Quick Reference-Fire Fighting (Part-1) : Class Type of Fire Type of Fire Extinguisher
Quick Reference-Fire Fighting (Part-1) : Class Type of Fire Type of Fire Extinguisher
Class of Fire
Fires involving Paper, Wood, Textile, Packing Water, foam, ABC dry power and
Class A
materials and the like. halocarbons.
Fires involving Oil, Petrol, Solvent, Grease, Foam, dry powder, clean agent and
Class B
Paints, Celluloid and the like. carbon dioxide extinguishers
Fires involving Electrical Hazards, Motor Vehicle Dry powder, clean agent and carbon
Class C
Gaseous substance under pressure. dioxide extinguishers
Fires involving Chemicals, Metal and active like Extinguishers with special dry
Class D
Magnesium ,titanium powder for metal tires
Sprinklers 6 sq.mt.
Hydrant Riser (Outlet 100 mm dia with landing valve and First aid hose reel) 930 sq.mt
Q = 3000 P
P = Population in Thousands
Note: The above rate must be maintained at a minimum pressure of 1 to 1.5 kg / cm2 for at least four hours.
Water Requirement for Wet Riser/Down Corner System (As per NBC -TABLE 4)
Water Requirement for Wet Riser/Down Corner System (As per NBC -TABLE 5)
Business Terrace
U.G. Water Storage Tank Static
Building Tank
15 m to 30 m 100000 lts (50000 lts if covered area in G.F is less than 300sq.m.) 20,000 lts
450 Liter/Min Pumps to be installed on the terrace to feed the Down Comer System.
900 Liter/Min Pumps to be installed on the terrace to feed the Down Comer System.
Type of Fires
Type of Extinguisher IS
Class Class Class Class
A B C D
IS 940 , IS
water type (gas cartridge) S NS NS NS
13385
IS 2171 , IS
dry powder type (gas cartridge) S S S NS
10658
dry powder type for metal fires IS 11833 NS NS NS S
IS 2878, IS
carbon dioxide type NS S S NS
8149
IS 4862 , IS
halon 1211 type S S S NS
11108
Pressure
Test Test
Maintained
Type of Extinguisher IS Interval Pressure
for Min.
(Year) (kg/cm2)
(kg/cm2)
IS2171,
Dry powder (gas cartridge) 3 35 2.5
IS10658
Water type 10
Foam type 10
Powder type 10
Carbon dioxide 15
Clean agent 10
Class
Type of Nature of
Occupancy of Typical Examples
Occupancy Occupancy
Fire
Lodging or rooming, one or two
Residential CLASS family houses, private dwellings,
Group A Low Hazard
buildings A dormitories, apartment houses, flats,
up to 4 star hotels, etc
Medium CLASS
Schools, colleges, etc
Hazard A
Industrial CLASS
Group G Low Hazard Small industrial units
buildings A
Corrugated carton manufacturing
Medium CLASS units, paper cane units, packing case
Hazard A manufacturing units, cotton waste
manufacturing units
Class of
Occupancy No of Fire Systems
Fire
One 4.5 kg capacity carbon dioxide or one 2/3 kg capacity clean agent
Special
extinguisher for every 100 m2 of floor area or part thereof with
Hazard
minimum of two extinguishers
One 10 kg dry powder extinguisher with special dry powder for metal
CLASS D High Hazard fires for every 100 m2 of floor area or part thereof with minimum of two
extinguishers per compartment/room
Size of the Mains for Fire Fighting as per Type of Building ( IS 3844 )
Mains of Fire
Type of Building Building Height
Fighting
150mm with twin XIII) All buildings classified under Above 25 m and area exceeding
outlet landing IV above 500m2/floor
a) Dry-riser system,
Type of
b) Wet-riser system,
Riser
c) Wet-riser-cum-down-comer system
d) Down-comer system.
Dry-riser main system can be installed in buildings under Group A (iI, ii, ii, iv ), where the
Dry-Riser height of building is above 15 m but not exceeding 24 m up to terrace level and where the
System ( for water supply for firefighting is immediately available either through the underground water
Cold Region storage tank/tanks or through water mains/town’s main
)
Dry-riser system does not include hose reel, hose cabinets, fire hose and branch pipes.
