Professional Documents
Culture Documents
Hydrofit General Contractors Guide 2012
Hydrofit General Contractors Guide 2012
Installation
Process
General
Contractor
Guide
Coordination between the various building trades during the elevator installation process is
essential for the smooth installation, completion, and final Code Authority acceptance of the project
elevators.
The information contained in this reference manual is intended as a tool and an aid to the General
Contractor/Project Manager. The purpose is to ensure that “elevator related” work items are
identified early in the construction process. This will allow other trades sufficient time to complete
their work to permit a timely elevator installation and successful final elevator inspection by the
local Code Enforcing Authority.
A Contractors Pre-Start Checklist and key items of coordination is enclosed, along with a “Work
by Others Reference” section. This information should be shared with the appropriate
subcontractors. The checklist items must be completed, and the form signed and returned, before
Otis can begin the installation. If drilling is required, the “Outside Drilling Information” form must
be completed and a copy sent to Otis and the Drilling contractor.
A Contractors Pre-Inspection Checklist of the non-elevator work items is enclosed. This form
along with the “Work by Others Reference” section serves as a ready reference. These items,
which are often cited as deficiencies during the Code Authority inspection, must to be complete
prior to the elevator being inspected and approved for public use.
Prior to calling for Code Inspection, all elevator as well as non-elevator work items, outlined in the
pre-inspection checklist, must be complete and ready for final inspection. Otis will not be
responsible for re-inspection fees or additional labor cost caused by the failure of other
trades to perform as required.
We would also like to take the opportunity to advise you that it is the policy of Otis Elevator
Company that 90% of the contract amount is paid before the equipment is turned over to you. If
you foresee any problems with this requirement, please contact the Otis Superintendent.
The enclosed information is provided as a reference based on current Code interpretations and
experience. Local Code Authority interpretation of requirements may at times differ and obviously
will govern.
Pit
Pit must be clean and dry with overhead protection (cleaning & pumping of pit by others).
Pit specifications per Otis contract drawing (i.e., width, length and depth).
Metal pit ladder extending from the pit floor upward, not less than 48” above the bottom landing floor level.
Hoistway
Hoistway clean and dry with overhead protection.
Hoistway rise and rough opening per Otis contract drawing (i.e., width, length and depth). Plumb within 1”.
Overhead clearance per Otis contract drawing.
Blockouts for to-from oil line and wiring (machine room HydroFit) (all cutting and patching by others).
Rail bracket inserts, entrance support, and fastenings per Otis contract drawing. All intermediate steel in place as required.
Rail bracket attachment supports must be exposed and flush with the clear hoistway line and finished floor flush with inside
hoistway wall line. Surveyor to coordinate floor lines as required.
Safety
Otis / OSHA approved, freestanding, removable barricades on all floors.
Steel safety beam properly supported and secured against movement located over the center of main rails with a minimum
load rating of 5000# (or greater) as indicated on the Otis contract drawing.
Working area clear of debris, which could cause an accident.
Adequate lighting in front of hoistway, and in machine room.
OSHA approved stairwell access to all floors.
Elevator work Areas 55º min.
#2
#1
#3 #4
Occupied
Building
Otis Requirements
Installed by others, maintained by Otis
Free-standing, removable barricades
Barricade should span only one rough opening
Typical 2”x4” timber construction (minimum)
Lintel/Header Beam
(By others)
10"
Rough Opening
Rough Opening
Fixtures Clear Opening
Rough Opening
Note: If deviation of above is required, seek approval in writing through the Otis Construction
Superintendent.
(Rev. 8/2006)
Key Item of Coordination
3 1/2" M in.
W
7 1/4" M ax.
5/8"
(2) Layers 1/2" or 5/8" Sheetrock
Drywall Arrangement - D2 - 2 layers of gypsum wallboard on corridor side and 2 layers of gypsum
wallboard on hoistway side around metal or wood studs.
(2) Layers 1/2" S heetrock (2) Layers 5/8" Sheetrock
3 1/2" M in. W ood or X 3 1/2" Min.
W ood or X Metal Stud 7 1/2" Max.
M etal S tud 7 1/2" M ax.
Drywall Arrangement - D3 - 1 layer of gypsum wallboard on corridor side and 1 layer of gypsum wallboard
on hoistway side around metal or wood.
F W W
W
5/8" 1/2"
Notes:
1. All frames are bolted. Frame heads project 1/4" (6 mm) beyond front face of side jamb. All jamb faces (head and sides) are 2".
2. Embossed handicapped plates measuring 4" x 4" (102 mm x 102 mm) are applied to both jambs of each entrance at appropriate
height, characters are 2" (51 mm) high and raised with adjacent Braille.
3. Opening type and size are per cab selection. Entrances arranged for flush sill support per layout "Detail A".
4. Arrangements D1, D2, M1, M2, and M3 have a one and a half (1½) hour fire protection rating. Arrangement D3 has a one (1) hour
fire protection rating.
5. Sight guards are black with any metal finish door. Powder painted doors have matching powder painted sight guard.
Warning - Interface of the two-hour wall with the Otis frame by the drywall constructor must be per Otis requirements in order
to maintain the fire rating of the entrance assembly, only the exact arrangements depicted above can be provided.
The location of the HydroFit MRL access door in critical to ensure proper component
clearances and elevator operation. The elevator layouts include details on positioning this
door, specifically the door jamb, and these requirements need to be clearly understood.
The requirements reference the position of the inside edge of the door jamb, not the rough
opening. The rough opening requirements will depend on the door frame construction and wall
interface and should be accounted for so that the final door jamb position is as indicated on the
layout.
Rev. 9/2012
Key Item of Coordination
Requirements:
1. The access door size is 914mm (3’-0”) wide x 2134mm (7’-0”) tall.
2. Standard self closing and self locking metal door with a group 2 locking device
per agreed upon location and Otis layout. Self closing mechanism cannot
protrude into the machine space at any time. Door knob shall have a blank plate
on the hoistway side of the door.
3. The door must be located on an interior wall of the building. It cannot be opened
to the outside of a building.
4. The dimension locating this access door from the front hoistway wall only has a
+/- 6mm (1/4”) tolerance. – SEE DETAIL ON NEXT PAGE
3’-0” Door
2’-7”
Left-hand Controller
3’-0” Door
2’-7”
Right-hand Controller
Rev. 9/2012
Key Item of Coordination
DOOR DIMENSION
“X” FROM INSIDE
TYPE DUTY
FRONT HOISTWAY
WALL
2100 31 ± ¼”
2500 (787 ± 6mm)
PASSENGER
3000 33 ± ¼”
3500 (838 ± 6mm)
4500 16 ± ¼”
HOSPITAL/SERVICE
5000 (406 ± 6mm)
36” DOOR
(913mm)
(SEE TABLE)
X
Rev. 9/2012
Confirmation of HydroFit Machine Roomless Access Door Size and Position
Customer: OTIS ELEVATOR COMPANY
Project: Contact:
Phone: Fax:
NOTE: Installation will not be started until the owner or the owner's representative signs and returns this form to Otis Elevator
Company. This form must be completed, signed and returned by _____ to meet the scheduled completion date of _ _ ___ .
You are requested to verify (or correct) this information and confirm its accuracy by your signature in the space provided. Should a
change in the information provided subsequently occur, immediate notification of the change is necessary.
A. Machine Roomless Access Door Dimensions
Access door must be 36” (3’), 914 mm wide by 84” (7’), 2134 mm tall.
