355 BASIC X-SERIES TECHNICAL TRAINING

INSTALL AND SETUP X4I EXERCISE


_________________________________________________________________________

INSTRUCTIONS

The following exercise is to familiarize on the setup of the X4i Controller for 2 units of rotary
simulators. The X4i is a basic system controller that controls 2 to 4 compressors. Proper
installation and setup is the key factor during commissioning of the new controller.

You will use the designated training X4i simulator, and two Electronic Controller simulators
for this exercise. This exercise is marked and contributes to your final score for the course.

The following activities are to be performed:

1. Wire up the IR-PCB to the Electronic Controller simulators


2. Wire up the X4i to the IR-PCB
3. Configure the X4i Controller
4. Verify the operation of the Electronic Controller simulators with the X4i

Note:
1. All fields of each form are to be completed.
2. Put a Tick on each box after completing the steps
3. Participants will be assessed on the criteria at the attached Performance Checklist.
355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________
355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________
PROCEDURES

Exercise Scenario

Electronic Controller simulator with Remote Load/Unload and Remote Load Enable inputs –
Configured as compressor#1 and compressor#2 in the network with a capacity of 600 cfm
Customer downstream pressure expectation – 110psi
Customer prefers FILO operation and would want a rotation of sequence on every day
2300hrs. When the X4i is stopped, all compressors must goes back to local control

1. Wire up the IR-PCB to the Electronic Controller simulators

a. Connect control cables supplied with the IR-PCB kit from Electronic Controller

simulators to the IR-PCB as shown in the diagram

b. Provide a suitable 115Vac to the Electronic Controller simulators

X - SERIES AUTOMATION
COMPRESSOR #1
+VDC 15 Remote Load/Unload
X01 TERMINAL
C01 VFD/fixed 2 24Vac
V1 V V
Load Enable 13 Remote Enable
1 1 SEQ CONT
Load/Unload
2 2 LOAD UNL
3 3 GND C03
NO
4 4 D11
OUT

C
5 5 D12
NC
6 6 +20V C02
NO
LED 5 VFD
IN

C
LED 2 LOAD
NC
LED 1 SEQ
READY
LED 4

18 0Vac
RUN
LED 3

ALARM
11 Alarm
C05
C04 RUN
9 Run
1
2 READY

IR-PCB

7 Ready

2. Wire up the IR-PCB to the X4i Simulator

a. Connects X4i Terminal PCB Terminal X01 to IR-PCB for 1st Electronic

Controller simulator as shown above

b. Connects X4i Terminal PCB Terminal X01 to IR-PCB for 2nd Electronic

Controller simulator as shown above


355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________

3. Wire up the X4i simulator

a. Connects 115/230Vac to XPM-TAC24 Terminal X01 L (X01-2), N (X01-1) and

E (X01-3)

b. XPM-TAC24 Terminal X04 configured as __________________________

c. Connects Pressure Transducer Pin 1 (signal) to X4i Terminal PCB X05-26

d. Connects Pressure Transducer Pin 3 (+V) to X4i Terminal PCB X05-25

4. Power up the X4i Simulator and configure it

a. Set Menu S01 Ct to ___________________________

b. Set Menu S01 TS to ___________________________

c. SetMenu S01 RP to ____________________________

d. Set Menu S02 NC to ___________________________

e. Set Menu S02 PM to ___________________________

f. Set Menu S02 CF to ___________________________

g. Set Menu S03 1O to ___________________________

h. Set Menu S03 1R to ___________________________

i. Set Menu T01 PH to ___________________________

j. Set Menu T01 PL to ___________________________

k. Set Menu T01 Pm to ___________________________

l. Set Menu T01 SQ to ___________________________

m. Set Menu T01 Compressor#1 Priority to ____________

n. Set Menu T01 Compressor#2 Priority to ____________

o. Set Menu C01 Compressor#1 Hours to _____________

p. Set Menu C01 Compressor#2 Hours to _____________

q. Menu C02 Compressor#1 is for which simulator _________________

r. Set Menu C02 Compressor#1 Interface Type to _________________


355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________
s. Set Menu C02 Compressor#1 Start Time to ____________________

t. Set Menu C02 Compressor#1 Alarm Input to _____________

u. Menu C02 Compressor#2 is for which simulator _________________

v. Set Menu C02 Compressor#2 Interface Type to _________________

w. Set Menu C02 Compressor#2 Start Time to ____________________

x. Set Menu C02 Compressor#2 % Alarm Input to _____________

5. Apply power to the Electronic Controller simulators

6. Press the Start button on the X4i simulator.

7. Ensure X4i is controlling the Compressors correctly according to the Sequence


355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________
355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________

INSTALL AND SETUP X4I

Candidate Name: ……………………………………………………………

Date: ………………………………………………………………………….

Did the Candidate:


Y N
1. Understand scope of work required

2. Setup the IR-PCB to Electronic Controller Simulator

3. Setup the IR-PCB to X4i

4. Setup and Configure the X4i

5. Clean and clear the Simulators of all debris and leave in a good working state

Result:

Candidate completed the task satisfactorily

Candidate requires further practice at this activity before full competency is achieved

Signed: Acknowledgement:
Instructor Candidate

Further Action:
355 BASIC X-SERIES TECHNICAL TRAINING
INSTALL AND SETUP X4I EXERCISE
_________________________________________________________________________