Wet-riser system should be provided in the types of buildings according to the provision
mentioned. The system should consist of a pipe or number of pipes depending on the
area and height of the buildings permanently charged with water under pressure with
landing valves, hose reel, hose, branch pipe, etc, at every floor level
A provision of pressure differential switch to start the pump automatically, so that water
under pressure is advisable for operational hydrant, hose reels, etc, as soon as the water
is drawn from hydrant landing valves causing drop in pressure. The system also
incorporates a stand-by pump to come into operation automatically when the normal
power supply source fails.
Fire service inlet with gate and non-return valve to charge the riser in the event of failure of
Wet-Riser
the static pump directly from the mobile pump of the tie services should: be provided on
System
the wet-riser system. The, fire service inlet for 100 mm internal diameter rising main
should have collecting head with 2 numbers of 63 mm inlets and for 150 mm rising main,
collecting head with 4 numbers of 63 mm inlets should be provided.
For wet-risers down-comer system, two pumps of different capacities one for the wet-riser
and the other for down-comer system should be installed. The pumps should be fed from
normal source of power supply and also by an alternative source in case of failure of
normal source.
For a wet-riser system, two automatic pumps should be installed to independently feed the
wet riser main, one of which should act as stand-by, each pump being supplied by a
different source of power. The pump shall be arranged so that when acting as duty-pump,
operate automatically when one or more hydrant is opened thus causing a drop in
pressure. The stand-by pump should be arranged to operate automatically in case of
failure of the duty pump. The system should have an interlocking arrangement so that only
one of the pumps operate at a time.
Down-Comer Single headed landing valve, connected to a 100 mm diameter pipe taken from the terrace
System pump delivery should be provided at each floor/landing, A hose reel conforming to IS 884 :
1985 and directly tapped from the down-comer pipe should also be provided on each
floor/landing.
As per ( IS 3844 )
The position of risers should be located within lobby approach staircase or within, the
Riser staircase enclosure when there is no lobby. However, the risers or the landing valves
connected
Landing valves should be installed on each floor level and on the roof, if accessible, in
Landing
such
Valve
a way that control line of landing valve is 1 to 1.2 m above the floor level.
In buildings with basements, the internal hydrants as well as the hose reel installations
should be extended to cover the basement area also, over and above sprinkler system,
as necessary. .
Fire hoses should be of sufficient length to, carry water from the nearest source of water
supply to the most distant point in the area covered by a hydrant, by the normal route of
travel. For each internal hydrant ( single headed ), there should be a total length of not
Fire Hoses
less than.30 m of 63 mm conforming to Type A of IS 636 : 1988 or provided in two
lengths of not more than 15 m each wire wound with coupling together with branch pipe
conforming to IS 2871 : 1983
Such spare hoses also should be in length of not more than 15 m complete with coupling.
Hoses and accessories should be kept in hose cabinet painted fire red and constructed
preferably of wood with glass front
In addition to wet-riser systems, first aid hose reels should be installed on all floors of
buildings above 15 m in height. The hose reel should be directly taken from the wet-riser
pipe by means of a 37 mm socket and pipe to which the hose reel is to be attached.
The hose reel should be sited at each floor level, staircase, lobby or mid-landing adjacent
Hose Reels to, exits in corridors in such a way that the nozzle of the hose can be taken into every
room and within 6 m of any part of a room keeping in view the layout and obstructions.
Tbe doors provided for the hose reel recesses should he capable of opening to
approximately 180”. when installation is in open areas, the position should be above head
height and the nozzle retainer and tbe inlet valve should be at about 900 mm above floor
level.
To allow any trapped air in the rising main to escape when water is pressurized into
Air Valve
system,air release valve should be incorporated above the highest outlet of each main.
For external hydrants, piping (water main ) should be laid preferably underground, to
avoid it getting damaged by moving vehicles, etc. To avoid rusting, underground pipes
should be either of cast iron conforming to IS 1536 in which case it should be properly
External
treated with a coat of primary paint with two coats of bitumen paint. The pipes should be
Hydrant
properly supported of pedestals – not more than 3 m apart. Underground pipes should be
laid 1 m below to avoid damage during road repair, etc, and at road crossings where
heavy vehicles are expected to pass, it should pass
For bigger buildings or major installations, where chance of such leakage is very
Jockey Pump considerable, it is desirable to install a small pump ( using a small motor and 200/300
liter/min pump ) with pressure switches for automatic start and stop.