B. Machine Roomless Access Door Position
For 2100 and 2500 passenger duty elevators the inside edge of the access door jamb (show below) must be between 30-3/4
inches and 31-1/4 inches (781 and 793 mm) from the front hoistway wall.
For 3000 and 3500 passenger duty elevators the inside edge of the access door jamb (show below) must be between 32-3/4
inches and 33-1/4 inches (832 and 844 mm) from the front hoistway wall.
For service/hospital duty elevators (4500, 5000, and 5000AIA LB) the inside edge of the access door jamb (show below)
must be between 15-3/4 inches and 16-1/4 inches (400 and 412 mm) from the front hoistway wall.
The above access door dimensions and position are confirmed:
This form is in the Approval package and provides the
information that the
SIGNED BY: __________________________________ (sub)contractor
DATE: ________________ will need to meet
the elevator requirements.
1 2 3 4 5 6 7
A1
A TM
A
OTIS HYDROFIT MRL ACCESS DOOR REQUIREMENTS
B
SHEET NO. KIT DESCRIPTION REMARKS B
2 MRL PASSENGER DUTY WORKING SPACE SAFETY ZONE
3 MRL HOSPITAL DUTY WORKING SPACE SAFETY ZONE
4 --- MRL ACCESS DOOR SURFACE MOUNT
5 MRL ACCESS DOOR FLUSH MOUNT SUPPLIED BY OTHERS
6 MRL ACCESS DOOR RECESSED MOUNT
C NOTE: C
7' DOOR
OPENING
SEE AAA29517B_FMI FOR SHROUD INSTRUCTION
DOOR REQUIREMENTS
PROVIDE A ROUGH OPENING FOR AND INSTALL A 3' X 7' STANDARD FIRE RATED INTERIOR DOOR ON ONE
SIDE OF THE HOISTWAY, AS SHOWN ON THE OTIS LAYOUT. WHEN DETERMINING THE LOCATION OF THE
MACHINE SPACE DOOR, THE DIMENSION ON THE OTIS LAYOUT IS FROM INSIDE DOOR EDGE OF THE JAMB
AND NOT THE DOOR STOP EDGE. PLEASE BE ADVISED THAT THIS DOOR LOCATION IS VERY CRITICAL.
FOLLOW DOOR MANUFACTURING INSTRUCTIONS FOR THE DIFFERENT TYPES OF HOISTWAY WALL MATERIAL
AND MAKE THE APPROPRIATE ADJUSTMENTS SO THAT THIS DOOR WILL BE PLACED IN THE PROPER LOCATION.
THE DOOR FRAME MUST BE SECURLY MOUNTED TO THE WALL TO SUSTAIN A CANTILEVERED / HORIZONTAL
FORCE EXERTED BY ELECTRICAL DISCONNECT(S), ELECTRICAL CONDUIT AND WIRING UP TO AN APPROXIMATE
325 lb. LOAD. THE DOOR IN SOME CONFIGURATION HAS A MINIMUM OPENING OF 180 .
D D
MRL ACCESS DOORS MUST MEET CODE COMPLIANT FIRE RESISTIVE CONSTRUCTION. THE DOOR SHOULD BE SELF
CLOSING (LOCAL BUILDING CODE DEPENDANT) AND BE SELF LOCKING WITH A GROUP 2 LOCKING DEVICE. IN
ADDITION, ENSURE THAT ALL AIR GAPS AROUND THE DOOR ARE SEALED (i.e. THRESHOLD, WEATHER STRIPPING,
ETC.). SELF CLOSING MECHANISMS CANNOT PROTRUDE INTO MACHINE SPACE AT ANY TIME. THE MACHINE
SPACE DOOR KNOB SHALL HAVE A BLANK PLATE ON THE HOISTWAY SIDE OF THE DOOR.
CRITICAL NOTE:
DOOR MUST NOT BE LOCATED ON AN OUTSIDE WALL.
Rev.1998-03-01
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
PASSENGER DUTY
(2100, 2500, 3000, 3500)
A A
1092
DOOR HAND SHOWN IS RECOMMENDED, BUT IF DOOR [3' - 6"]
HAND RESTRICTS WORKING SPACE DUE TO WALLS OR
OTHER BUILDING STRUCTURES, THEN DOOR HAND
MUST BE OPPOSITE DOOR HAND SHOWN IS RECOMMENDED, IF DOOR CAN
NOT OPEN 180 DEGREES OR DOOR RESTRICTS WORKING
SPACE DUE TO WALLS OR OTHER BUILDING STRUCTURES,
THEN DOOR HAND MUST BE OPPOSITE
1092
[3' - 6"]
MINIMUM 180 DOOR OPENING
B B
MINIMUM DOOR OPENING
1219
[4']
1219
[4']
C C
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
HOSPITAL DUTY
(4500, 5000)
A A
1092 1092
[3' - 6"] [3' - 6"]
B B
1219
[4']
C C
1219
[4']
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
A A
B [3' - 0"]
914 DOOR
B
2100 787 6 mm
2500 [2' - 7" 1/4 in]
P
3000 838 6 mm
CLEAR HOISTWAY 3500 [2' - 9" 1/4 in]
4500 406 6 mm
H
[1' - 4" 1/4 in]
D 5000 D
FRONT HOISTWAY WALL
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
A A
B B
[3' - 0"]
914 DOOR
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
A A
B B
[3' - 0"]
914 DOOR
2100 787 6 mm
2500 [2' - 7" 1/4 in]
CLEAR HOISTWAY P
3000 838 6 mm
3500 [2' - 9" 1/4 in]
4500 406 6 mm
H
[1' - 4" 1/4 in]
D 5000 D
FRONT HOISTWAY WALL
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
The HydroFit machine room less (MRL) arrangement requires the use of a shroud that
serves three purposes:
1. It provides a mounting location for the mainline and cab lighting disconnects
2. It defines the space that is allowed for the disconnects to avoid any potential
interference with the elevator components.
3. It acts as a barrier to prevent access to the hoistway in the upper portion of the
MRL access door.
The shroud design is not “handed”; it will work with either left or right MRL machine
space locations. The shroud is simply flipped accordingly to orient the deeper section
toward the rear of the hoistway for passenger duties or to orient the deeper section to
the front of the hoistway for hospital (service) duties. The cover plate on the bottom of
the shroud is then removed.
Installation:
The shroud ships with hardware and brackets for mounting it in the machine space door
jamb, adjustable unistrut sections for mounting the mainline disconnects to the shroud,
and both top and bottom covers (note: once installed the cover on the bottom is
removed).
Brackets to set
(locate) shroud from
top of door jamb
Unistrut provides
adjustment for mounting
a range of disconnect
cabinet sizes
Note: The small brackets may need to be removed and reattached depending on the
which side of the hoistway the MRL access door is and what “hand” of the shroud is
needed…the deeper section of the shroud is oriented toward the rear of the hoistway for
passenger duties (2100, 2500, 3000, 3500) or toward the front of the hoistway for
hospital (service) duties (4500, 5000, 5000AIA).
EXAMPLE: For a 2500lb duty passenger car, orient the deep portion of shroud to rear of
hoistway; shallow portion toward the front of hoistway
Front of Hoistway
Attach mounting
brackets to top of
Small cover plates shroud w/ screws
used to fill slots provided
when smaller
disconnects are If top of jamb is >2” the
mounted supplied brackets may
not work as intended
Unistrut can be
removed if
necessary for
deeper disconnects
Mounting brackets can be used to hang shroud from top of door jamb; the brackets also
set the correct depth of the shroud in the jamb
The shroud fits inside jamb and is butted up against the top inside of the jamb; ensure
that it is plumb and parallel to the jamb; attach to jamb with screws provided.
