UPS Setting Tool

User Version

Version: XX1009AS

1
Table of Contents

Type A Setting Tool For English Language: ...............................................................3


Type A Setting Tool For Chinese Language: ..............................................................5
Type B Setting Tool For English Language:...............................................................7
Type B Setting Tool For Chinese Language: ............................................................10

2
Type A Setting Tool For English Language:

Fig. 1
1 Select the output voltage of the UPS for display : 110Vac or 220Vac system
2 Select the output voltage of the UPS: 200V、208V、220V、230V、240V.
3 Select the working mode of the UPS:
3.1 Normal mode:The UPS is working under “On-line” mode.
3.2 ECO mode:The UPS is working under “Economic” mode.
3.3 CF50:The UPS is working under 50Hz Frequency Converter mode.
3.4 CF60:The UPS is working under 60Hz Frequency Converter mode.
4 Default value is 20pcs. Please use the default value.
5 UPS ID Numbers: 1~4. If the UPS is running as a standard alone UPS, please
set it as ID=1.
6 Enable/Disable the Parallel Mode
6.1 Disable: set as 1.
6.2 Enable: set as 2
7 Output Voltage Micro Tuning: 0%, +1%, +2%, +3% or -1%, -2%, -3% according
the output voltage set at Step 2.
8 Bypass Sensitivity Window:
8.1 Sensitivity Low:184V~260V
8.2 Sensitivity High:195V~260V
9 Synchronization:
9.1 3Hz means the window of the output frequency is at +/- 3Hz
9.2 1Hz means the window of the output frequency is at +/- 1Hz
10 To indicate the firmware of the UPS.
11 To indicate the name of the company provided or manufactured the UPS
12 To indicate the type of the UPS offered
13 To indicate the capacity of the UPS

3
14 To indicate the setting of the special functions of the UPS.
15 Write: Write those new configurations to the UPS via RS232 port.
16 To read the settings of the UPS and update the content of the Fig. 1 automatically.
17 Com Port: To set the Com port from 1 to 10.
18 Com not open or Serial Port Open: It shows whether the setting tool finds RS232
port or not.
19 Connected or Not connected: To show if the connection between the setting tool
and the UPS is successful or not.
20 Baud Rate Selection:2400bps、4800bps、9600bps.

4
Type A Setting Tool For Chinese Language:

Fig. 1
1 設定 UPS 的輸出電壓顯示內容為 110Vac or 220Vac 系統。
2 設定 UPS 的輸出電壓:200V、208V、220V、230V、240V。
3 設定 UPS 的工作模式:
3.1 Normal mode:On-line UPS 的工作模式。
3.2 ECO mode:經濟工作模式。
3.3 CF50:Frequency Converter 模式,UPS 定頻 50Hz 輸出。
3.4 CF60:Frequency Converter 模式,UPS 定頻 60Hz 輸出。
4 電池顆數設定:目前機種只有 20 顆機種,請使用者用預設值即可。
5 並聯時設定 UPS 的辨認 ID,ID=1~4,單機一律 ID=1。
6 並聯模示的開啟或關閉。
6.1 關閉請設為1
6.2 開啓請設為 2
7 UPS 會依項次 2 所設定的結果,將輸出電壓往上調整 0%、1%、2%、3%或
往下調整 1%、2%、3%。
8 設定旁路電壓破窗的範圍
8.1 Sensitivity Low:旁路電壓破窗的範圍為 184V~260V。
8.2 Sensitivity High:旁路電壓破窗的範圍為 195V~260V。
9 設定 UPS 輸出頻率範圍
9.1 3Hz:UPS 輸出頻率範圍為+/- 3Hz
9.2 1Hz:UPS 輸出頻率範圍為+/- 1Hz
10 顯示 UPS 的程式碼版本。
11 顯示 UPS 設定的公司名稱。
12 顯示 UPS 設定的型式名稱。
13 顯示 UPS 的容量。

5
14 顯示目前 UPS 之特殊功能碼的設定值。
15 將所設定的設定值利用 RS232 傳送至 UPS。
16 讀取 UPS 的設定值,並會自動更新應用程式畫面 Fig.1 之內容。
17 設定電腦 RS232 的通訊埠,可設定的範圍為 1~10。
18 顯示本軟體是否有偵測到實體的 RS232 通訊埠,Com not open 或 Serial port
open。
19 顯示本軟體是否與 UPS 通訊成功,No Connect 或 Connect。
20 鮑率選擇:2400bps、4800bps、9600bps。

6
Type B Setting Tool For English Language:

Fig. 2
1 Select the output voltage system of the UPS : 110Vac or 220Vac system
2 Select the output voltage of the UPS: 200V、208V、220V、230V、240V or 100V、
110V、115V、120V、127V。
3 Select the working mode of the UPS:
3.1 Normal mode:The UPS is working under “On-line” mode.
3.2 CF50:The UPS is working under 50Hz Frequency Converter mode.
3.3 CF60:The UPS is working under 60Hz Frequency Converter mode.
4 Output Voltage Micro Tuning: 0%, +1%, +2%, +3% or -1%, -2%, -3% according
to the output voltage set at Step 2.
5 Bypass Sensitivity Window:
Sensitivity Low Sensitivity High
110V System 92V~130V 97V~130V
220V System 184V~260V 194V~260V
6 Synchronization:
6.1 3Hz means the window of the output frequency is at +/- 3Hz
6.2 1Hz means the window of the output frequency is at +/- 1Hz
7 KVA: Key in 0.1 ~ 3.0 for the UPS Kva rating (make sure ≦ the capacity of the
UPS itself.)

