Certificate of Compliance

Certificate: 2452443 Master Contract: 163545

Project: 2452443 Date Issued: January 25, 2012


Issued to: Eaton Corporation
1000 Cherrington Pkwy
Moon Township, PA 15108
USA
Attention: Lou Grahor

The products listed below are eligible to bear the CSA Mark shown

Steve Jeffrey
Issued by: Steve Jeffrey

PRODUCTS
CLASS 1432 01 - CIRCUIT BREAKERS - Moulded Case Type

Circuit breakers, moulded case type, LD-frame, Series C; Type CLD, LD, LDB, CLDB, CLDC, LDC, LDCB,
CLDCB, CHLD, HLD, HLDB, CHLDB, HLDDC, 300-600A, 2, 3 and 4-pole, 600V ac and 250V dc in 2 and 3-
pole configuration and 600V dc in 3-pole configuration.
Notes:
1. These circuit breakers may be marked with the following high current interrupting ratings in RMS
symmetrical kilo amps:

Interrupting Capacity (KA)

Type Frequency (Hz) 240V ac 480V ac 600V ac 250V dc 600V dc

CLD, LD, LDB 50/60 65 35 25 22 -


CLDC, LDC,
LDCB 50/60 200 100 50 30 -
CHLD, HLD,

DQD 507 Rev. 2009-09-01 Page: 1


Certificate: 2452443 Master Contract: 163545

Project: 2452443 Date Issued: January 25, 2012

HLDB 50/60 100 65 35 25 -


HLDDC - - - - *50 **42KA * (2 poles in
series) ** (3 poles in series)

2. When factory sealed, Types LDB, HLDB, LDCB circuit breakers are suitable for use with revised line/
load connections.

3. Types LD, LDB, HLD and HLDB circuit breakers are supplied with Type LT thermal magnetic trip units
or Type LS solid static trip units.

4. Type LD-DC circuit breakers are supplied with Type LT thermal magnetic trip units only.

5. Type LD, LDB, HLD and LD-DC circuit breakers are supplied with type LT thermal magnetic trip units
with adjustable magnetic trip ranges as follows:

Trip Unit Adjustable Magnetic


Rating (A) Trip Range (A)

300 1500-3000
350 1750-3500
400 2000-4000
450 2250-4500
500 2500-5000
600 3000-6000

6. These circuit breakers are calibrated to 40C requirements.

DQD 507 Rev. 2009-09-01 Page: 2


Certificate: 2452443 Master Contract: 163545

Project: 2452443 Date Issued: January 25, 2012

7. Three pole devices are suitable for use on single phase ac circuits.

8. The mechanism is trip free of the handle which assumes a mid-position between on and off upon
automatic tripping.

9. Types CLD, CLDB, CHLD, CHLDB, CLDC AND CLDCB circuit breakers are suitable for use at 100
percent rating.

10. Types LD, HLD & LDC circuit breakers are supplied with Type LEP Digitrip OPTIM solid state trip
units.

APPLICABLE REQUIREMENTS
CSA C22.2 No. 5-09 - Moulded Case Circuit Breakers UL Std. No. 489 -
Moulded-Case Circuit Breakers and Circuit Breaker Enclosures

DQD 507 Rev. 2009-09-01 Page: 3