Professional Documents
Culture Documents
Lee 2002
Lee 2002
Abstract: This paper describes a seismic design procedure for rib-reinforced steel moment connections based on an equivalent strut
Downloaded from ascelibrary.org by UTEP LIBRARY-SERIALS on 08/20/14. Copyright ASCE. For personal use only; all rights reserved.
model. It is shown from the results of finite-element analysis that the force transfer mechanism in the rib connections is completely
different from that predicted by the classical beam theory and that a diagonal strip in the rib acts as a strut. By treating the rib as a strut,
an equivalent strut model that could be used as the basis of a practical design procedure is proposed first. A step-by-step design procedure
is then recommended based on the proposed model.
DOI: 10.1061/共ASCE兲0733-9445共2002兲128:9共1121兲
CE Database keywords: Seismic design; Struts; Connections; Finite-element method; Models; Steel.
Introduction et al. 2000; Lee and Uang 2001兲. Especially, it was noted that an
inclined strip in the web of the straight haunch acts as a strut
The 1994 Northridge, California, earthquake caused widespread rather than following the beam theory. Lee and Uang viewed the
brittle fracture in connections of steel moment-resisting frames. A web of a straight haunch as a vertical rib plate and the haunch
variety of improved moment connection details have been pro- flange as a stability element. It was speculated that there exists a
posed after the earthquake. Now there is plenty of evidence that close link between the rib and the straight haunch.
the original welded connection with notch tough weld metal and a
few detail improvements 共the so-called WUF-W connection兲 can Objective and Scope
provide a very ductile response 共Ricles et al. 2000兲. However, the The main objective of this study was to propose a practical design
more popular strategies that have been developed include procedure for rib-reinforced steel moment connections. To this
strengthening the connection or weakening the beams that frame
into the connection 共Bruneau et al. 1998兲. The aim is, based on
the capacity design concept, to shift the plastic hinging away from
the face of the column, thus reducing the possibility of brittle
failure conditions. Fig. 1 shows an example of a rib-reinforced
moment connection 共the test specimen COH-1, Zekioglu et al.
1997兲. In this case, the rib reinforcement was used to supplement
the taper-cut reduced beam section 共RBS兲, i.e., to further limit the
stress in the beam flange welds and to provide increased redun-
dancy for the connection. Rib reinforcement may also be used to
address the situation where the frame design requires an excessive
RBS 共greater than 50% of the beam flange兲 due to short spans, or
larger beam depths 共Iwankiw 1997兲.
Engineers often use rib plates to enhance the seismic perfor-
mance of welded steel moment connections, thinking that the mo-
ment of inertia is increased near the face of the column so that the
tensile stress in the groove weld is reduced. However, such think-
ing is brought into question in this study. Previous studies have
indicated that the classical beam theory cannot provide reliable
force transfer predictions in steel moment connections with a
welded haunch 共Lee and Uang 1997; Lee and Uang 2000; Yu
1
Professor, Dept. of Architectural Engineering, Kyungnam Univ.,
Masan, South Korea, 631-701. E-mail: chlee@kyungnam.ac.kr
Note. Associate Editor: Brad Cross. Discussion open until February 1,
2003. Separate discussions must be submitted for individual papers. To
extend the closing date by one month, a written request must be filed with
the ASCE Managing Editor. The manuscript for this paper was submitted
for review and possible publication on July 12 2001; approved on January
3, 2002. This paper is part of the Journal of Structural Engineering, Vol.
128, No. 9, September 1, 2002. ©ASCE, ISSN 0733-9445/2002/9-
Fig. 1. Rib connection detail 共Zekioglu et al. 1997兲
1121–1129/$8.00⫹$.50 per page.
R ⫽tan⫺1(N/Q) 共deg兲 ers the strut action in the rib, is proposed for practical design
G ⫽tan⫺1(b/a) purposes. First, equivalent strut area A e is defined as
Downloaded from ascelibrary.org by UTEP LIBRARY-SERIALS on 08/20/14. Copyright ASCE. For personal use only; all rights reserved.