Inside top of
door jamb
7/8”
7/8”
21”
13-3/4”
29”
Deep section - up to
11” deep w/o
unistrut - handle in
furthest extended Shallow section
position (On or Off) 7-1/8” deep
Example of installed shroud and disconnects (2500 lb passenger duty, car offset = left):
Front of hoistway
(car offset = left)
Front of hoistway
(car offset = right)
1 2 3 4 5 6 7
A1
A TM A
OTIS HYDROFIT MRL SHROUD
NOTE: FOR FUTHER DETAIL ASK YOUR LOCAL OTIS REPRESENTATIVE FOR
THE MANUFACTURING DRAWING OF THE SHROUD (ABA384AVP)
C C
D D
Rev.1998-03-01
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
B. SLOT GUARDS ARE USED TO COVER SLOTS FOR SAFETY WHEN ABA384AVP1
SMALL DISCONNECTS ARE MOUNTED.
ITEM DESCRIPTION PICTURE QTY
C. HANGER TO BE USED TO MOUNT SHROUD TO DOOR JAMB. A MOUNTING PANEL (ABA384AVP2) 1
A IF DOOR JAMB IS RECESSED AWAY FROM HOISTWAY, HANGERS B GUARD (ABA384AVP4) 4
A
WILL HELP LINE UP SHROUD. IF DOOR FRAME IS MORE THAN
C HANGER (ABA384AVP3) 2
2 INCHES WIDE HANGER WILL NEED TO BE REMOVED.
D UNI-STRUT (AAA347BLG25) 2
D. UNI-STRUT IS TO HELP IN MOUNTING SMALLER DISCONNECTS. E COVER TOP (ABA384AVP6) 1
IF DISCONNECT IS TO DEEP, REMOVE UNI-STRUT.
F COVER BOTTOM (ABA384AVP6) 1
E & F. DEPENDING ON THE ORIENTATION E OR F COULD BE A
TOP OR BOTTOM. ALWAYS REMOVE BOTTOM. G M12 X 25 HEX HEAD SCREW 4
B B
M6 X 12 HEX HEAD THREAD
K 10
ROLLING SCREW
M4 X 8 HEX HEAD THREAD
L 6
(LEFT HAND CAR OFFSET SHOWN) ROLLING SCREW
TOP
TOOLING LEGEND
BOLT/NUT SIZE WRENCH/SOCKET REQUIRED
[6.673]
169.5
M4
C C
M6
M12
[4.409]
NOTE:
112
BOTTOM
(SEE NOTE 1)
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
ORIENTATION GUIDE
A A
DOOR
DIRECTION
C C
CAR OFFSET
D D
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
ORIENTATION GUIDE
A A
CAR OFFSET
B B
DOOR
DIRECTION
C C
D D
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
ORIENTATION GUIDE
A A
B B
C C
DOOR
DIRECTION
CAR OFFSET
D D
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
ORIENTATION GUIDE
A A
B B
CAR OFFSET
DOOR
DIRECTION
C C
D D
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
224
D [8.819]
SHROUD
DEPTH MAX
A
B B
A
C C
C
0.320
D D
D0.240
B A-A
B-B
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
224
[8.819]
D SHROUD
DEPTH MAX
B B
A
D D
A-A
B B-B D0.240
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
224
[8.819]
SHROUD
D DEPTH MAX
B A B
D D
D
B-B A-A
0.240
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
B B
C C
NOTHING BELLOW
SMOKE SENSOR SMOKE SENSOR
SUPPLIED BY OTHERS
NOTHING BELLOW
SUPPLIED BY OTHERS
BOTTOM LINE
THIS POINT
BOTTOM LINE
THIS POINT
[1.319]
[1.319]
33.5
33.5
E
WARNING
CHANGES
THIS WORK AND THE INFORMATION IT CONTAINS ARE THE
PROPERTY OF OTIS ELEVATOR COMPANY ("OTIS"). IT IS DWG E
DELIVERED TO OTHERS ON THE EXPRESS CONDITION THAT
IT WILL BE USED ONLY FOR, OR ON BEHALF OF, OTIS;
THAT NEITHER IT NOR THE INFORMATION IT CONTAINS
WILL BE REPRODUCED OR DISCLOSED, IN WHOLE OR IN
PART, WITHOUT THE PRIOR WRITTEN CONSENT OF OTIS;
AND THAT ON DEMAND IT AND ANY COPIES WILL BE
PROMPTLY RETURNED TO OTIS.
FORM PA1102
CHK
APPD SHEETS
AUTH
SHEET
(Rev. 8/2012)
Key Item of Coordination
Note: Standard Machine Room Rear (w/ Car Offset = Right) – opposite of above
(Rev. 8/2012)
Key Item of Coordination
Simplex Duplex
11'-6" (3505mm) - 2 Car Group
5'-9" (1753) 17'-0" (5182mm) - 3 Car Group
mm) 22'-0" (6708mm) - 4 Car Group
8'-6"
Controller Controller
Controller 7'-4" (2591mm)
(2236)
3'-6"
(1067mm)
CLEAR 4'-0"
(1220 mm)
3'-6" CLEAR
MAIN LINE & MAIN LINES & (1067mm)
3'-6" (1067mm) CLEAR LIGHT SW. 3'-6" (1067mm) CLEAR
LIGHT SW.
(NOT BY OTIS) CLEAR
(NOT BY OTIS)
OTES: NOTES:
. Machine room size reflects the typical worst case condition and Otis' largest tank size. 1. Machine room sizes reflect the typical worst case conditions and Otis' largest tank size.
2. All Machine room sizes and clearances are ANSI & NEC Compliant. Consult your local code for greater clearances
. All Machine room sizes and clearances are ANSI & NEC Compliant. Consult your local code for
required in your area.
reater
clearances required in your area. 3. It is recommended that a minimum clearance of 4" be maintained between the tank and the machine room wall.
Notes:
. It is recommended that a minimum clearance of 4" be maintained between the tank and the 4. The preferred machine room location is adjacent to the hoistway at the lowest landing, however, remote machine
rooms are acceptable.
machine room wall.
. The preferred machine room location is adjacent to the hoistway at the lowest landing, however, remote
machine
1. Machine room sizes reflect the typical worst case conditions and Otis' largest tank size.
rooms are acceptable.
2. All machine room sizes and clearances are ANSI & NEC Compliant. Consult your local code for
greater clearances required in your area.
3. It is recommended that a minimum clearance of 4" be maintained between the tank and the machine
room wall.
(Rev. 8/2012)
Key Item of Coordination
Consult the Otis Construction Superintendent if any unusual space conditions exist.
Rev.8/2012
Preparatory Work By
Others
PREPARATORY WORK BY OTHERS
The following items must be performed or provided at no cost to Otis Elevator Company (“Otis”) by the
Owner or General Contractor or their agents in accordance with governing codes. The price and
installation schedule of Otis is based on these jobsite conditions existing at the beginning and during
installation of the elevator equipment. Failure to provide the items specified in this list will result in
additional work performed by Otis beyond the scope of our contract causing installation delays. A
change order will be submitted by Otis for materials and / or labor expended.
All work to be performed per the latest revision of the applicable national code and / or local code.
4. Prior to the start of installation, provide a dry, properly framed, enclosed and vented hoistway in accordance with
all applicable codes.