7
8 Write: Write those new configurations to the UPS via RS232 port.
9 Programmable outlet setting
The UPS is equipped with 2 programmable outlets for supplying less critical loads.
These outlets can be disabled to shed the less critical loads during back-up modes or
overload conditions to maintain quality power supply to the more critical loads
connected to the UPS.
Click on the “Programmable outlet setting” bar to enter to the setting screen as
shown below.

9.1 Outlet Turn On After Turn on UPS – select the time to automatically enable
this outlet within the specified time when the UPS is powered on. If “0” sec
is selected, the outlet will be enabled once the UPS is powered on.
9.2 Outlet Turn Off After AC Failure – select this option to automatically
disable the outlet within the specified time after utility outage to shed the
less critical loads to provide longer battery back-up time for the other more
critical loads connected to the UPS.
9.3 Outlet Turn On After AC Recovered – select this option to automatically
enable the outlet within the specified time after the utility is restored.
9.4 Outlet Turn Off When Battery Lower than - select this option to
automatically disable the outlet at the specified remaining battery power
capacity(%) during battery mode to shed the less critical loads to prolong

8
battery back-up time for the other more critical loads connected to the UPS.
9.5 Outlet Turn Off When Overload – select this option to automatically disable
the outlet during overload condition (bypass mode) to possibly allow the
more critical loads.
Note: To be continually supplied via Bypass without shut down.
10 Com Port: To set the Com port from 1 to 10.
11 Com not open or Serial Port Open: It shows whether the setting tool finds RS232
port or not.
12 Connected or Not connected: To show if the connection between the setting tool
and the UPS is successful or not.

9
Type B Setting Tool For Chinese Language:

Fig. 2
1 設定 UPS 的輸出電壓系統為 110Vac or 220Vac 系統。
2 設定 UPS 的輸出電壓:200V、208V、220V、230V、240V or 100V、110V、
115V、120V、127V。
3 設定 UPS 的工作模式:
3.1 Normal mode:On-line UPS 的工作模式。
3.2 CF50:Frequency Converter 模式,UPS 定頻 50Hz 輸出。
3.3 CF60:Frequency Converter 模式,UPS 定頻 60Hz 輸出。
4 UPS 會依項次 2 所設定的結果,將輸出電壓往上調整 0%、1%、2%、3%或
往下調整 1%、2%、3%。
5 設定旁路電壓破窗的範圍
Sensitivity Low Sensitivity High
110V System 92V~130V 97V~130V
220V System 184V~260V 194V~260V

6 設定 UPS 輸出頻率範圍
6.1 3Hz:UPS 輸出頻率範圍為+/- 3Hz
6.2 1Hz:UPS 輸出頻率範圍為+/- 1Hz
7 KVA : 鍵入 0.1~3.0(需≦硬體容量才可設定)。

10
8 將所設定的設定值利用 RS232 傳送至 UPS。
9 Programmable outlet setting 參數設定
在上圖點選 Programmable outlet setting 進入此視窗,請依需求設定所需參數。

Programmable outlet setting


9.1 Outlet Turn On After Turn on UPS –選擇此功能使 outlet 在 UPS 開機後,
延遲開啟的時間,Default 值為零。
9.2 Outlet Turn Off After AC Failure –選擇此功能使 outlet 在 UPS 市電異
常,延遲關閉的時間,Default 值為零。
註:此功能的選擇目的在於當 outlet 接非關鍵性的負載,可讓主要輸出端
的負載有較長的放電時間。
9.3 Outlet Turn On After AC Recovered –選擇此功能使 outlet 在市電回復
後,延遲開啟的時間,Default 值為零。
9.4 Outlet Turn Off When Battery Lower than –選擇此功能當電池容量低於
設定的百分比時,關閉 outlet,Default 值為 50%。
9.5 Outlet Turn Off When Overload –選擇此功能當 UPS 過載跳至旁路時,關
閉 outlet。
註:跳至旁路後依旁路規格持續工作
10 設定電腦 RS232 的通訊埠,可設定的範圍為 1~10。
11 顯示本軟體是否有偵測到實體的 RS232 通訊埠,Com not open 或 Serial port
open。
12 顯示本軟體是否與 UPS 通訊成功,No Connect 或 Connect。