Air System Sizing Summary for SS Cuarto de UPS

Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1


01/27/2021
Prepared by: UNICLIMA 09:53

Air System Information


Air System Name ........................... SS Cuarto de UPS Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 360,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,0 Tons Load occurs at ..................................................... Jul 1600
Total coil load .......................................................... 23,5 MBH OA DB / WB ...................................................... 86,4 / 73,8 °F
Sensible coil load ................................................... 18,5 MBH Entering DB / WB ............................................. 74,6 / 63,3 °F
Coil CFM at Jul 1600 ............................................. 1044 CFM Leaving DB / WB .............................................. 56,3 / 55,3 °F
Max block CFM ..................................................... 1044 CFM Coil ADP ..................................................................... 54,3 °F
Sum of peak zone CFM ........................................ 1044 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,785 Resulting RH ................................................................. 54 %
CFM/Ton ............................................................... 532,6 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 183,6 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 65,4 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 4,71 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1044 CFM Fan motor BHP ........................................................... 0,14 BHP
Standard CFM ......................................................... 933 CFM Fan motor kW ............................................................. 0,11 kW
Actual max CFM/ft² ................................................. 2,90 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 126 CFM CFM/person .............................................................. 63,00 CFM/person
CFM/ft² ................................................................... 0,35 CFM/ft²

Hourly Analysis Program 5.11 Page  1  of  14 


Zone Sizing Summary for SS Cuarto de UPS
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

Air System Information


Air System Name ........................... SS Cuarto de UPS Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 360,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1044 1044 2,90 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 18,1 Dec 1700 0,4 360,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
SS Cuarto de UPS 1 18,1 Dec 1700 1044 0,4 360,0 2,90

Hourly Analysis Program 5.11 Page  2  of  14 


Air System Design Load Summary for SS Cuarto de UPS
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 86,4 °F / 73,8 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 152 ft² 672 - 152 ft² 434 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 360 ft² 108 - 360 ft² 0 -
Partitions 236 ft² 354 - 236 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 450 W 1336 - 0 0 -
Task Lighting 259 W 821 - 0 0 -
Electric Equipment 3600 W 11572 - 0 0 -
People 2 411 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 1000 - 0 0
Safety Factor 10% / 5% 1527 71 0% 0 0
>> Total Zone Loads - 16801 1481 - 434 0
Zone Conditioning - 16457 1481 - -605 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1044 CFM 0 - 1044 CFM 0 -
Ventilation Load 126 CFM 1620 3586 126 CFM 1027 0
Supply Fan Load 1044 CFM 387 - 1044 CFM -387 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 18464 5067 - 35 0
Central Cooling Coil - 18464 5067 - 0 0
>> Total Conditioning - 18464 5067 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  3  of  14 


System Psychrometrics for SS Cuarto de UPS
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

July DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 86,4 0,01721 126 400 1620 3586
Vent - Return Mixing Outlet 74,6 0,01131 1044 632 - -
Central Cooling Coil Outlet 56,3 0,01016 1044 632 18464 5067
Supply Fan Outlet 56,7 0,01016 1044 632 387 -
Cold Supply Duct Outlet 56,7 0,01016 1044 632 - -
Zone Air - 73,0 0,01050 1044 664 16457 1481
Return Plenum Outlet 73,0 0,01050 1044 664 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 16801 Cooling 16457 73,0 1044 664 0 0

Hourly Analysis Program 5.11 Page  4  of  14 


System Psychrometrics for SS Cuarto de UPS
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 126 400 -1027 0
Vent - Return Mixing Outlet 65,4 0,01024 1044 466 - -
Central Cooling Coil Outlet 65,4 0,01024 1044 466 0 0
Supply Fan Outlet 65,8 0,01024 1044 466 387 -
Cold Supply Duct Outlet 65,8 0,01024 1044 466 - -
Zone Air - 66,4 0,01024 1044 475 605 0
Return Plenum Outlet 66,4 0,01024 1044 475 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -434 Deadband 605 66,4 1044 475 0 0

Hourly Analysis Program 5.11 Page  5  of  14 


System Psychrometrics for SS Cuarto de UPS
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 09:53

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: July DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014