5. Provide a clear plumb hoistway with variations from the size shown on the Otis layout not to exceed -0 inch / +1
inch (25 mm).
6. Install per Machine Room / Machine Space Prep / Work and Electrical Requirements.
Provide a rough opening for and install a 3’ X 7’ standard fire rated interior door on one side of the hoistway, as
shown on the Otis layout. When determining the location of the machine space door,the dimension on the Otis
layout is from the inside door edge of the jamb and not the door stop edge. Please be advised that this door
location is very critical. Follow door manufacturing instructions for the different types of hoistway wall material
and make the appropriate adjustments so that this door will be placed in the proper location.
The door frame must be securely mounted to the wall to sustain a cantilevered / horizontal force exerted by the
electrical disconnect(s), electrical conduit, and wiring up to an approximate 150 lb. load. Install per Machine
Room / Machine Space Prep / Work and Electrical Requirements. The door should be able to open fully (180°).
7. Furnish adequate rail bracket supports and bracket spacing as required by governing code from pit floor to top of
hoistway. For steel or wood frame construction, adequate backing for a rail bracket to be installed not less than
10’-3” (3124 mm) or more than 11’-3” (3429 mm) from the top landing. Furnish separator beams where required.
Rail bracket attachment supports must be exposed and flush with the clear hoistway line.
If the floor to floor height exceeds the maximum bracket spacing allowed by the elevator code, Otis requires some
form of steel support to properly attach our guide rail brackets. The maximum allowed bracket spacing is
indicated in the rail force and bracket detail table on the Otis layout. Any rail bracket mounting surfaces that are
not in line with the finished hoistway dimension (i.e. the clear hoistway line) may need to be extended to meet the
required distance. Otis agrees to provide guidance on this matter at the appropriate time.
If rail bracket embedded plates or inserts are provided by Otis, they shall be installed by others in accordance with
Otis’ documentation and instruction.
If vertical tube steel is utilized as rail support, (2) vertical tubes spaced at 20.4” (518 mm) on center are required
for car rail brackets with “A” dimension ≥ 5.76” (146 mm). For Machine Space applications, horizontal rail bracket
supports must be provided. Note: Vertical supports will interfere with the machine space access door.
The rough openings, per sizes shown on the Otis layout, are required. Prior to the completion and turnover of the
elevator(s), all entrance walls must be installed and rough openings filled in complete to maintain fire rated
hoistway requirements.
12. Provide adequate support at all fastening points of each entrance. Provide plumb vertical surfaces for entrances
and sill supports, one above the other, and square with the hoistway. For 4’-0” (1219 mm) and 4’-6” (1372 mm)
two speed door arrangements, an additional hoistway attachment point is required for an auxiliary support bracket
under the sill assembly in the center of the clear door opening. Finish floor and grout, if required, between door
frames to sill line. A horizontal support is to be provided 1 foot (305 mm) above the clear opening at the top
landing to support the door frame assembly. If floor heights exceed 12’-0” (3658 mm), a horizontal support is to
be provided 1 foot (305 mm) above the clear opening. If transoms are required, the support would be 1 foot (305
mm) above the transom height.
13. Provide and install a steel safety beam per elevator, from side wall to side wall at the top of the hoistway, capable
of withstanding a maximum net live load of 5000 lb. (2268 kg). Otis requires 2” (51 mm) clear above the beam.
Beam must be removed before car is placed in operation if it infringes on required clearance.
14. Glass used in hoistway construction must block 98% or more of incident full spectrum ultraviolet radiation for the
full height of the hoistway.
15. If an emergency door in a blind hoistway is required, provide an outward swinging single section type door with
door closer and a self closing barrier per ASME A17.1-2007, section 2.11.1.2. Contact your local Otis personnel
for a detailed drawing (AAA26900D_FMI), showing Otis specific requirements.
Electrical Requirements
25. All 125 volt, 15 or 20 ampere single phase receptacles installed in pits, machinery spaces, and elevator car tops
shall be of ground fault circuit interrupter (GCFI) type. All 125 volt, 15 or 20 ampere single phase receptacles
installed in machine rooms / machine spaces shall have GFCI protection. A dedicated single phase receptacle
supplying a permanently installed pit sump pump shall not require GFCI protection. (NEC 620-85 or CEC Rule 38-
085).
26. Furnish a dedicated, balanced, 3 phase, 3 wire electrical feeder system with a separate solidly grounded
equipment grounding conductor terminating in the machine room / machine space. Size of the feeders and
grounding conductor to suit elevator power characteristics. Feeder conductors and grounding conductor must be
copper. A fused disconnect switch or circuit breaker capable of being locked in the open position for each elevator
per the National Electrical Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1) with feeder or branch
wiring to the controller (NEC 620-51, 620-61(D), and 620-62 or CEC Rule 38-013(2)(a)) must be provided. Fuses
are to be current limiting class RK1 or equivalent. Circuit breakers are to have current limiting characteristics
equivalent to class RK1 fuses. Fuses or circuit breakers are to be time delay to cover the full load up accelerating
current as listed in the Otis Confirmation of Power Supply form.
[Note: If the 3 phase power to the control system is simulated (not from the utility), by use of a phase
converter system, the phase converter must have all three phases balanced. Digital phase converter is
required.]
Furnish a separate 120 volt, 15 ampere single phase branch circuit and SPST fused disconnect switch or circuit
breaker capable of being locked in the open position to supply the car lights, receptacles, auxiliary lighting power
source, and ventilation on each car in compliance with the National Electrical Code must be provided.
When a machine room is used and where practical, disconnects shall be located adjacent to the door of the
machine room enclosure. When a machine space is used, disconnects or circuit breakers shall be located behind
the door of the machine space per Otis layout.
Branch circuit wiring to each controller (NEC 620-53 or CEC Rule 38-053) must be provided.
For machine room applications, a convenience outlet and a suitable light, of not less than 200 Lux (19FC) as
measured at floor level must be provided in the machine room with a light switch located within 18” (456 mm) of
lock jamb side of machine room door.
For machine space applications a convenience outlet located inside the machine space door and a suitable light
located outside the machine space door on the lock jamb side, of not less than 200 Lux (19FC) as measured at
A convenience outlet and light fixture of not less than 100 Lux (10FC) as measured at the pit floor level must be in
the pit with a light switch located adjacent to the pit access door (NEC 620-24 or CEC Rule 38-024). The light
bulb(s) shall be externally guarded to prevent contact and accidental breakage.
[Note: Consult with the Otis Construction Superintendent at your location concerning the following
paragraph.]
To meet the date upon which the elevators are to be turned over, the permanent 3 phase feeder system and
protective devices must be installed and power available prior to the start of elevator installation.
27. Provide 120 volt, 20 ampere power for light, tools, hoist, etc. to the hoistway during installation. Source must be
within 75 feet (22.86 M) of the hoistway.
28. Provide one (1) dedicated outside telephone line per elevator car to the elevator machine room / machine
space(s), and terminated at the controller designated by the Otis construction superintendent. Reference the
A17.1 / CSA-B44 code and the Otis Confirmation of Power Supply for specific requirements.
29. [Optional for Elevators with an intra building Intercom] Provide a separate 120 volt, 15 ampere, single phase
power supply with fused SPST disconnect switch or circuit breaker located as required for intercommunicating
system power supply. Circuit to be arranged for feeding from the building emergency lighting supply if provided.
Conduit and wiring for remotely located intercommunicating stations must be provided.
