs should contain a short circuit isolator and a red alarm LED. The alarm
should be triggered by smashing the glass panel, with the alarm remaining in alarm state until a
new glass panel is inserted. Manual call point shall be in compliance to EN54 Standards.
Features: -
• Direct decade addressing (01-99)
• Built-in electronics
• Fast response
• LED shows polling (optional) and activation
• Flush or surface mounting
• Up to 99 per loop (+99 analogue sensors)
• LPCB approved
• Simple to test
• Designed to the requirements of BS5839, Part 2
• IP67 rated model
Specifications: -
Mechanical Specification
Operating temperature : - 10°C to 60°C
Humidity : 10% to 93% non-condensing
Dimensions (HxWxD) : Surface: 87 x 87 x 52 mm
Weight : 125 gr.
Electrical Specification
Operating voltage : 15 to 32 Vdc
Current consumption
Stand by current : 200 μA @ 24 Vdc
LED current : 7 mA @ 24 Vdc
6. Fault Isolator With Base: - Fault Isolator Module shall be used on panel intelligent loop
communication circuits along with other modules and sensors. It detect a wire-to-wire short and
electrically isolates that condition from the circuit so that communication is maintained with
unaffected devices on the same circuit. Application: The module enables part of an intelligent
interface board communication circuit to continue operating when a short occurs on the circuit. If
used in a two wire loop configuration, one module isolates a short to the part of the loop between
the module and the intelligent interface board, allowing the rest of the loop to continue operating
normally, the modules isolate a short or open to the part of the loop between them. In a star
configuration a module can be used in each leg so a short on one leg does not affect communication
on any other leg. An integral LED blinks to indicate normal status and is on to indicate a short in
the loop.
Features: DIN rail mounting option • Surface mounting option • Plug in connectors • Tri-colour
LED status indication • Address selector switches visible in 2 planes • LED status visible in 2
planes • Approved to GEA GEI 1-082 and CEA GEI 1-084
Mechanical: Dimensions (mm) 93 x 94 x 23 (H x W x D) Weight 62g Operating
Environmental Specifications:
Temperature -20 ºC to +60 ºC
Humidity 0 to 95% maximum non-condensing
Electrical Specification
Electrical Operating voltage 15 to 30 Vac
Standby current 200µA at 24 Vdc maximum
Fault detection delay 100 to 400 mS on resistance 0.065Ω at 15 Vdc maximum
Terminal Wire 2.5 mm
DIN rail mounting clip
7. Response Indicator: - The response indicators should have to be of approved quality. Duel LED
should be there and should get actuate at the time fire detected in the detector.
FEATURES
Compatibility with all Detectors
Dual LED Lamp
ABS Plastic
Indoor use only
Wall Mounted & Ceiling Mount
TECHNICAL
SIZE H61m.m x W72m.m x D18m.m
Wire Entrance Back side of the Component
Alarm Current 10 mA, LED Lamp 5 mm LED Lamp Glow Light colour red
Enclosure Colour White or Off White
Voltage 24v Dc Mounting Methods in of the Cabinet
8. Loop Powered Sounder With Base: - Shall be suitable for indoor allocation. All hooters shall be
24 VDC operated. The Max sound level shall be about 100 dB @ 10 feet. Hooter shall be in
compliance to EN54 standards The hooters shall be loop powered and shall drew power from the
main panel for their operation in alarm condition.
Electrical Specification:
Supply Voltage: 15 to 32VDC (Non-isolation) 15 to 28VDC (Isolation)
Standby Current: 120μA (Non-Isolation) 225μA (Isolation)
Max current consumption: 11.4mA (High Volume Tone 21 @24V)
Max Sound Output 97dB (A) +/-3dB @1metre (High Volume, Tone 8 @24V)
Environmental Specification:
Operating Temp: -25o C to 70o C
Relative Humidity: Up to 95% non-condensing
Ingress Protection: IP44 (with surface mount base) IP65 (Waterproof base)
Approvals: Approved to: EN54-3, EN54-17 where applicable and CPD for RoHS, WEEE &
REACH information
Terminal Size: 1.5 - 2.5mm2 max
Number of Tones: 32 Volume Setting: High, Medium, And Low
Mounting options: Low Profile, Surface or High IP
9. Armoured Cables: - The cables required for detectors connection shall be multi core, stranded as
per IS-1554, IS – 8130 & IS – 5831. The cable shall be Fire Resistant Low Smoke (FRLS),
screened type. However if any special cables are required for detector cabling etc., the tenderer
shall specify clearly briefing the specification. For detector wiring - Annealed tinned solid copper
conductor of 1.5 sq. mm, as required (IS – 1554) PVC insulated & PVC sheathed, Armoured cable.