In main high rise buildings, the basement is used for car parking/housing transformers/or
Using Wet- storages and other floors may be used as shopping areas departmental stores, etc, the
Riser System total area used for such purpose being small, in such cases, the same wet-riser pump
Pump for may be used for feeding the sprinkler system provided that:
Partial
Sprinkler a)the total area of the basement to be protected is less than 500 m2.
System b) the total area utilized as shops departmental stores is less than 1000 m2.
c)the pump has a capacity of at least 2850 l/min with suitable motor.
AS per IS 15301
The thickness of the foundation shall be 50 mm minimum for small pumps up to 900
Foundation of Liter/min capacity, 75 mm for pumps up to 2280 liter/min capacity and 100 liter/min for
Pump
bigger pumps up to 4 500 liter/min. For extra ordinary big pumps, the thickness may go
up to 150 mm. The size of the foundation shall cover the full length and width of the
pump and at least 150 mm on the front and back of the pump and 75 mm on the sides
as clearance.
Normally, pump rooms shall be located 6 m away from all surrounding buildings and
overhead structures
Where this is not feasible, they may be attached to a building provided a perfect
separation wall having 4 hour fire rating is constructed between the pump room and the
attached building, the roof of the pump room is of RCC construction atleast 100 mm
thick and access to the pump room is from the outside. The pump rooms shall normally
have brick/concrete walls and noncombustible roof with adequate lighting, ventilation
and drainage arrangements.
Pump Room
Transformer cubicles inside the sub-stations shall be separated from H.T. and L.T.
Location
cubicles and from each other by walls of brick/stone/concrete blocks or 355 mm
thickness or of RCC of 200 mm thickness with door openings, if any, therein being
protected by single fireproof doors having 2-hour fire resistance
Transformers installed outdoors, which are supplying power to fire pump shall also be
located at least 6 m away from all surrounding buildings including sub-station or D.G.
House, Where this is not feasible, all door and window openings of the building within 6
m of the transformers] shall be protected by single fireproof doors and 6 mm thick wired
glasses in steel
framework respectively.
Requirement of the Fire Safety for Group A – Residential Buildings – Above 15 m in height (IS 3844)
Type of Fire
Protection A3- Dormitories, A4- Apartments Houses A5- Hotels
Required
Above
15 Mts 35 Mts 45 Mts 15 Mts 30 Mts
Above
Fire Safety To 35 To 45 To 60 To 30 and A6
60 Mts
Mts Mts Mts Mts Hotels
(Starred)
Fire
Minimum 2 per floor Depending upon the Area and Travel Distance
Extinguishers
5,000
Terrace 25,000 liters 10,000 25,000 20,000 20,000
Level Over liters (5,000 liters liters liters liters
Head Tank capacity liters if capacity capacity capacity capacity
basement)
900 LPM
at
Terrace Fire Not Not Not Not Not
Terrace
Pump Required Required Required Required Required
level
Tank
Hose Reel
Required Required Required Required Required Required
Assembly
Not Not
Yard Hydrant Required Required Required Required
Required Required
Fire Service
Required Required Required Required Required Required
Inlet
Manually
Operated
Fire Alarm Required Required Required Required Required Required
Call Point
(MCP)
Automatic
Detection & Not Not Not
Required Required Required
Alarm Required Required Required
System
Required Required
if area of if area of
Automatic
basement basement
Sprinkler Required Required Required Required
exceeds exceeds
System
200 200
Sq.mts Sq.mts
Requirements of Fire Safety for Group B – Educational Buildings of above 15 mts in height (IS 3844)
Requirement of the Fire Safety for Group C – Institutional Buildings – Above 15 m in height (IS 3844)
Fire Safety (Active 15 Mts not 24 Mts not 15 Mts not 24 Mts not
Measures) exceeding exceeding exceeding exceeding
Fire Extinguishers Minimum 2 per floor Depending upon the Area and Travel Distance
20,000
Terrace Level Over 20,000 liters 10,000 liters 20,000 liters
