EQUIPMENT: TM520

PUBLICATION: 08A-02-D16
ISSUE No. & DATE: 03 4/99

DOCUMENT CONTROL NUMBER /


TM520 TIMER MODULE

PRODUCT APPLICATION & DESIGN INFORMATION


1. INTRODUCTION 2. MECHANICAL CONSTRUCTION
The TM520 module is used to control the Sector Disable As stated, the TM520 Timer Module is fitted onto a custom
function i.e. disable detectors in specified sectors for a built facia plate designed to be mounted onto a standard dual-
predetermined time, i.e. whilst loading/unloading is in progress gang MK box. The dimensions of this facia plate are given in
in a large internal loading bay. The module may be connected Fig. 1.
via a CM520 Contact Monitoring Module or directly to the
controller via the Occupied Premises input and provides three The MK box is surface mounted. Suitable holes are required
volt free contacts [Common, Normally Open and Normally to be drilled in the box for electrical connection. A cable gland
Closed]. Once operated by the keyswitch, the module activates is required for MICC cable and conduit use, whilst a grommet
a relay for a predetermined period of time selected via a 7-way must be fitted when using PVC cable. The PCB is fitted with
DIL switch [see Table 1] plus a 5 minute safety timeout period. a red [TIMEOUT] and a yellow [TIMING] LED which extend
through the front of the facia plate and provides indication of
The TM520 Timer Module is contained on a double sided unit operation.
printed circuit board [PCB] which is fitted to a custom built
facia plate with a protective covering being fitted over the PCB,
leaving only the connection terminals and DIL switch
exposed. The facia plate is then fitted onto a standard dual-gang
MK box. The TM520 is designed for internal applications.

Fig. 1 TM520 Timer Module Switch Settings

© 1999 Tyco Electronic Product Group PAGE 1 of 3


Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE

$  ,17(51$7,21$//7'&203$1<
TM520
08A-02-D16
03 4/99

148

87

14

Fig. 2TM520 Timer Module Front Cover

3. OPERATION 4. TECHNICAL SPECIFICATION


The operation of the TM520 Timer Module is controlled by Overall Dimensions [see Fig. 1]
the TIMER OFF keyswitch, on operation of the key switch
the timing sequence is initiated. The yellow TIMING LED Weight: 100g
will flash one second ON, one second OFF. At the end of the
pre-determined time period, the red TIMEOUT LED will
light and the internal buzzer will sound synchronously with Material
the yellow TIMING LED for the 5 minute safety timeout Housing: ‘BAYBLEND’ [polycarbonate
period. /ABS alloy]
Operation may be cancelled at any time by turning the
TIMER OFF keyswitch off. Turning the TIMER OFF
Environmental
keyswitch OFF then ON within 3 seconds reinitiates the
timeout period. Operating Temperature: -200C to +700C
Relative Humidity: up to 95% RH
[non-condensing]

Electrical Characteristics
Power supply: 28V d.c. (from external
supply or controller)
Current rating: 40mA max when operated
Relay Contact Rating: 1A @ 24V d.c.
Relay Operation/Release: 7ms / 3ms

Electromagnetic Compatibility
EMC: Equals or exceeds the
requirements of
BS EN 50081-1 and
BS EN 50082-1

Note: The above standards fulfil the requirements


of the European Directive for EMC
(89/336/EEC).
Fig. 3 TM520 Timer Module PCB

PAGE 2 of 3
EQUIPMENT: TM520
PUBLICATION: 08A-02-D16
ISSUE No. & DATE: 03 4/99

Fig. 4TM520 Simplified Wiring Diagram

5. CABLING
Refer to Fig. 4. A maximum of one 1.5mm cable may be
connected at any one terminal.
The external power supply is connected as follows:
• Positive (+24V)
• Negative (GND)

6. ASSOCIATED EQUIPMENT
The Timer Module may be used in conjunction with a
CM520 Contact Monitoring Module.

7. ORDERING INFORMATION
TM520 Timer Module: 557-180-423

CB/jm
19th April 1999

© 1999 Tyco Electronic Product Group PAGE 3 of 3