PG605U
PG605U
PG 605U
Programmer
Manual
! WARNING
Hazardous voltage.
Can cause death, severe
personal injury, or substantial
property damage.
Restrict use to qualified
personnel.
See safety instructions.
Only qualified personnel should install or maintain this equipment after becoming thoroughly familiar
with all warnings, safety notices, and maintenance procedures contained in this manual. The successful
and safe operation of this equipment is dependent upon proper handling, installation, operation, and
maintenance.
The following are definitions of the terms “qualified person”, “danger”, “warning”, and “caution”, as
applicable for this document.
Qualified Person DANGER
One who is familiar with the installation, Indicates loss of life, severe personal injury, or
construction, and operation of this equipment and
substantial property damage will result if
the hazards involved. In addition, the person
should have the following qualifications: proper precautions are not taken.
WARNING
• Be trained and authorized to use and tag
circuits and equipment in accordance with Indicates loss of life, severe personal injury, or
established safety practices substantial property damage can result if
proper precautions are not taken.
• Be trained in the proper care and use of
protective equipment in accordance with CAUTION
established safety practices Indicates minor personal injury or property
damage can result if proper precautions are not
• Be trained in rendering first aid
taken.
Appendices
Installation Guidelines
How To Use This Book
Technical Specifications
4
3
2
1
C/D
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaa
A/B/
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaa aaaaaaaa
PG 605U Manual Preface
Preface
This book provides an overview of the PG 605U programmer. It describes the hardware and
installation procedures. It also provides information on programming, applications, error/fault
messages, and technical specifications. Also included is a STEP 5 operation set reference section.
This book is intended for engineers, programmers, and maintenance personnel who have a
general knowledge of programmable controller concepts.
If you have any questions about the PG 605U programmer not answered in this book, please con-
tact your local Siemens representative. In the United States of America, please call 1-800-322-7224.
This chapter provides an overview of the PG 605U programmer. It also lists the controllers that
can be programmed using the PG 605U.
This chapter describes the technical specifications for the PG 605U, the principle of operation,
and the keypad.
This chapter discusses the various options for connecting the PG 605U to SIMATIC S5 pro-
grammable controllers.
This chapter discusses programming on the PG 605U programmer, and describes the various
options available to the user.
This appendix lists all of the error codes and their meanings.
• Index
The index contains an alphabetical list of key terms and subjects covered in this book and their
corresponding page numbers.
• Remarks Form
The Remarks Form is provided for your comments and recommendations. If you are in the
United States of America, please use the postage-paid form.
Reference Material
It is recommended that you have the following books that support the PG 605U programmer:
Catalog ST 59
Training
Contact your local Siemens representative for information on training courses to aid you in
becoming familiar with this product. Consult Appendix C for a list of Siemens offices worldwide:
Conventions
The following conventions are used in this book and are listed for your reference.
4
3
2
1
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
System Overview
aaaaaaaaaaaa
aaaaaaaaaaaa
Installation Guidelines
aaaaaaaaaaaa
Technical Specifications
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
1-1.
1-1.
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
Tables
Figures
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. - 1
The PG 605U Programmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1. . - 2
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
AGs
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S5-95U
S5-90U
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S5-115U
S5-101U
S5-100U
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PGs
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
•
•
•
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
System Overview
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
•
•
•
•
•
Order number 6ES5 605-0UA11
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
6ES5 984-1UA41)
(6ES5 984-1UA31,
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
•
•
•
•
•
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Order number
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
6ES5 605-0UA12
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
System Overview
1-1
The table below shows you how the two versions of the PG 605U programmer can be connected to
You can use the PG 605U to develop, correct and debug STEP 5 user programs. You can also print
aaaaaaaaaaaaaaaaaaa
System Overview PG 605U Manual
4
3
2
1
aaaaaaaaaaaa
2.3
2.2
2.1
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
System Overview
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
Installation Guidelines
aaaaaaaaaaaa
aaaaaaaaaaaa
Technical Specifications
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
2-2.
2-1.
2-1.
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
Tables
Figures
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa
2 Technical Specifications
Only one block can be processed at a time in the PG 605U. If a block already in the PLC memory is
to be displayed, corrected or debugged, it is automatically copied into the programmer memory
when it is called up, and so remains available in the PLC memory. The block previously in the
programmer is overwritten.
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
Note:
When the programmer is unplugged, its memory contents are lost.