30. [Optional for Elevators with a Battery Powered Emergency Return Unit (ERU)] Provide the disconnecting
means required by the National Electrical Code (NEC) or Canadian Electrical Code (CEC) with an auxiliary
contact and wiring to the controller. The auxiliary contact is to be positively open when the main disconnecting
means is open. The auxiliary contact shall cause the ERU power source to be disconnected from its load when
the disconnecting means is in the open position. Size of main contacts to suit elevator power characteristics.
[Additional ERU Requirement]
In the United States, heat sensors used to automatically disconnect the mainline power supply prior to the
application of water from sprinklers shall be provided with a normally closed contact with wiring from the sensing
device to a controller designated by Otis. The normally closed contact shall be closed when the heat sensor is
not activated and shall be open when the heat sensor is activated.
31. [Optional for Installations with Emergency (Standby) Power] Provide the emergency (standby) power unit
and means for starting it, and deliver to the elevator via disconnect switches in the machine room / machine
space, sufficient power to operate one or more elevators at a time at full rated speed and rated load.
An automatic Power Transfer Switch is required for each power feeder to monitor both Normal and Emergency
(Standby) Power conditions and to perform the transfer from one to the other. Switch to have two sets of normally
closed dry contacts, one to be open when the switch is in the Emergency (Standby) Power position, the other to
open upon initiation of power transfer and to close when transfer is complete. Switch to have an inhibit function
which will delay transfer to Normal and / or Emergency (Standby) Power by an adjustable period of 0 - 300
seconds. Switch shall have a Phase Monitor feature, which prohibits the transfer of power between "live" sources
unless the sources are in phase with each other. If a Shunt Trip device is provided, an additional Normally
Closed contact is required from the Emergency (Standby) Power source.
Emergency (standby) power system shall be connected to the 125 volt power circuit as noted in A.3 of the
Confirmation of Power Supply for the branch circuit supplying the car lights, car top receptacle, auxiliary car
lighting power source and car ventilation.
You agree to indemnify and save Otis harmless against any and all liability and costs arising out of your failure to carry out
any of the foregoing requirements.
Per out agreement, it is Otis’ responsibility to arrange for this inspection and to pay the required fee. We ask you to ensure that all “work by others”
has been completed prior to our agreed-upon date for inspection.
If the elevator installation does not pass inspection due to uncompleted work by others, we would expect all additional costs associated
with a re-inspection to be the responsibility of others. The total charge for the re-inspection will be a minimum of $ 500.00.
_______________________________________________ _______________________________________________
Form Prepared By / Date General Contractor / Date
General
.
Tank and
controller
(close to MRL door Hoistway
location or in Machine
Room)
Tools
Platform
Rail
brackets
Structural cab panels
C R
Piping kit
Y A
Entrances
L I
I L
Oil N S
D Raceway
E
R
S TC and Cab finishes
hoistway
wiring kits
Provide suitable on-site storage area for all elevator equipment, with rollable access to the elevator
hoistway at ground level or uninterrupted use of a forklift or crane with supplied operator. A suitable
storage area is defined as follows: Dry and enclosed under a dried in-building structure, is within 100
ft. of the hoistway, is larger than 25 x 20 feet per elevator.
We require suitable tractor-trailer access to the building for unloading of material. In addition, we
need rollable access from unloading point to and from storage, and storage to hoistway area.
1
Hoistway and Pit
Hoistway Requirements
100”
5”
95”
Effective hoistway
dimension when the
hoistway is not
plumb
NOTE:
2
Rail Bracket Attachment Points
3
Rail bracket support provided by tube steel sections (see detail next page for larger brackets).
5
Tube Steel requirements for rail bracket mounting
30” (762mm)
1/2” (12.7mm) Thick Plate
(Not by Otis)
17” (432mm)
6” (152mm)
2” (51mm)
28-7/8” (733mm)
Passenger Arrangements
30” (762mm)
15” (381mm)
15” (381mm)
1/2” (12.7mm) Thick Plate
(Not by Otis)
6” (152mm)
X” (see table)
X” Dimension
Opening 4500lb 5000lb 5000AIA
Arrangement duty duty duty
65-3/8” 68” 71-5/8”
Front only
(1661mm) (1727mm) (1819mm)
Hospital Arrangements
6
Pit Requirements
Furnish a dry pit reinforced to sustain vertical forces on car rails and impact loads on cylinder
head(s) and buffer(s). The pit must be dry and clean. The elevator pit may not have a floor
drain/sump pump connected directly to a storm drain or sewer. Otis recommends that the owner
verify the system complies with all applicable laws. See “Preparatory Work by Others”, for more
information.
Typical pit
ladder
Pit light and GFCI convenience outlet (with cover and guard) mounted 12" off pit floor on rear wall and
switch to be located adjacent to pit ladder piped in accordance with local code. If front and rear
opening contact Otis representative for location.
Metal pit ladder is to extend from the pit floor upward, not less than 48” above the bottom landing floor
level, per Otis shop drawings and/or Otis instructions.
7
Hoistway Overhead Beam
Provide and install a safety beam capable of withstanding a maximum net live load of 5000 lb.
(2268 kg). Otis requires 2” clear above the beam. Beam must be removed before car is placed in
operation if it infringes on required clearance.
8
Hoistway Barricades
9
Hoistway Entrance Support
The hoistway walls are to include adequate fastening for hoistway entrance assemblies. One front
entrance wall, at the main landing, is not to be constructed until after all elevator material is located in
the hoistway. Remaining front entrance walls are not to be constructed until after door frames and
sills are in place. If front walls are poured concrete weight bearing walls, rough openings are to be
provided to accept entrance frames and filled in after frames are set. Rough opening size per Otis
layouts.
Provide plumb vertical surfaces for entrance-sill supports, one above the other, and square with the
hoistway. For 4’-0” (1220 mm) and 4’-6” (1372 mm) two-speed door arrangements on 4500 lb.
(2041 kg) and 5000 lb. (2270 kg) cars a hoistway attachment point is required for an auxiliary support
bracket under the sill assembly in the center of the clear door opening. Finished floor and grout, if
required, between doorframes to sill line.
A horizontal support is to be provided 12” (305 mm) above the clear opening at each landing to
support the doorframe assembly.
10
Hoistway Ledges (Bevels) and Patching
Hoistway walls shall be flush on hoistway sides. Any ledges over 4” shall be provided with a beveled
angle of not less than 75º.
Spaces containing machines, control equipment, sheaves and other machinery shall be enclosed with
fire-resistive enclosures. Enclosures and access doors thereto shall have a fire-resistance rating at
least equal to that required for the hoistway enclosure.
Furnish hoistway walls designed and constructed in accordance with the required fire rating (including
those places where elevator fixture boxes and rail-bracket fastenings penetrate the hoistway walls).
11
Door frames to be sealed to meet code. Patch any holes in the elevator hoistway and machine room.
Grout under and in front all sills. Top of hoistway and machine room shall have a fire rating in
accordance with local elevator codes.
Hoistway Venting
Provide hoistway ventilation in accordance with all applicable codes and regulations.
12
Machine Space & MRL Access Door
Spring hinges
on door
elevator
controller
Blank plate on
cabinet hoistway side
door of door
valve sound
isolation box and
cover panels
Provide a rough opening for and install a 3’ X 7’ standard fire rated interior door (referred to as
machine space door) on one side of the hoistway, as shown on the Otis layout. When determining the
location of the machine space door,the dimension on the Otis layout is from the inside door edge of
the jamb and not the door stop edge. Please be advised that this door location is very critical. Follow
door manufacturing instructions for the different types of hoistway wall material and make the
appropriate adjustments so that this door will be placed in the proper location.
