KP308.V1.0 Controller Operation Manual 2nd Version
KP308.V1.0 Controller Operation Manual 2nd Version
0 Controller
Operation Manual
V A
RUN
Version No.:KP308V1.0.1
KP308V1.0
CONTENT
1. INSTRUCTION ..................................................................................... 1
2. MODEL NOMENCLATURE EXPLAINED ............................................. 1
3. PERFORMANCE AND FEATURES ..................................................... 1
4. SPECIFICATION ................................................................................... 2
4.1 Working Power ................................................................................ 2
4.2 AC measurement............................................................................. 2
4.3 Engine speed measurement ........................................................... 2
4.4 Switch input ..................................................................................... 3
4.5 Output .............................................................................................. 3
4.6 Environment .................................................................................... 3
5. OPERATION ......................................................................................... 3
5.1 FUNCTION OF KEYS ..................................................................... 3
5.2 CONTROLLER LAYOUT ................................................................ 5
5.3 MANUAL OPERATION ................................................................. 10
5.4 REMOTE OPERATION ................................................................. 10
6. PROTECTION .................................................................................... 11
6.1 ALARM .......................................................................................... 11
6.2 TIME DELAYED STOP ALARMS .................................................. 11
6.3 Immediate shutdown alarming ...................................................... 11
7. WIRING ............................................................................................... 13
8. PARAMETER SETTING ..................................................................... 14
8.1 PARAMETER SET LIST................................................................ 15
8.2 PROGRAMMABLE OUTPUT LIST ............................................... 19
9. INITIAL START.................................................................................... 20
10. TYPICAL APPLICATION ................................................................... 21
10.1 3-phase 4-line .............................................................................. 21
10.2 3-phase 3-line .............................................................................. 22
10.3 1-phase 2-line .............................................................................. 23
10.4 2-phase 3-line .............................................................................. 24
11. INSTALLATION ................................................................................. 25
12. TROUBLESHOOTING ...................................................................... 26
I
KP308V1.0
1. INSTRUCTION
The KP308V1.0.1 controller features manual/remote generator start and stop, data measurement,
alarm and protection. The KP308V1.0.1 can display detailed genset running and alarm data
through an LED display in five digits. An RS232 interface with the host computer can start and stop
the generator and display real time run data through the host computer. The host computer
software has a Chinese and English interface. An S485 interface is also available for remote
monitoring and control.
KP308V1.0
Manufacturer code Version No.
Controller No.
1
KP308V1.0
4. SPECIFICATION
4.1 Working Power
4.2 AC measurement
4.2.1 Voltage
4.2.2 Frequency
4.2.3 Current
2
KP308V1.0
4.5 Output
Fuel 15A,12VDC
Starting 15A,12VDC
4.6 Environment
5. OPERATION
5.1 FUNCTION OF KEYS
Stop/Reset
When genset is in alarm status, press to reset.
Screen When genset is running or in ready mode, press to enter display the
selection key running data in sequence.
3
KP308V1.0
Note:
1. When the generator is stopped and in “Manual” Mode, press and at the same time for
5 seconds, password “Test” mode is displayed. If user doesn’t input the right
password in 60 seconds the system will automatically exit the password menu and enter the
System Operation menu.
2 In “Parameters Set” menu, press and at the same time for 5 seconds to backup
current system set and the digital readout displays “Backup” for 2 seconds.
3. When the genset is stopped and in “Manual” Mode, press and for 5 seconds to
restore system set and the digital readout displays “Reset” for 2 seconds.
4. In the “Oil Filter Running Time” mode, press for 5 seconds and it will clear and reset the oil
filter maintenance alarm.
5 In the “Fuel Filter Running Time” mode, press for 5 seconds and it will clear and reset the oil
filter maintenance alarm.
6. In the “Air Filter Running Time” mode, press for 5 seconds and it will clear and reset the
filter maintenance alarm.
7. Press and for 5 seconds until the signal flashes which indicates the system has
blocked some protection functions (over/under frequency, over/under voltage,current overload
protection); then press and for 5 seconds until the signal stops flashing which indicates
the system has restored the protection functions (over/under frequency, over/under voltage, current
overload protection).
4
KP308V1.0
Press to display voltage, current, frequency, revolution, battery voltage, running time and
maintenance time in sequence.
Note:Battery charging voltage, switch value input/output status and system delay status is also
available with the RS232 port.
Genset status and working mode will be displayed on the LED panel.
