Instructions For Mounting and Maintenance of Relays of The SPA-300 Series

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

34 SPA 11 EN1A

Instructions for mounting and 1990 - 10 - 19


maintenance of relays of the Written
Checked
SPA-300 series Approved
ABB Network Control
& Protection

U4 U5 U1 U2 U3

Fig. 1. A SPA-300 series relay unit with the system panel removed.
U1, U2, U3 Measuring relay modules
U4 Auxiliary output relay module
U5 Power supply module

Construction A relay unit of the SPA-300 range comprises and the mother PC board has to be discon-
five relay modules, i.e. three measuring relay nected at the module side.
modules (U1, U2, U3) as well as an output
relay module (U4) and a power supply module The input/output module is bolted to the rear of
(U5) located behind a common front plate. the case. It contains the terminal blocks of the
relay case, the matching transformers, a mother
The relay modules can be changed without PC board interconnecting the relay modules,
undoing the wirings. Each measuring relay and the wiring between the terminal blocks
module is locked to the collar of the case by and the mother PC board.
means of two finger screws. The relay modules
are removed by unwinding the screws and Changing of the locations of the measuring
withdrawing the relay modules from the case relay modules in the case does not affect their
by means of the screws. operation, but because the control signals of
the output relays are separately wired from
Before withdrawing the power supply or each PC board location to the auxiliary relay
auxiliary output relay module the system panel module, the measuring relay modules have to
has to be removed by undoing the four fixing be located according to the module symbols
screws. The modules are pulled out of the (U1, U2, U3) marked on the system panel of
case by using the handle on the front of the the relay case and the type designations relating
module. When removing the output relay to these.
module, the flat cable connecting the module

1
Handling of the Because the relay modules of the relay particular, it is important to protect the separate
relay modules assembly, i.e. the measuring modules and the modules against static discharge electricity.
power supply and auxiliary relay module, An anti-static plastic bag should always be
contain integrated circuits which are sensitive used for transporting and storing detached
to static electricity, they should be handled relay modules.
with care when removed from the case. In

Installation The relay case is made of an extruded The relay is designed for flush mounting. To
drawings and aluminium profile, the collar is of cast aluminium reduce the mounting depth a raising frame of
dimensions and the cover of a clear UV-stabilized 40 mm, 80 mm or 120 mm for the flush mounting
polycarbonate. case can be delivered on separate order.

226 285 Serial


249 34 interface
20 229
162

136

Flush mounted relay case


Terminals

a b 214 ±1

139 ±1
Panel cut-out

Raising frame a b
SPA-ZX 301 209 74
SPA-ZX 302 169 114
Mounting bracket SPA-ZX 303 129 154

The relay is fixed to the mounting panel by The rear part of the relay contains two pairs of
means of four mounting brackets. The collar is terminal blocks. Each terminal is dimensioned
provided with a rubber gasket providing a IP 54 for one or two max. 2.5 mm2 wires. A connection
degree of protection between the case and the diagram adjacent to the terminal blocks
mounting panel. illustrates the connection of the terminals.

The cover is locked with two sealable finger When using a raising frame, SPA-ZX 301,
screws. The rubber gasket between the cover SPA-ZX 302 or SPA-ZX 303, the dimensions
and the collar ensures that the cover, too, of the panel cut-out are the same as those for
fulfills the IP 54 requirements. The opening a normal flush mounting case.
angle of the cover is 145o.

2
Maintenance Due to the lack of wearing components The best results with regard to preventive
electronic devices need no preventive measures are obtained by controlling the
maintenance. The slow ageing of the ambient temperature and the relative humidity
components is not perceivable in practice. in order to keep these within given spec-
ifications. Further, the environment should be
Cleaning of the contacts of the PC board free from dust and corrosive gases.
connectors may, however, prevent possible
contact faults.

Testing When the auxiliary voltage is connected to the In most fault situations a fault code, indicating
relay, the measuring relay modules perform a the nature of the fault, appears on the display
self-testing program including the testing of of the faulty relay module. The fault code,
e.g. the contents of the microprocessors’ which consists of one red digit and a green
program memories and the displays of the code number, cannot be removed from the
measuring modules, though the operator has display by resetting. The fault code should be
to inspect the function of the displays visually. recorded and stated when ordering service.
The matching transformers and the contacts of
the output relays are not included in the test. The self-supervision system output contact of
the relay assembly operates on the circuit-
The measuring relay modules also perform opening principle. Thus an auxiliary voltage
self-testing in normal service situations. If a failure also leads to an activation of the self-
permanent fault is detected by the self-testing, supervision alarm.
when connecting operating voltages or in a
normal service situation, the driver circuits of Mostly, a fault can be eliminated by changing
the output relays of the concerned module are one of the modules of the relay assembly.
blocked, the red IRF indicator starts glowing
and the protective relay releases a self- For complete operational testing of a protective
supervision alarm. The indicator starts glowing relay ordinary relay testing equipment is to be
and the alarm is activated approx. 1.5 minute used. Such a test includes the matching
after the fault was discovered. transformers, the output relays and the
accuracy of the operating values.

Trouble-shooting If the self-supervision alarm of a protective - If the IRF indicator of each measuring relay
relay assembly is activated, the following module glows, and the fault code 1004 is
measures can be taken to locate the fault: indicated on the display, the auxiliary relay
module is defective, or the flat cable between
- If none of the IRF indicators of the measuring the mother PC board and the auxiliary relay
relay modules glows, neither does the green module has got loose, or the cable terminals
Uaux indicator on the system front panel, the are defective. Check the terminals and the
power supply module of the protective relay connection of the flat cable. Change the
assembly is defective or the auxiliary voltage output relay module.
supply fails. Check and repair the auxiliary
supply or change the auxiliary power module. - If the IRF indicator of a measuring relay
module glows and the display shows a fault
- If the IRF indicator of only one measuring code other than 1004, the relay module is
relay module glows, and the display of the defective. Change the module, record the
module shows the fault code 1004, the fault code and state it when ordering service.
concerned module or the output relay module
is defective. Change the measuring relay
module or the output relay module.