N⫽ 冉冊
b
a
Q (2)
Fig. 10. Comparison of deformed shapes Fig. 11. Definition of rib cross section width
冕
d x 共 strut兲 ⫽ ⫽ 0.60a
ke ke
d x 共 beam兲 ⫽ 共 x 兲 flange dx
Downloaded from ascelibrary.org by UTEP LIBRARY-SERIALS on 08/20/14. Copyright ASCE. For personal use only; all rights reserved.
⫽ ⫻Q
冕
(5)
共 ab⫺c 2 兲 tE db 0.60a
⫽ M 共 x 兲 dx
2EI b 0
⫽V pd 共 x⫹0.40a⫹L ⬘ /2兲 ⫺2 冉冊 b
a
Qx⫺Qd b (6)
The relationship between Q and is obtained by equating Eqs.
共5兲 and 共8兲 for deformation compatibility as follows:
冉 共0.21a⫹0.15L ⬘ 兲 ad b
Ib 冊 ⫻V pd
冉冊
Q⫽ (9)
1 共 0.60兲 冑共 a 2 ⫹b 2 兲 冑共 a⫺c 兲 2 ⫹ 共 b⫺c 兲 2 共 0.18b⫹0.30d b 兲共 ad b 兲
⫹
共 ab⫺c 2 兲 t Ib
To calibrate the equivalent strut area factor, horizontal shear force With an equivalent strut area factor of 1.50, Table 4 shows the
values Q obtained from the finite-element analysis within some degree of accuracy of Q and N values predicted by using Eqs. 共2兲
practical range of the rib slope and thickness were inserted into and 共9兲. Using a larger equivalent strut area factor 共say, 1.80兲
Eq. 共9兲. The results are summarized in Table 3. Although the produces only slightly larger predictions. Thus, it is recom-
factors vary more or less depending on the rib slope and thick- mended, for practical design purposes, that equivalent strut area
ness, they are fairly stable. The average value is close to 1.50. factor be taken as
⫽1.50 (10)
Knowing the two interface forces, the moment at the column face
is
冉 冊
below. H C ⫺d b ⫺2b
兺 M *pb ⫽ 兺 关 M pd ⫹V pd共 e⫹d c /2兲兴 HC
(18)
Preliminary Rib Sizing
Consider a portion of the moment frame in Fig. 4. Based on the 兺 M *pc ⫽ 兺 Z c共 F yc ⫺ f a 兲 (19)
available experimental and analytical database, suggested depth b
and angle G b ⫽tan⫺1(b/a)c are chosen as where Z c ⫽plastic section modulus of the column, F yc ⫽nominal
yield strength of the column, and f a ⫽column axial stress.
b⬇ 共 41 – 15 兲 d b (13)
G ⬇30° – 40° (14) Rib Design
Determine interaction forces Q and N by employing Eqs. 共2兲, 共9兲,
Beam Design Moment and Shear and 共10兲. Consider the free body of the rib shown in Fig. 15.
Based on the von Mises yield criterion, the minimum rib thick-
For design purposes, the plastic hinge is assumed to develop at ness can be computed as follows:
the narrowest section in the RBS 共see Fig. 4兲. Following the AISC
Seismic Provisions 共Seismic 1997兲, the design beam plastic mo- N
f v⫽ (20)
ment is bt
M pd ⫽1.1Z RBSF ye (15) Q
f n⫽ (21)
where Z RBS and F ye ⫽plastic section modulus at the narrowest bt
section in the RBS and expected yield strength of the beam, re-
spectively. The corresponding beam shear is then
Fig. 13. Comparison of flexural stress predictions Fig. 14. Free body for strong column–weak beam condition
冑冉 Q
0.707S⫻2a 冊 冉
2
⫹
N
0.707S⫻2a 冊 2
⭐ 共 0.6F EXX 兲 (25)
冑冉 Q
冊 冉
2
N
冊 2
Downloaded from ascelibrary.org by UTEP LIBRARY-SERIALS on 08/20/14. Copyright ASCE. For personal use only; all rights reserved.