If the controller is powered on, the digital readout will show the version number:
5
KP308V1.0
If the genset switches to the following status, the readout will display genset status:
Start:
Stopping delay:
Three-phase four-line
Three-phase three-line
6
KP308V1.0
Single-phase two-line
Two-phase three-line
Three-phase three-line
Single-phase two-line
7
KP308V1.0
Two-phase three-line
Speed
Note: If the “Speed Low” is set to zero, the speed won’t be displayed.
Battery voltage
Running time
Maintenance time
Oil filter
Note: When the value of "oil filter setting time" is set as "0", parameter of oil filter will not be
displayed and the function of oil filter fault testing is canceled.
Fuel filter
Note: When the value of "fuel filter setting time" is set as "0", parameter of fuel filter will not be
displayed and the function of fuel filter fault testing is canceled.
Air filter
8
KP308V1.0
Note: When the value of "Air filter setting time" is set as "0", parameter of air filter will not be
displayed and the function of air filter fault testing is canceled.
9
KP308V1.0
When the controller is working, it is initialized to “Manual” Mode, with illuminated. Press
or turn the ignition lock to start the genset.
Start steps:
Fuel relay output.starting relay output. Maximum starting time (configurable parameter) starts
counting down.If the genset can start successfully during the countdown, the starting relay is
de-energized. If starting fails, the fuel relay and starting relay are powered off and the starting
operation is aborted. The LED start failure indicator ( ) flashes.
After the genset has started, the security delay (configurable parameter)countdown timer
starts.During the security delay range, low oil voltage, high temperature, under speed, under
voltage, under frequency and a battery charging fault are ignored. The genset is in specified
running status.
10
KP308V1.0
6. PROTECTION
The controller has several built-in protection functions. When the genset has a particular
problem, the relevant fault LED alarm is actuated. The fault alarm can be one of three types:
warning, delay shutdown, immediate shutdown.
6.1 ALARM
With the following alarms, the relevant LED flashes but the genset keeps running.。
Controller alarming items are as follows:
No. Type Description
When the oil filter is past its change setting, there will be
1 Oil filter change overdue an oil filter overtime alarm and the maintenance LED
flashes.
When the fuel filter is past its change setting, there will be
2 Fuel filter change overdue a fuel filter overtime alarm and the maintenance LED
flashes.
When the air filter is past its change setting, there will be
3 Air filter change overdue an air filter overtime alarm and the maintenance LED
flashes
When the battery voltage is higher than the set value, the
4 Battery over voltage
battery LED flashes.。
When the battery voltage is lower than the set value, the
5 Battery under voltage
battery LED flashes.
When the charging voltage is lower than the set value,
6 Charging fault
the battery LED flashes.
11
KP308V1.0
and the genset will stop instantly. A buzzer sounds an additional alarm.
Controller alarming items are as follows:
12
KP308V1.0
7. WIRING
KP308V1.0 Controller Back Panel:
24 23 22 21 20 19 18 17 16 15 14 13 12
Current
Genset Voltage (Rated 5mA)
Comm_VCC
Comm_GND
A B C N ICOM IA IB IC
RXD
TXD
DIR
24 23 22 21 20 19 18 17 16 15 14 13 12
120/240 Select
Crank
Oil Press
B+
Remote
Start sw
B-
EM Stop
Charge winding
+
1 2 3 4 5 6 7 8 9 10 11
13
KP308V1.0
8. PARAMETER SETTING
After logging in to the Parameter Set menu, the remote mode light flashes and the parameters
will be displayed on the controller.
Press to return to “System Operation” menu
When genset is stopped, and is in “Manual” Mode, press and at the same time for 5
seconds and the password test mode is displayed
After inputting the right password, press to enter the “Parameters Set” menu. Take the
settings of flywheel teeth for example. After entering the flywheel tooth menu, press to set the
number; the default value is 100. While the value is flashing, press or to increase or
14
KP308V1.0
decrease the value. After inputting the value, press to confirm and save the value. Press the
key to return to the “Parameters Set” menu.
There are two configurable authorities for the controller: Operator and engineer.
After entering the password setting menu, input correct password and log in parameter setting
menu.
Module initial password:
Operator password:0001
Note: Engineer authority is for the manufacturer to set the parameter before
delivery. Manufacturer can configure the system parameters according to
engine performance, module properties and user's requirements. All the
parameters should be configured properly or the genset will be seriously
damaged and unpredictable accidents will be caused.
8.1.2 Operator
V A
Parameter Code
Data
RUN
15
KP308V1.0
8.1.3 Engineer
Terminal “8” has “Remote” function; the function is only valid in “Remote mode”.