The 3’ x 7’ machine space door must be a self closing and self locking metal door with a group 2
locking device in the hoistway per Otis layout. In addition, ensure that all air gaps around the
machine space door are sealed (i.e. threshold, weather stripping, etc.). Self closing mechanism
cannot protrude into the machine space at any time. The machine space door knob shall have a
blank plate on the hoistway side of the door.
The door frame must be securely mounted to the wall to sustain a cantilevered / horizontal force
exerted by the electrical disconnect(s), electrical conduit, and wiring up to an approximate 150 lb.
load. Install per Machine Room / Machine Space Prep / Work and Electrical Requirements. The door
should be able to open fully (180°).
The machine space will be in the hoistway behind the metal door installed per Hoistway and Pit Prep /
Work above with ventilation in accordance with all applicable codes and regulations. The machine
space is to be maintained at a temperature between 32°F (0°C) and 104°F (40°C). Relative humidity
not to exceed 95% non-condensing. Local codes may require tighter temperature ranges. The
temperature and humidity range shall be permanently posted in the machine room / machine space.
Please check with your local code authority for the exact requirements in your area.
13
For machine space applications a GFCI convenience outlet located inside the machine space door
and a suitable light located outside the machine space door on the lock jamb side, of not less than
200 Lux (19FC) as measured at floor level must be provided per Otis layout. The machine space light
circuit shall be a dedicated circuit separate from other lighting circuits. (NEC 620-23 or CEC Rule 38-
023)
Provide a Class “ABC” fire extinguisher, minimum 10 lbs., in a location convenient to the machine
space.
14
Machine Room
Provide a suitable dry machine room with access and ventilation in accordance with all applicable
codes and regulations. The machine room is to be maintained at a temperature between 60°F and
100°F, with relative humidity is not to exceed 95% non-condensing. Local codes may require tighter
temperature ranges. Please check with your local code authority for the exact requirements in your
area.
Only elevator equipment is allowed in an elevator machine room and hoistway (no access panels). If
a sprinkler system is required contact local code authority.
Machine room doors - shall be self-closing and self-locking and rated per machine room construction.
Furnish a 3-phase, electrical feeder system with a separate equipment grounding conductor
terminating in the machine room. Size of the feeders and grounding conductor to suit elevator power
characteristics. A fused disconnect switch or circuit breaker capable of being locked in the open
position, for each elevator per the National Electrical Code (ANSI/NFPA 70) with feeder or branch
wiring to controller (NEC 620-51) must be provided. Where practical, disconnects shall be located
adjacent to the door of the machine room enclosure. Switch must be in sight of elevator machine and
shall be the type that cannot be engaged with door open.
15
Disconnect should be equipped with a microswitch when ERU units are being furnished. (NEC
620.91-C) Examples of ERU auxiliary contacts - Square D - #EK300-2, I.T.E. - SC-3, West. Elec. -
EK-1
A separate 120-volt AC, 15-ampere single-phase branch circuit and SPST fused disconnect switch or
circuit breaker, arranged to be locked in the open position, to supply the car lights, receptacles,
auxiliary lighting power source and ventilation on each car in compliance with the National Electrical
Code must be provided. Suitable light and GFCI convenience outlets must be provided in machine
room with light switches located within 18” (456 mm) of lock jamb side of machine room door.
Electric power for light, tools, hoist, etc.; must be provided during installation as well as electric
current for starting, testing and adjusting the elevator.
Telephone in elevator cab connected to a 24-hour maintained location. (It should be wired and, upon
entry into the machine room, piped to the elevator controller).
16
Electrical Requirements
Confirmation of Power Supply-Hydraulic Approval
Customer: OTIS ELEVATOR COMPANY
Project: Contact:
Phone:
NOTE: Manufacture will not be started until the owner or the owner's representative signs and returns this form to Otis Elevator
Company. This form must be completed, signed and returned by _____ to meet the scheduled completion date of _ _ ___ .
A. POWER CONFIRMATION
Our records indicate the supply to be as indicated below. You are requested to verify (or correct) this information and confirm its
accuracy by your signature in the space provided. Should a change in the information provided subsequently occur, immediate
notification of the change is necessary.
1. Dedicated ______ volts, balanced utility three phase, three wire, 60 hertz and a separate solidly grounded equipment
grounding conductor.
Note: If three phase power is simulated by use of a phase converter, a digital phase converter must be used.
Please consult Otis Representative in your location.
2. Voltage variations to be within 10% of normal. Frequency variations to be within 2 hertz. If voltage or frequency
variation exceeds these limits, please give details.
3. Car Lighting: 125 volt, single phase, 15 ampere, 60 Hertz dedicated branch circuit.
The above power supply characteristics are confirmed.
SIGNED BY: __________________________________ DATE: ________________
B. ELECTRICAL REQUIREMENTS (SEE ANSI/NFPA 70)
To assist you in the planning of the electrical
This formrequirements
is in thetoApproval
be provided bypackage
other trades prior
andto provides
the installation of our equipment,
we are pleased to supply the AC current data as detailed below. The following data are based upon the power supply as noted above.
Should your confirmed powerthe supply information that thethan
be of a different characteristic (sub)contractor willrevised
that shown, please request need datatofrom your local Otis
representative. Additional electrical requirements are listed on the next page.
meet the elevator requirements.
The AC line current data below are based on the power supply information provided in Part A, item 1, above.
REFER TO ANSI/NFPA 70, SECTION 620-13
(For Code Versions Prior to 1996 Refer to Section 620-14)
NAMEPLATE
ELEVATOR ELEVATOR RATED PEAK STARTING OR
NAME OR CONTRACT CAR HORSE NEC MOTOR ACCELERATING
NUMBER NUMBER(S) DUTY SPEED POWER LETTER CURRENT CURRENT
Elevator controller terminations for 3 phase wiring are rated for 75 C. Refer to NEC ANSI/NFPA70 Section 110-14.
Elevators supplied to this document are rated at 10,000 Amps RMS Symmetrical Short Circuit Current (SCCR.)
Elevator Feeder Short Circuit protection by others shall limit the Available Short Circuit Current (ASCC) in the machine room / space to 10,000
Amps maximum symmetrical RMS.
To assist you in providing proper electric service, the items required BY OTHERS have been checked below:
X A three (3) phase, electrical feeder system must be enclosed in EMT with a separate equipment grounding conductor
terminating in the machine room / space. Feeder conductors and grounding conductor must be copper. Size of the feeders and
grounding conductor to suit elevator power characteristics. A fused disconnect switch or circuit breaker (not acceptable in all areas),
capable of being locked in the “off” position, for each elevator per the National Electrical Code (ANSI/NFPA 70) with feeder or
branch wiring to controller [620-51] and [620-61(D)]. Fuses are to be current limiting class RK1 or equivalent, see section B for
elevator equipment SCCR. Circuit breakers are to have current limiting characteristics equivalent to class RK1 fuses, see section B
for elevator equipment SCCR. Fuses or circuit breakers are to be time delay to cover the full load up accelerating current as listed in
Section B above. [Note: If the 3 phase power to the control system is simulated (not from the utility), by use of a phase converter
system, the phase converter must have all three phases balanced. Digital phase converter is required.]