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
Programmer
Operation function keys
keys
Cursor control
keys
Operand
keys ((Photo Nr.:
GWA 7287/10))
Function
Shift key keys
The PG 605U has a number of dual-function keys. The secondary functions (marked in white) are
activated by first pressing the white <SHIFT> key. If you require several secondary functions in
succession, you must press the <SHIFT> again for each function. Press the <SHIFT> key once
again to reset. A broken line at the bottom left of the display indicates that a secondary function
has been selected.
XI
PB
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Key
aaaaaaaaaaaaaaaaaa
XI
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
<CLEAR>
<SHIFT> :
<STATUS>
aaaaaaaaaaaaaaaaaa
<INPUT> key
aaaaaaaaaaaaaaaaaa
<ENTER> key
<BREAK> key
<INSERT> key
aaaaaaaaaaaaaaaaaa
<DELETE> key
<SEARCH> key
<SPECIAL> key
<DISPLAY> key
<REMOVE> key
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
display)
aaaaaaaaaaaaaaaaaa
counters)
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
(Input/output)
(Input/output)
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Function
(Special functions)
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
(Terminate input/output)
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Technical Specifications
2-3
aaaaaaaaa
aaaaaaaaaaaaaaaaaa
2-4
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Key
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Technical Specifications
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
<ARROW UP>
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
<ARROW LEFT>
<ARROW RIGHT>
<ARROW DOWN>
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Function
aaaaaaaaaaaaaaaaaa
PG 605U Manual
4
3
2
1
aaaaaaaaaaaa
3.2
3.1
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
System Overview
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
Installation Guidelines
Technical Specifications
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
3-3.
3-2.
3-1.
aaaaaaaaaaaa
aaaaaaaaaaaa
Figures
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
...................3 - 2
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
3.1
$
—..,,
To connect the PG 605U, plug the programmer connector into the connecting socket of the
programmable controller and lock it. This establishes all the necessary connections, including the
power supply.
After connection, the programmer executes a short self-test and then enters the initial state. The
following appears on the display:
The PG 605U programmer is switched off by unlocking and unplugging the programmer
connector.
—
. . . . . — , . .
Figure 3-2. The PG 605U as a Handheld and Dt?SktOp Unit
, [
.,,-,----
1
Drill-holes for
securing screw I I I +
(M4, max length: I
8 mm/O 3 In.) I 203 mml
8 In.
1
I
I
? I ‘p
A I 93
t I
05 mml ; mml
I
0.2 In 3.7 in.
I
v v
,
I ‘+I
92 mm13 6 In ‘
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . .- . 1
4.2 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4. . -. . 2
4.2.1 Selecting Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4. . -. 2
4.2.2 Entering Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4. .- 2
4.2.3 Entering Labels (Only in FBs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ..- 4
4.2.4 Programming Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4. . - 5
4.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4. . .- . 6
4.3.1 Display from the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4. .- 6
4.3.2 Display from the Programmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4. - 7
Figures
Tables
4.1 General
Sec.
fnct.
RLO SIG Message No.
After it has been connected to the programmable controller and has completed the short self-test,
the programmer (PU) prompts the user to enter a command.
4.2 Input
Press the <INPUT> key (Table 2-1). Press the <SHIFT> key and use the operand keys to enter the
block type (OB, PB, FB) and the block number (1 to 255). Terminate the entry and execute the
command with the <ENTER> key. The example ( Figure 4-2) shows the entry of OB 1.
000:
OB 1
PU PC?
OB 1
Press the <ENTER> key again to transfer the block into the programmable controller.
If you press the <BREAK> key twice, the programmer aborts input (which is not stored) and
returns to the previous function.
The block remains in the programmer after aborting entry, and you can continue to manipulate it
by pressing <DISPLAY> and <ENTER>.
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
Note:
If you wish to display a block on the PG 635, 675, 685 and 695 CRT-based progammers, you must
enter "BLD 255" (End of segment) after a maximum of 255 STEP 5 statements.
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
<SHIFT key>
Block type
and
number
Statement
PU PC? B R E A K ?
O B 1
OVERWRITE?
*OB 1
:
*COMMAND*
Function
X :
Label number
X10:
X10:
Note:
New labels are generated when transferring blocks from the PLC to the programmer. You can
rename the labels you have entered.
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
To program a data block, select the INPUT or DISPLAY function. Press the <SHIFT> and <*>
keys, and enter the block number instead of entering "FB", "OB" or "PB". The following display
appears when you press the <ENTER> key:
0000: KH
DB 1
You can now switch to other formats using the <ARROW RIGHT> key.
0000: KH
DB 1
0000: KF
0000: KT
0000: KC
After you have entered a data word, you can key in a repetition factor (1 to 255) after first
pressing the <SHIFT> and <*> keys. The number can then be inserted with the <INSERT> key
or overwritten with the <ENTER> key.