In the “Remote mode”, after Terminal “8” is closed (low potential), genset starts after Remote
start delay (parameters can be set). If terminal “8” is open (high potential), genset won’t stop.
In the “Remote mode”, after terminal “8” is open (high potential), the genset starts after remote
start delay (parameters can be set). If terminal “8” is closed (low potential) the genset won’t stop.
19
KP308V1.0
In the “Remote Mode” after terminal “8” is closed (low potential), the genset won’t start. With
terminal “8” open (high potential), the genset stops after Remote Stop Delay(parameters can be
set).
In the “Remote mode” after terminal “8” is open (high potential), the genset won’t start.
Terminal “8” closed (low potential), the genset stops after Remote Stop Delay (parameters can be
set).
In the “Remote mode” after Terminal “8” is closed (low potential), the genset starts after remote
start delay (parameters can be set). With terminal “8” open (high potential), the genset stops after
Remote Stop Delay (parameters can be set).
In the “Remote mode", after terminal “8” is open (high potential), the genset starts after remote
start delay (parameters can be set). Terminal “8” closed (low potential), the genset stops after
Remote Stop Delay (parameters can be set).
9. INITIAL START
Before the initial start of the controller, please check the following:
1. All connections and wires;
2. The DC working power of the controller is equipped with a fuse and the batteries for proper
connection and polarity;
3. The Emergency Stop button is connected with the battery positive terminal through the
normally closed emergency stop button and fuse;
4. Take proper measures to prevent the engine from starting such as disabling the fuel valve
connections then connect the battery and select manual mode.
5. Set the controller to "Manual" mode,press (start) to start the generator. Genset won’t
start. If start failure alarms activate, press (stop) to recover the controller.
6. Restore the engine to the proper starting condition and press (start). The genset should
start and if everything is normal, the genset will be in idle status (if idle running is available) then the
genset should run normally. At this time, check all parameters such as voltage, current, and
frequency. If there are any abnormalities, stop the genset and refer to the operation manual.
7. Please check with your seller or the factory if you need additional help.
20
KP308V1.0
Load
16 15 14 13 12
DIR
TXD
W
U
N
V
RXD
Comm_GND
20 19 18 17
IC
Charge winding
9 10 11
IB
IA
ICOM
Oil Press
8
Remote
21
7
N
Start sw
6
120/240 Select
22
5
C
Crank
4
Fuel
23
EM Stop
B
B+
24
B-
A
Generator N
B
A
21
QF
A U
10.2 3-phase 3-line
B V
C W
Load
Generator
A B C ICOM IA IB IC
DIR
TXD
RXD
22
Comm_VCC
Comm_GND
KP308V1.0
24 23 22 21 20 19 18 17 16 15 14 13 12
B-
B+
Fuel
Crank
Remote
Start sw
EM Stop
Oil Press
Charge winding
120/240 Select
+
QF
A U
10.3 1-phase 2-line
N N
Load
Generator
A N ICOM IA
DIR
TXD
RXD
Comm_VCC
Comm_GND
23
24 23 22 21 20 19 18 17 16 15 14 13 12
KP308V1.0
B-
B+
Fuel
Crank
Remote
Start sw
EM Stop
Oil Press
Charge winding
120/240 Select
+
QF
A U
10.4 2-phase 3-line
B V
N N
Load
Generator
A B N ICOM IA IB
DIR
RXD
TXD
Comm_VCC
Comm_GND
24
24 23 22 21 20 19 18 17 16 15 14 13 12
KP308V1.0
B-
B+
Fuel
Crank
Remote
Start sw
EM Stop
Oil Press
Charge winding
120/240 Select
+
11. INSTALLATION
25
24 23 22 21 20 19 18 17 16 15 14 13 12
Current
Genset Voltage (Rated 5mA)
KP308V1.0
A B C N ICOM IA IB IC
DIR
RXD
TXD
Comm_VCC
Comm_GND
24 23 22 21 20 19 18 17 16 15 14 13 12
Start sw
Oil Press
EM Stop
Charge winding
+
120/240 Select
1 2 3 4 5 6 7 8 9 10 11
The KP308V1.0 controller is to be panel mounted. Dimensions are as follows:
KP308V1.0
12. TROUBLESHOOTING
Fault Solutions
Check batteries
No power to the controller Check controller connections
Check DC fuse
Low oil pressure alarm after Check oil pressure sensor and connections
start
26