liters
Head Tank capacity capacity capacity
capacity
1,50,000
Under Ground Water 1.00,000 liters 75,000 liters 1,00,000 liters
liters
Tank capacity capacity capacity
capacity
Not
Terrace Fire Pump Not required Not Required Not Required
Required
2 electric
pump & 1 1 electric pump
1 electric pump Diesel & 1 Diesel 2 electric pump &
Fire Pump near & 1 Diesel pump pump of pump of 1 Diesel pump of
Under Group Water of capacity 2280 capacity capacity 2280 capacity 2280
Tank LPM & Jockey 2280 LPM LPM & Jockey LPM & Jockey
Pump 180 LPM & Jockey Pump 180 Pump 180 LPM
Pump 180 LPM
LPM
Manually Operated
Fire Alarm Call Point Required Required Required Required
(MCP)
Automatic Detection
Required Required Required Required
& Alarm System
Automatic Sprinkler
Required Required Required Required
System
Requirement of the Fire Safety for Group D – Assembly Buildings Above 15 m in height (IS 3844)
D7 – Elevated or
D1 – Theater over 1000 persons, D6 – Not
underground for
D2 up to 1000 persons D3 – exceeding 30
Type of Fire assembly not covered
Permanent Stage over 300 persons mtrs
Protection D1-D6
Required
D4 – up to 300 persons, D5 all
others
Fire
Minimum 2 per floor Depending upon the Area and Travel Distance
Extinguishers
Terrace Level
10,000 liters 20,000 liters 20,000 liters
Over Head 20,000 liters capacity
capacity capacity capacity
Tank
1,00,000 liters
capacity
Under Ground 75,000 liters 1,00,000
D1-D5, 1,00,000 liters capacity
Water Tank capacity liters capacity
2,00,000 liters
for D6 Multiplex
Terrace Fire
Not required Not Required Not Required Not Required
Pump
Hose Reel
Required Required Required Required
Assembly
Down Comer
Not Required Not Required Not Required Not Required
System
Wet Riser
Required Required Required Required
System
Fire Service
Required Required Required Required
Inlet
Manually
Operated Fire
Required Required Required Required
Alarm Call
Point (MCP)
Automatic
Detection & Required Required Required Required
Alarm System
Automatic
Sprinkler Required Required Required Required
System
Requirement of the Fire Safety for Group E – Business Buildings Above 15 m in height (IS 3844)
Hose Reel
Required Required Required
Assembly
Down Comer
Not Required Not Required Not Required
System
Manually Operated
Fire Alarm Call Required Required Required
Point (MCP)
Automatic
Detection & Alarm Required Required Required
System
Automatic Sprinkler
Required Required Required
System
Requirement of the Fire Safety for Group F Mercantile Building Above 15 m in height (IS 3844)
Fire Extinguishers Minimum 2 per floor Depending upon the Area and Travel Distance
Automatic Sprinkler
Required Required Required
System
Requirement of the Fire Safety for Group G Industrial Buildings Above 15 m in height not to be permitted 18 Mts in height (IS 3844)
More
More More
than 100 More Up to
Up to 100 Up to than 100Sq.mtrs than 500Sq.mtrs
Fire Safety Sq.mt. & than 500 1000
Sq.mt 100Sq.mtrs and up to 500 and up to 1000
up to 500 Sq.mtrs Sq.mt
Sq.mtrs Sq.mtrs
Sq.mt
Fire
Minimum 2 per floor Depending upon the Area and Travel Distance
Extinguishers
5000 liters
5000 liters add 5000
in case of liters if the
Terrace 10,000 10,000 20,000
basement provision 10,000 Liters 20,000 Liters
Level Over liters Liters Liters
area of capacity capacity
Head Tank capacity capacity capaci
exceeds sprinkler
200m 2 in
basement
Under 1,00,00
Not Not 1,00,000 Not 75,000 Liters
Ground Not required Liters
required required liters required capacity
Water Tank capaci
Terrace Fire
450 LPM 450 LPM 450 LPM 900 LPM 900 LPM 900 LPM 900 LP
Pump
1 electric 1 elect
pump & pump &
1 Diesel 1 Diese
1 electric pump &
Fire Pump pump of pump o
1 Diesel pump of
near Under Not Not capacity Not capaci
Not required capacity 2280
Group Water required required 2280 required 2280
LPM & Jockey
Tank LPM & LPM &
Pump 180 LPM
Jockey Jockey
Pump Pump
180 LPM 180 LP
Manually
Operated
Not Not Not Not
Fire Alarm Not Required Required Requir
required required Required Required
Call Point
(MCP)
Automatic
Detection & Not Not Not
Required Not Required Required Requir
Alarm required required Required
System