Cables connected to detectors shall be given ‘S’ loop on both sides of the detectors which shall be
properly clamped to the ceiling. ‘S’ loop shall also be left where cables connect sounders, panels,
dampers, etc., Appropriate glands shall be provided for the armoured cable near terminals of
junction box. All the cables and wires shall be tagged for proper identification. Wires shall be
identified by ferrules at junction and cables by colour bands at every 3 M distance. Over-headlines
for fire alarm system shall not be used when connecting different building. They shall be laid
underground according to IS: 1255-1983. The cables and wiring for fire Alarm circuit shall not be
clubbed with other cables and wiring which must be laid well away from them. The panel should
have additional capacity to operate auxiliary equipment like fire dampers, ventilation and / or
pressurizing fans, emergency light, smoke vents etc. if required.
Unused cable holes if any should be plugged. The contractor shall dispose of the debris in
connection with this job at his own expenses by his own transport and labour and clean out all part
of the work and leave everything clean.
10. UPS: Emergency power supply for a supply interruption period of 24 hours. • One point
monitoring for all detector zones. • Alarm counter. • Real time clock and Recognition and
evaluation of the status of detectors along with this all other parameters that are required for
making the addressable type control panel full proof should be maintained.
Input Voltage 220 - 240 Vac
Frequency 50/60 Hz ±3 Hz (Auto-sensing)
Brownout Transfer 155 Vac,
Typical Over-voltage Transfer 280 Vac,
Typical Output UPS Capacity (total) 1100 VA / 550 W
Voltage On Battery 230 Vac rms
Frequency on Battery 50/60 Hz ± 1 Hz
Transfer Time 4 ms typical
Protection AC Input Resettable circuit breaker
Battery Type (maintenance free, lead acid) 12 V, with 4 nos 12 AH
11. Junction Box: 4”/4” metal Junction box made of 16SWG sheet steel is to be provided for
mounting of detectors in the concrete mother ceiling along with necessary glancing.
12. Beam Detector: The linear BEAM type smoke detector should consists of a combined transceiver
unit and an accompanying reflector which is to be fitted without any other accessories. The
distance between opposite walls is to be kept between 10 and 80 m from one another. If required,
special additional stable ball joint units may be used to ensure that they are precisely fitted. The
infrared beam that is emitted by the transmitter and is to be bounced back by the reflector and to
be evaluated by the receiver. This is to be done by measuring the absorption of the infrared beam
and of the smoke or fire modulation. The detectors should get individually adapted to local
conditions in the event of there being difficult visible conditions like strong interference from
foreign light sources, reflections or very short monitoring distances etc. The beam detector should
be connected to the loop line via. individual monitor/ IO module to enable the detector being
addressable and it should operate in separate DC supply of 12 – 24 V
13. Fire Exit Board: Self illuminous “FIRE EXIT” sign boards shall be provided indicating escape
routes to escape.
PRE-DISPATCH INSPECTION: The following activities will be earned out without any
additional charges.
1. Checking the specifications of individual components.
2. Physical in inspection, dimensional check and mechanical fittings of individual sub-
assemblies.
3. Checking of functions of the microcontroller based control panel.
4. Checking of smoke detector, heat detector, hooter etc.
5. Testing of the micro controller panel using few of the test loops connected with smoke
detector, heat detectors and hooters.
6. Test for identification of fault in any detector m a loop and random checking of smoke
detectors, heat detectors and sounder from the panel.
7. Training can be given for operational and maintenance of the equipment. It includes
demonstration of systematic operating procedures for the operation of the equipment as
wen as handling of the instrument in case of system failure or some human faults and
training for the maintenance of the complete equipment.
8. Any instruments required to carry out the test at the time of inspection can be supplied by
the supplier.
ACCEPTANCE CRITERIA: - The following acceptance tests shall be apart from the standard
or routine tests should be normally conducted by the supplier after the installation of the complete
system.
Few of the test are mentioned below.
1. Testing of each components like smoke detectors, Heat detectors etc., by physical
simulation.
2. Functional tests of the microcontroller based fire alarm panel.
3. Zone alarm. Test, fault detection test etc.
4. The Mock trial of the complete Fire Detection and Alarms system,
5. Mains failure performance.
6. UPS consistency test.
7. Open/Short circuit of each detectors, sounder circuit to be tested etc.