Professional Documents
Culture Documents
1500W Single Output Power Supply: Series
1500W Single Output Power Supply: Series
Dimension
L * W * H
278 * 127 * 83.5 (2U) mm
10.9 * 5 * 3.29 (2U) inch
Bauar t gepruft
Sicherheit
egel ma ge
od o s
be wac g
RoHS
ID 2000000000
■ Features ■ Applications
Universal AC input / Full range Factory control or automation apparatus
Built-in active PFC function Test and measurement instrument
High efficiency up to 91% Laser related machine
Forced air cooling by built-in DC fan Burn-in facility
Output voltage programmable Digital broadcasting
Active current sharing up to 6000W (3+1) RF application
Built-in remote ON-OFF control / remote sense /
auxiliary power / power OK signal
Protections: Short circuit / Overload / Over voltage
/ Over temperature
Optional conformal coating
5 years warranty
■ Description
RSP-1500 is a 1.5KW single output enclosed type AC/DC power supply. This series operates for 90~264VAC
input voltage and offers the models with the DC output mostly demanded from the industry. Each model is
cooled by the built-in fan working for the temperature up to, 70℃. Moreover, RSP-1500 provides vast design
flexibility by equipping various built-in functions such as the output programming, active current sharing,
remote ON-OFF control, auxiliary power, etc.
Block Diagram
+S
ACTIVE RECTIFIERS RECTIFIERS
EMI INRUSH POWER +V
I/P CURRENT & &
FILTER SWITCHING FILTER -V
LIMITING PFC
-S
PFC O.V.P.
CONTROL O.L.P.
PWM PV
DETECTION
O.T.P. CONTROL CIRCUIT P OK
REMOTE RC
LOAD CONTROL
SHARING
LS
FAN
AUX RECTIFIERS
POWER & AUX POWER
FILTER (12V/0.1A)
Static Characteristics
70 MODEL
INPUT 24V 27V 48V
60
1512W 1512W 1536W
100~264VAC
50 63A 56A 32A
80 86
84
60
50 82
LOAD (%)
+5V
40
80
20 78
76
-20 0 10 20 30 40 45 50 60 70 (HORIZONTAL) 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
AMBIENT TEMPERATURE (℃) LOAD
◎ The curve above is measured at 230VAC.
Function Manual
1. Remote Sense
※ The Remote Sense compensates voltage drop on the load wiring up to 0.3V
CN1
+V
-V +V PIN7 -S PIN8 +S
LOAD
-V
2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
※ In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 70~100%(Typ.) of the nominal voltage by applying
EXTERNAL RESISTANCE
CN1
-V +V PIN7 -S PIN8 +S
◎ Connect an external resistor between TRIM(pin4) & -S(pin3 or pin4 or pin5) on CN1 or CN2, and +S & +V, -S & -V also need to be connected.
Vout
100%
90%
80%
70%
R
0Ω 470Ω 1.8KΩ OPEN
Fig. 2.2 External Resistance (Typical)
3.Remote ON-OFF
※ Remote ON-OFF is activated by the configuration with respect to CN1,CN2 and CN3 as shown in the following diagram.
CN2
CN3
-V +V
PIN5 RC1 PIN6 AUX
PIN4 AUXG
AUX
2.2KΩ
RC1
5V
150Ω RC2
12V typ.
620Ω
SW
RCG
AUXG
AUX
2.2KΩ
RC1
150Ω RC2
12V typ.
RCG
SW
AUXG
AUX
2.2KΩ
RC1
150Ω RC2
12V typ.
SW
RCG
AUXG
◎ Connection Method
Fig. 3.2(A) Fig. 3.2(B) Fig. 3.2(C)
Output on SW Open SW Open SW Close
SW Logic
Output off SW Close SW Close SW Open
CN3
-V +V
P OK
R
0.1uF 100KΩ V
No.1(Master)
-V +V
AC/L AC/N ◎ When remote sensing is used in parallel operation, the sensing wire must be
connected only to the master unit
◎ Sense lines should be twisted in pairs to minimize noise pick-up.
No.2(Slave)
-V +V
AC/L AC/N
+S
+V
Load
-V
-S
No.3(Slave)
-V +V
AC/L AC/N
No.4(Slave)
-V +V
AC/L AC/N
240 11.2
16 max.
22.7
38
38.1
83.5
1 1
16
8-M4 L=5(Both Sides)
ψ8 .5
2-M4
278
240 11.2
OUTPUT
4
17
+V
4-M4 L=5
1 1 -V
CN1 CN2 CN3
86 42 86 42 64 2
75 31 75 31 53 1
Air flow
I/P LED
direction
127
93
SVR
10
1
2
13
1 1
3
7 1
6 2
Mating Housing HRS DF11-6DS or equivalent
Terminal HRS DF11-**SC or equivalent
5 1
Installation Manual
Please refer to : http://www.meanwell.com/manual.html