Test Report No.

7191152016-MEC-16/03-OHH
dated 21 DEC 2016

Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group and the
General Terms and Conditions of Business of TÜV SÜD PSB Pte Ltd. In addition, this report is governed by the
terms set out within this report.

SUBJECT:

Tensile and flattening test of Vertical Standard and Transom submitted by


Seng Yew Scaffolding & Engineering Pte Ltd on 29th Nov 2015.

TESTED FOR:

Seng Yew Scaffolding & Engineering Pte Ltd


18 Sungei Kadut Avenue
Singapore 729489

Attn: Ms Eileen Khiew

TEST METHOD:

311 : 2005 "Specification for steel tubes and fittings used in tubular scaffolding.
Clause 3.2 Steel scaffold tubes – material."

DESCRIPTION OF SAMPLE:

1 sample each of Vertical Standard and Transom was recieved.

TEST RESULT

1. Dimension Measurements

SS 280 Part 2 : 2009


2.0m 1.8m
Sample reference Clause 4.2 & 5
Standard Transom
Requirements
Measured outside diameter (mm) 48.50 48.52 48.3 ±0.25

Measured thickness (mm) 3.08 2.73 2.7 ±0.2

LA-2007-0380-A LA-2007-0384-G The results reported herein have been performed in accordance with the
LA-2007-0381-F LA-2007-0385-E terms of accreditation under the Singapore Accreditation Council.
LA-2007-0382-B LA-2007-0386-C Inspections/Calibrations/Tests marked "Not SAC-SINGLAS Accredited" in
LA-2007-0383-G LA-2010-0464-D this Report are not included in the SAC-SINGLAS Accreditation Schedule for
our inspection body/laboratory.

Laboratory: Phone : +65-6885 1333 Regional Head Office:


TÜV SÜD PSB Pte. Ltd. Fax : +65-6776 8670 TÜV SÜD Asia Pacific Pte. Ltd.
No.1 Science Park Drive E-mail: enquiries@tuv-sud-psb.sg 1 Science Park Drive, #02-01
Singapore 118221 www.tuv-sud-psb.sg Singapore 118221
Co. Reg : 199002667R Page 1 of 3
Test Report No. 7191152016-MEC-16/03-OHH
dated 21 DEC 2016

2. Tensile Test

2.0m 1.8m SS 280 Part 2 : 2009


Sample reference
Standard Transom Clause 4.2 Requirements
Measured width (mm) 18.98 18.97 -

Measured thickness (mm) 3.08 2.73 -

Sectional area, So (mm2) 58.46 51.78 -


Min. 315(for 2.7 t < 2.9mm)
0.2%Yield stress (N/mm2) 429 380
Min. 235 (for t 2.9mm)
Tensile strength (N/mm2) 480 437 -

Elongation on 50mm (%) 57 23 -

3. Flattening Test

3.0m 1.8m SS 311: 2005


Sample reference
Standard Transom Annex B Requirement
Flattening test (75% of OD) Pass Pass
No cracks or flaws
observed
Flattening test (60% of OD) Pass Pass

Note: Please refer to test report 732014910-CEG16/2, for chemical analysis.

Sean Loh Oh Heng Hwa


Associate Engineer Executive Engineer
Industrial Group
Mechanical Centre

Page 2 of 3
Test Report No. 7191152016-MEC-16/03-OHH
dated 21 DEC 2016

Please note that this Report is issued under the following terms :

1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.

2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.

3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.

4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.

5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.

July 2011

Page 3 of 3

You might also like