A separate 125 volt AC, 15 ampere single phase branch circuit and SPST fused disconnect switch or circuit breaker, capable of
being locked in the “off” position, to supply the car lights, receptacles, auxiliary lighting power source and ventilation on each car
in compliance with the National Electrical Code. [620-53]
The disconnecting means shall be located adjacent to the door of the machine room enclosure or behind the door of the machine
space on an Otis supplied metal shroud per Otis layout.
Provide branch circuit wiring to each controller.
For machine room applications, a convenience outlet and a suitable light, of not less than 200 Lux (19FC) as measured at floor level
must be provided in the machine room with a light switch located within 18” (456 mm) of lock jamb side of machine room door.
This
For machine space applications form isoutlet
a convenience in the Approval
located package
inside the machine space doorandand aprovides
suitable light located outside the
machine space door on thethe
lock jamb side, of not less than 200 Lux (19FC)
information that the (sub)contractor will needas measured at floor level must betoprovided per Otis
layout. The machine space light circuit shall be a dedicated circuit separate from other lighting circuits. (NEC 620-23 or CEC Rule
38-023) meet the elevator requirements.
A convenience outlet and light fixture in the pit with switch located adjacent to the pit access door. [620-24]
Provide 125 volt AC, 20 ampere electric power for light, tools, hoist, etc. during installation.
X Refer to National Electrical Code, Article 430-52 “Exceptions” to select applicable ratings for protective devices. This exception
should be fully utilized in order to provide the maximum capacities listed for the various type protective devices.
Note: The building Emergency (Standby Power) Generator system used to supply the elevator(s) shall be capable of supplying
non-linear loads.
When more than one elevator is subject to the same standby power system and the standby power system is not large enough to
run all elevators at once, the transfer switch must include one set of normally closed dry contacts that open when the switch is in
the standby power position.
COMMUNICATION REQUIREMENTS
Separate 125 volt, 15 ampere single phase power supply with fused SPST disconnect switch or circuit breaker with duplex outlet
located as required for inter-communicating system power supply. Circuit to be arranged for feeding from the building standby or
emergency lighting supply if provided. Conduit and wiring for remotely located inter-communicating stations (in Engineer’s
office, etc.).
X One (1) dedicated outside “Analog” (i.e. capable of carrying voice and data) telephone line to the elevator machine room / space
must be furnished. The telephone line must meet the following requirements:
Loop Current: Min 20mA, Max 120mA Nominal AC Line Impedance = 600 ohms
Line Voltage: On Hook – MinThis
15Vdc,form is in the Approval
Max 56.5Vdc Ringpackage
Voltage: Min and provides
40Vac(rms), Max 150Vac(rms)
Off Hook – Min 8.75Vdc Ring Frequency: 15-68Hz
the information that the (sub)contractor will need to
meet the elevator requirements.
SMOKE DETECTORS
Smoke detectors, located as required, with wiring from the sensing devices to the controller(s) designated by Otis.
X I. For each group of elevators, provide a normally closed contact representing the smoke detector at the designated return
landing.
X II. For each group of elevators, provide a normally closed contact representing all smoke detectors located in lobbies, hoistways,
or machine rooms/machine space, but not the smoke detector at the designated return landing (see above) or the smoke detectors
as described in a & b below:
a) If a smoke detector is located in the hoistway at or below the lower of the two recall landings, it shall be wired to activate the
same normally closed contact as the smoke detector located in the lobby at the lower of the two recall landings.
b) If the machine rooms/machine space is located at the designated return landing, the smoke detectors located therein shall be
wired to activate the same normally closed contact as the smoke detector at the designated landing.
III a. For a single unit, or group of elevators having one common hoistway, or one common machine room and one common
hoistway, provide one additional normally closed contact representing the hoistway smoke detectors.
III b. If the group contains more than one hoistway, and hoistway smoke detectors are installed, or if the group has more than
one machine room, provide one normally closed contact for each elevator. The contact is to represent the smoke detector in the
machine room for that particular elevator, and / or hoistway containing that particular elevator.
Confirmation of Power Supply - Hydraulic Approval
TOTAL BTUs
SA Pwsuphyd.doc REV 03/16/2012
CN281791
Elevator controller terminations for 3 phase wiring are rated for 75 C. Refer to C.E.C. – C22.1
Elevators supplied to this document are rated at 10,000 Amps RMS Symmetrical Short Circuit Current (SCCR.)
Elevator Feeder Short Circuit protection provided by others shall limit the Available Short Circuit Current (ASCC) in the machine room / space to
10,000 Amps maximum symmetrical RMS.
X A three (3) phase, electrical feeder system must be enclosed in EMT with a separate equipment grounding conductor
terminating in the machine room / space. Size of the feeders and grounding conductor to suit elevator power characteristics. Feeder
conductors and grounding conductor must be copper. A fused disconnect switch or circuit breaker, capable of being locked in the
“off” position, for each elevator per the Canadian Electrical Code (C22.1) with feeder or branch wiring to controller CEC [Rule 38-
013(2)(a)]. Fuses are to be current limiting class RK1 or equivalent, see section B for elevator equipment SCCR. Circuit breakers are
to have current limiting characteristics equivalent to class RK1 fuses, see section B for elevator equipment SCCR. Fuses or circuit
breakers are to be time delay to cover the full load up accelerating current as listed in Section B above. [Note: If the 3 phase power to
the control system is simulated (not from the utility), by use of a phase converter system, the phase converter must have all three
phases balanced. Digital phase converter is required.]
A separate 125 volt AC, 15 ampere single phase branch circuit and SPST fused disconnect switch or circuit breaker, capable of being
locked in the “off” position, to supply the car lights, receptacles, auxiliary lighting power source and ventilation on each car in
compliance with the Canadian Electrical Code [Rule 38-053].
The disconnecting means shall be located adjacent to the door of the machine room enclosure or behind the door of the machine space
on an Otis supplied metal shroud per Otis layout.
Provide branch circuit wiring to each controller CEC [Rule 38-013(2)(a)].
For machine room applications, a convenience outlet and a suitable light, of not less than 200 Lux (19FC) as measured at floor level
must be provided in the machine room with a light switch located within 18” (456 mm) of lock jamb side of machine room door.
For machine space applications a convenience outlet located inside the machine space door and a suitable light located outside the
machine space door on the lock jamb side, of not less than 200 Lux (19FC) as measured at floor level must be provided per Otis
layout. The machine space light circuit shall be a dedicated circuit separate from other lighting circuits. (NEC 620-23 or CEC Rule
38-023)
A convenience outlet and light fixture in pit with switch located adjacent to the pit access door CEC [Rule 38-054].
Provide 125 volt AC, 20 ampere electric power for light, tools, hoist, etc. during installation.
This form is in the Approval package and provides
EMERGENCY RETURN UNIT the information that the (sub)contractor will need to
___ The disconnecting means required by the Canadian Electrical
meet theCode shall be provided
elevator with an auxiliary contact with wiring to the
requirements.
controller. The auxiliary contact is to be positively open when the main disconnecting means is open. The auxiliary contact shall
cause the ERU power source to be disconnected from its load when the disconnecting means is in the open position. Size of main
contacts to suit elevator power characteristics.
SMOKE DETECTORS
Smoke detectors, provided either voluntarily or when required by the National Building Code of Canada [subsection 3.2.6],
located as required, with wiring from the sensing devices to the controller(s) designated by Otis.
I. For each group of elevators, provide a normally closed contact representing the smoke detector at the designated return
landing.
