Professional Documents
Culture Documents
Er-105-1-1 - Proflo No-Flow Switch
Er-105-1-1 - Proflo No-Flow Switch
It is good practice to attach the welding ground clamp as close as possible to the area
where the welding will occur and to use the lowest practical welder output setting. Welding
must not cause a current flow across any compressor bearing surface, including but not lim-
ited to crankshaft and crosshead bearing surfaces.
Proflo Installation
1. Loosen the two hex-socket set screws on top of
Proflo case and remove magnet housing. Do not
remove magnet, spring, and spacer from
magnet housing.
2. Remove end plug from desired divider valve.
The Proflo installs on either side of any divider
valve, but requires the correct magnet housing
for each divider valve manufacturer (Trabon,
Lincoln). NOTE: Do not install the Proflo on
any divider valves with cycle indicator pins.
3. Verify O-ring is in place on Proflo magnet
housing. Screw magnet housing into end of 1. End Plug 5. Hex-Socket Set Screws (2)
divider valve. Torque magnet housing to 15 foot- 2. Divider Valve 6. LCD Display
pounds max. 3. Magnet Housing 7. Wire Leads
4. Slide Proflo all the way onto magnet housing. 4. O-Ring
Torque set screws to 15 inch-pounds max. DO FIGURE 2 Typical Proflo Installation
NOT over tighten set screws.
5. The Proflo LCD indicates cycle time. Verify correct operation by pumping oil through the divider valve
assembly. The LCD enables the operator to adjust the lubricator pump for correct cycle time. The force
feed lubricator data plate on the lubricator box indicates either normal and break-in cycle times at
maximum rated speed, or normal cycle time for applied speed. Use break-in cycle times only for the first
200 hours of operation before changing to the normal cycle time. If unable to determine cycle time,
contact the Ariel Response Center.
6. All conduit and connections should be appropriate for area classification. Use flexible conduit to ease
installation. Support conduit and fittings to minimize vibration.
7. After Proflo installation or performance of any maintenance on the lube system, compressor cylinders, or
packing, pre-lube the complete system with a purge pump to purge air from the divider valves
and all components BEFORE COMPRESSOR START-UP.
Display Errors
ALARM - Displays when divider valves are not cycling. Programmed divider valve cycle time has expired.
ALARM flashes every 2 seconds during compressor shutdown.To clear alarm, press SET. Alarm will clear
and again indicate cycle time upon compressor re-start.
OVERLOAD - Indicates a wiring short or circuit switching of too large a load. To correct this, check wiring
insulation for bare wires touching ground or each other. Insulate unused wires or re-terminate wires. Self-
resetting fuses on the inputs protect Proflo electronics; they auto reset 45 seconds after fixing a short.
NOTE: Moisture on Proflo circuitry causes most reset errors. Several design precautions keep
moisture from the circuit board:
l The Proflo housing is completely sealed in a low humidity room.
l There is a desiccant pack in the circuit board chamber.
l The circuit boards have a protective conformal coating.
The Proflo monitor stores up to one year of operating data in first in, first out (FIFO) memory. FFT software
can reset Proflo memory. Reset time and date records to the Proflo Electrical Erasable Programmable
Read Only Memory (EEPROM).
To start the download, push SET then push MODE five times until the LCD displays SEND DATA?, then
push SET again. Set the FFT software to accept the Proflo data and hold the handheld computer in a pos-
ition to communicate with the IrDA port. The LCD displays SENDING. If there is no device to receive data,
the LCD displays FAILURE and returns to LAST and AVG default display after 30 seconds. The software
converts Proflo data to Microsoft Excel files for trending and graphing.
The internet or most electronic and discount stores offer hand-held palm operating system computers. For
more details on this and other Proflo accessories, contact your packager or Ariel.
4. If isolated inputs are not an option, connect the alarm/shutdown contact to the safety system and install
another proximity switch for the control system to read and calculate oil consumption. Contact Ariel for a
proximity switch part number.
Some relays may require a current limiting resistor to prevent shorting the power supply through the relay
coil. Many relays come with built-in current limiting circuits. The control system designer must choose proper
relay components.
Enter the above calculation as a constant for each Proflo. In the example, the PLC calculates a running total
by adding 0.004987 pints to a totalizer the whole time the compressor runs. Use this information to track oil
consumption.
Proflo Specifications
l Temperature Range: -40°F to +185
l Switching Capability: 170 VDC - 120 VAC @ .5 Amps
l Environment Rating: Class I Div. 2 Groups A,B,C,D - T4
l Internal Power: AA Lithium batteries.
l Device Inputs: Remote switch closure from proximity switch to enable operator to mount Proflo in a
control panel, control room, or other location.
Proflo Accessories
1. AC panel mount power supply - for safe area only.
2. Panel mount kit. Includes panel mount bracket and a proximity switch.
3. Relay interface module. Use to switch an AC load 120/240 VAC @ 10 Amps.
4. Additional proximity switch.
5. Palm interface Fluid Flow Trending (FFT) software. Converts all information to Excel format for hard
copy trending, graphing, and presentation:
For more details on the Proflo and available accessories, contact your packager or Ariel.
The contents of this document are proprietary and confidential. They are the property of Ariel Corporation and may
not be disclosed, reproduced, or used for manufacture in part or in whole without written permission from Ariel Cor-
poration.