2 0,012
34 5
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  6  of  14 


System Psychrometrics for SS Cuarto de UPS
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 09:53

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  7  of  14 


Air System Sizing Summary for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

Air System Information


Air System Name .......................... SS Hall de asensor Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 155,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 0,7 Tons Load occurs at ................................................... Jun 1500
Total coil load ............................................................ 8,0 MBH OA DB / WB ...................................................... 86,0 / 74,0 °F
Sensible coil load ..................................................... 4,5 MBH Entering DB / WB ............................................. 75,8 / 67,3 °F
Coil CFM at Jun 1500 ............................................. 265 CFM Leaving DB / WB .............................................. 58,1 / 57,4 °F
Max block CFM ....................................................... 265 CFM Coil ADP ..................................................................... 56,1 °F
Sum of peak zone CFM .......................................... 265 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,568 Resulting RH ................................................................. 68 %
CFM/Ton ............................................................... 400,1 Design supply temp. ................................................... 56,0 °F
ft²/Ton ................................................................... 233,7 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 51,3 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 1,59 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 265 CFM Fan motor BHP ........................................................... 0,04 BHP
Standard CFM ......................................................... 237 CFM Fan motor kW ............................................................. 0,03 kW
Actual max CFM/ft² ................................................. 1,71 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 55 CFM CFM/person .............................................................. 13,81 CFM/person
CFM/ft² ................................................................... 0,36 CFM/ft²

Hourly Analysis Program 5.11 Page  8  of  14 


Zone Sizing Summary for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

Air System Information


Air System Name .......................... SS Hall de asensor Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 155,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 265 265 1,71 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 4,1 Jan 2000 0,0 155,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
SS Hall Ascensor 1 4,1 Jan 2000 265 0,0 155,0 1,71

Hourly Analysis Program 5.11 Page  9  of  14 


Air System Design Load Summary for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 86,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 92 ft² 0 - 92 ft² 0 -
Partitions 368 ft² 552 - 368 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 165 W 484 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1280 - 0 0 -
People 4 810 820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 1500 - 0 0
Safety Factor 10% / 5% 363 116 0% 0 0
>> Total Zone Loads - 3989 2436 - 0 0
Zone Conditioning - 3734 2436 - -436 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 265 CFM 0 - 265 CFM 0 -
Ventilation Load 55 CFM 690 999 55 CFM 540 0
Supply Fan Load 265 CFM 98 - 265 CFM -98 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4522 3435 - 6 0
Central Cooling Coil - 4522 3436 - 0 0
>> Total Conditioning - 4522 3436 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  10  of  14 


System Psychrometrics for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

June DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 86,0 0,01752 55 400 690 999
Vent - Return Mixing Outlet 75,8 0,01414 265 1053 - -
Central Cooling Coil Outlet 58,1 0,01108 265 1053 4522 3436
Supply Fan Outlet 58,5 0,01108 265 1053 98 -
Cold Supply Duct Outlet 58,5 0,01108 265 1053 - -
Zone Air - 73,1 0,01325 265 1224 3734 2436
Return Plenum Outlet 73,1 0,01325 265 1224 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 3989 Cooling 3734 73,1 265 1224 0 0

Hourly Analysis Program 5.11 Page  11  of  14 


System Psychrometrics for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 09:53

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 55 400 -540 0
Vent - Return Mixing Outlet 66,0 0,01024 265 431 - -
Central Cooling Coil Outlet 66,0 0,01024 265 431 0 0
Supply Fan Outlet 66,4 0,01024 265 431 98 -
Cold Supply Duct Outlet 66,4 0,01024 265 431 - -
Zone Air - 68,1 0,01024 265 439 436 0
Return Plenum Outlet 68,1 0,01024 265 439 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband 436 68,1 265 439 0 0

Hourly Analysis Program 5.11 Page  12  of  14 


System Psychrometrics for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 09:53

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: June DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 1
4. Supply Fan Outlet 0,018
5. Room Air

0,016
2

Specific Humidity ( lb/lb )


5 0,014

34 0,012

0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  13  of  14 


System Psychrometrics for SS Hall de asensor
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 09:53

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  14  of  14 