II. For each group of elevators, provide a normally closed contact representing all smoke detectors located in lobbies, hoistways,
or machine rooms/machine space, but not the smoke detector at the designated return landing (see above) or the smoke detectors
as described in a below:
a) If a smoke detector is located in the hoistway at or below the lower of the two recall landings, it shall be wired to activate the
same normally closed contact as the smoke detector located in the lobby at the lower of the two recall landings.
b) If machine rooms/machine space is located at the designated return landing, the smoke detectors located therein shall be wired
to activate the same normally closed contact as the smoke detector at the designated landing.
III a. For a single unit, or group of elevators having one common hoistway, or one common machine room and one common
hoistway, provide one additional normally closed contact representing all the hoistway smoke detectors.
III b. If the group contains more than one hoistway and hoistway smoke detectors are installed, or if the group has more than one
machine room, provide one normally closed contact for each elevator. The contact is to represent the smoke detector in the machine
This
room for that particular elevator, and / or form
hoistway is inthat
containing the Approval
particular elevator. package and provides
TOTAL BTUs
SA Pwhydcsa.doc REV 03/16/2012
CN281791
Common Inspection
Violations
Common Inspection Violations
Before the elevator(s) can be complete and ready for inspection by the state or local
inspector, all requirements of the ASME/ANSI A.17.1 Elevator Code and local code
requirements must be met. This includes completion of work that must be performed
by other trades. Per our agreement, it is Otis’ responsibility to arrange for this
inspection. We ask you to ensure that all “work by others” has been completed prior to
our agreed upon date for inspection. Note - If the elevator installation does not
pass inspection due to uncompleted work by others, then all additional costs
associated with a re-inspection will not be the responsibility of Otis.
Below is a list of common inspection violations. A review of these items along with the
Pre-Inspection Checklist is recommended prior to the inspection process to allow for
any necessary corrective action.
Elevator Pits
□ Elevator pits shall be waterproof and designed to provide a dry pit area.
Standing water in the pit area is considered a major violation of Code. Note - A
sump pump cannot be used alone to meet the requirements of providing a
dry pit area. Proper waterproofing is required.
□ Drain holes connected to the building sanitary sewer are not allowed in the
elevator pit under any circumstances.
□ Sump pumps must be set into the pit floor and a metal cover provided to cover
the entire sump hole level with the pit floor. It must drain to approved area or oil
separator device, not a sanitary sewer. The purpose of the sump pump is to
remove casual water from the pit. Note - Check with local code authorities
for specific local requirements .
□ Any pit more than 3’-0” deep shall be provided with a non-combustible access
ladder.
1
Elevator Hoistways
□ Hoistways serving more than two (2) floors shall be provided with means for
venting smoke and hot gases directly to the outer air or through non-combustible
ducts to the outer air in case of fire. Vents shall be located in the side of the
hoistway directly below the roof or directly over the hoistway. The clear open
area of the vents shall be not less than three and one-half (3 ½) percent of the
area of the hoistway, and in no case less than three (3) square feet for each
hoistway, whichever is greater. Note - More stringent local building codes will
take precedence over elevator code requirements. Special attention is
required for hoistway ventilation exposed to weather. Vents shall have an insect
screen to prevent the entry of birds, insects, etc.
□ Hoistway enclosures shall have substantially flush surfaces. Beams, floor, slabs,
or other building construction shall not project more than two (4) inches inside the
general line of the hoistway unless the top and bottom of the projection is beveled
at the angle of not less than 75° degrees with the horizontal. Where setbacks
occur, the top of the setback shall be beveled at the same angle. Setbacks or
recesses at the hoistway vent are included under this requirement. This
requirement does not apply to divider beam(s) between elevators.
□ Drywall construction, if used, shall be a tested assembly approved for the use it is
being applied to (partition wall or floor-ceiling assembly). Only non-combustible
systems are approved. Penetrations in the dry wall assembly for elevator fixtures
are required, and the responsibility for maintaining the fire rating of the dry wall
system at these points is borne by the system installer. Note - More stringent
local building codes will take precedence over elevator code in regard to the
fire rating of elevator hoistways.
□ Hoistway door entrance frames and headers shall be grouted solid to maintain fire
ratings of the hoistway.
□ All voids, holes, slots, etc., in the hoistway shall be grouted or pointed up to
maintain fire rating of the hoistway.
□ All nails, snap-ties, form straps, and wood shall be removed from the hoistway.
□ Only equipment required for the operation of the elevator is permitted inside the
elevator hoistway.
□ Landing areas for all floors and elevator lobbies shall be completed prior to the
inspection.
2
Elevator Machine Rooms
□ Only machinery and equipment required for the operation of the elevator shall be
permitted in the elevator machine room. Pipes or ducts conveying gases, vapors,
or liquid or electrical equipment, wiring, piping and controls not used for the
operation of the elevator are prohibited in the elevator machine room.
□ The elevator machine room shall be free of refuse and shall not be used for
storage of any materials not related to the elevator equipment.
□ Machine room doors shall have fire rating with labels. Doors shall be self-closing
and self-locking. Minimum height of the door is 6’-0”. Minimum width of the door
is 30”. The door lock shall be of the type that can be opened from the inside
without a key. However, a key is required to open the door from the outside at all
times. Push-button type locks are not allowed in the machine room door.
□ Machine rooms shall have a minimum of seven (7) feet clear headroom under all
obstructions (including hoist beam, light fixtures, etc.).
□ Special attention is required for machine room ventilation and machine room
doors when exposed to the weather. Extra precautions must be taken to prevent
entry of blowing rain.
□ Adequate lighting shall be provided in the elevator machine room to provide not
less than ten 19 foot-candles at all areas of the floor level. The light switch shall
be located within 18”on the lock-jamb side of the access door.
□ A GFCI type duplex receptacle shall be provided in the elevator machine room.
□ All voids, holes, slots, etc., in the machine room shall be grouted or pointed up to
maintain the fire rating. All nails, snap-ties, form straps, and wood shall be
removed from the machine room walls, floor, and ceiling.
□ A lockable fused disconnect switch in machine room with feeder wires to elevator
controller, all piped in accordance with N.E.C. or C.E.C. (Canadian Electrical
Code), and grounded. Switch must be in sight of elevator machine and shall be
the type that cannot be engaged with door open. Disconnect should be equipped
with a microswitch when ERU units are being furnished. (2.26.4) (NEC 620.91-C)
Examples of ERU auxiliary contacts - Square D - #EK300-2, I.T.E. - SC-3, West.
Elec. - EK-1
3
□ Lockable 120V disconnects per power confirmation for cab lighting circuit.
Car Enclosures
□ Finish flooring (whether carpet or tile) must be installed prior to final inspection. A
non-slip surface is required. Make sure that final elevator cab drawings are
reviewed to obtain the finish floor thickness dimension for which the elevator cab
was constructed.
□ Carpet used on elevator car floors must be securely attached to the car platform,
have a tight weave and low pile, be installed without padding, and conform to the
following requirements of ASTM E 84, UL 723, NFPA 252 or CAN/ULC-S102.2,
whichever is applicable:
(a) flame spread rating of 0 to 75
(b) smoke development of 0 to 450
General
□ Buildings having emergency power systems and elevators, which will be powered
by this generator, shall have the generator operable at the time of the final
inspection.
□ Fire Safety system must be installed and in working order prior to final inspection.
Smoke detectors may be required in each elevator lobby, hoistway, and machine
room. Check with local code authority. (2.27.3.2) Furnish normally closed fire
system contacts to the elevator controller as per power confirmation.
4
Local
Requirements/Options