Professional Documents
Culture Documents
440 - Example OHL Setting - 1-53
440 - Example OHL Setting - 1-53
440 - Example OHL Setting - 1-53
380 kV OHL
2109A Transient Block.: duration external flt: The transient blocking, also referred to
as current reversal guard, is required with the POTT scheme if parallel
circuits are present. During clearance of a fault on the parallel circuit, the fault
current may reverse on the protected circuit. To avoid operation of the POTT
scheme under these conditions, the transient blocking times are applied.
To ensure that transient blocking is only activated by external faults, it only
starts following reverse fault detection for this time which is set to 80% of the
fastest fault clearance on the parallel circuit (including CB operation).
Tw = 0.8 ⋅ (Tcircuit _ brea ker + Trelay _ parallel _ line _ min − Trelay _ protected _ line _ max )
Tw = 0.8 ⋅ (60ms + 10ms − 20ms)
Tw = 40ms
2110A Transient Block.:Blk. T after ext. flt: Following clearance of the external fault,
the transient blocking condition must be maintained until both line ends
securely detect the new fault condition. For this purpose the relay pickup time
(re-orientation) and channel delay time must be considered.