Beam design moment and shear M pd ⫽1.1Z RBSF ye ⫽(1.1)(2,269,000)(314)⫽783,713 kN mm, 共15兲,共16兲
L ⬘ ⫽L⫺2a⫽4,560 mm, e⫽a⫹X/2⫽415 mm, L⫺2e⫽4170 mm; V pd ⫽417 kN.
Rib design 共1兲 Interaction forces; Q⫽637 kN, N⫽(150/220)(637)⫽434 kN; 共2兲,共9兲,共10兲
共2兲 Flexural stress level; f b f ⫽211 MPa⬍F ye ⫽314 MPa; 共24兲
共3兲 Rib thickness check; assuming dual rib configuration; 共23兲
Q共per rib兲⫽637/2⫽319 kN, N 共per rib兲⫽434/2⫽217 kN,
t⫽15 mm ⭓ 冑Q 2 ⫹3N 2 /(bF y )⫽11.2 mm.
Rib weld design 共1兲 Fillet weld 共two-sided兲 between the rib and beam 共26兲
S⭓ 冑Q 2 ⫹N 2 /(0.636aF EXX )⫽5.6 mm; use 6 mm fillet weld;
共2兲 Use CJP groove weld to connect the rib to column flange.
Design of continuity and doubler plates Beam flange force P u f ⫽957 kN; no doubler plates were needed in this case and the 共29兲
continuity plates were provided according to the SAC 共2000兲 recommendations.
the RBS effectively pushed the plastic hinging of the beam out-
Fig. 16. Connection details of example design side the rib region. In the finite-element model, a circular hole
was included near the rib tip to reduce stress concentration; the
finite-element analysis results showed that drilling a circular hole
Design Example and Analytical Verification decreases the magnitude of the horizontal shear, vertical normal,
and von Mises stresses at the rib tip by about 17, 2, and 4%,
By assuming some realistic design conditions, the example design respectively.
was conducted by following the proposed design procedure. In
this example, the connection design by the weakening strategy
alone is not feasible, because a short span length 共assumed as 5 m Conclusions
long兲 requires an excessive RBS 共greater than 50% of the beam
flange兲. The rib was designed by assuming a 30% radius cut of The main conclusions on the seismic design of steel moment
the beam flange. Design conditions were as follows. connections reinforced with ribs are summarized as follows.
1. The force transfer mechanism in the rib connections is com-
pletely different from that predicted by the classical beam
Frame Data theory. The flexural stress prediction from the beam theory,
An exterior moment connection was considered with the follow- treating the beam and ribs as an integral section, underesti-
ing data: story height H c ⫽3600 共mm兲; bay width L⫽5,000 mates significantly the stress in the beam flange groove
共mm兲; beam H-600X200X11X17 共SS400 steel, F y ⫽236 MPa, welds. The diagonal strip in the rib acts as a strut, and strut
F ye ⫽314 MPa兲; column H-400X408X21X21 共SM490 steel, F yc action tends to produce reverse shear in the beam web.
⫽325 MPa兲; rib plate 共SM490 steel, F y ⫽325 MPa兲; a filler metal 2. Idealizing the rib as a strut, an equivalent strut model that
with a specified CVN value of 26.7 J 共20 ft lb兲 at ⫺28.9°C can be used to determine the interaction forces at the inter-
共⫺20°F兲 is to be used to connect the beam flanges and rib plates face between the beam and rib was proposed. With an
to the column (F EXX ⫽492 MPa兲; a uniformly distributed gravity equivalent strut area factor of 1.50, the proposed model pre-
load for the beam w g ⫽19.6 kN/m; and column axial stress f a dicted the interaction forces satisfactorily. Based on the pro-
⫽69 MPa. posed model, a step-by-step design procedure was also rec-
ommended.