4.3 Display
:
*DISPLAY*
<SHIFT> key
Block type
Block number
000:A I 0.1
OB 1
You can now display the subsequent statements by pressing the <ARROW LEFT> key. See 4.4 for
corrections.
Press the <DISPLAY> key ( Table 2-1.) and the <ENTER> key. If you have just terminated an
entry or display with the <BREAK> key, you can display the block by pressing the <DISPLAY>
and <ENTER> keys.
:
*DISPLAY*
000:A I 0.1
OB 1
If the block has already been overwritten in the PLC, error message "*84" appears (block not in
programmer; Appendix B). If you want to process this block, you must first transfer it from the
PLC to the programmer ( 4.3.1).
4.4 Correction
Select the desired statement with the cursor control keys or by using the Search function ( 4.6).
Press the <SHIFT> key and the <INSERT> key. The statement selected is deleted, and the next
statement is displayed.
Use the cursor control keys or the Search function to select the statement in front of which the
new statement is to be inserted. Enter the new statement, e.g. A I 1.0. Press the <INSERT> key.
The new statement is inserted and the display shows the statement in front of which the new
statement has been inserted.
Select the statement to be overwritten with the cursor control keys or by the Search function.
Enter the new statement, e.g. AN I 1.0. Press the <ENTER> key. The statement is overwritten and
the next statement is displayed.
You can control the cursor in the INPUT, DISPLAY and STATUS (program-dependent signal status
display) functions, and also with the Search function ( 4.6).
Press the <ARROW UP> key to display the previous statement and the <ARROW DOWN> key
for the next statement.
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaa
Note:
Both cursor control keys are of the auto-repeat type, i.e. the function is automatically repeated
if they are held down.
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaa
4.6
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
4.6.3
4.6.2
4.6.1
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
Note:
Note:
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
statement.
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
search function.
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
PG 605U Manual
”QW” or ”FW”.
for D
for C
Search Function
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
stop, press the <CLEAR> key. The last statement is then displayed.
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
The shift key must be pressed before the B, Y or W when entering ”IB”, ”QB”, ”FY”, ”IW”,
If the search address is in a multi-word statement (in two-word statements, e.g.L KF +1), the
If the address entered is greater than the number of addresses in the user program, the last
aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa aaaaaaaaaa
4-9
key is pressed. If you have not yet started the search with the <SEARCH> key and you want to
After selecting the function, enter the search item, e.g. A I 1.0 (statement) or I 1.0 (operand). Press
the <SEARCH> key ( Table 2-1). When the search item has been found, the statement with the
programmer. The search begins and ends at the address displayed before commencement of the
can quit the search by pressing any other key. If the search item is not present, message *86 is
corresponding address is displayed. Press the <SEARCH> key again to continue searching. You
( Table 2-1). Enter the address you are looking for. The search is started when the <SEARCH>
After selecting the Search function, start the address search by pressing the <SPECIAL> key
press the <SEARCH> key. The desired label appears in the display along with the corresponding
After selecting the Search function, press the <ARROW LEFT> key. Enter the label, e.g. F10, and
status display) functions. This function searches through the entire user program in the
The Search function is possible in the INPUT, DISPLAY and STATUS (program-dependent signal
aaaaa aaaaa aaaaa aaaaa
Programming and Operator-Process Communication PG 605U Manual
The program-dependent signal status display is an image of the current process status shown on
the program display and is updated cyclically in the display.
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
Note:
The PLC must be in RUN mode for program-dependent signal status display.
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
Start program-dependent signal status display by pressing the <FORCE> key ( Table 2.1). After
pressing the <SHIFT> key, enter the block type (OB, PB, FB) and the block number (0 to 255). Press
the <ENTER> key to execute the function. The first statement of the block selected appears in
the display ( 4.5 and 4.6).
000:A I 0.3
11
The signal state for the selected statement is shown in the second line of the display.
Digital operation R X X X X Y Y Y Y
R = RLO XXXX = ACCUM 1 YYYY = ACCUM 2
Binary operation R S
R = RLO S = SIG
Miscellaneous operations R
R = RLO
Counter operation R S K Z : X X X
R = RLO S = SIG XXX = Count
Timer operation R S K T : X X X . Y
R = RLO S = SIG XXX = Time
Y = Time base
RLO = Result of logic operation
SIG = Signal state
Figure 4-9. Representation of the Signal State
The STATUS VAR function enables you to display current binary signal states or digital values for
specific operands, such as are found during program scanning in the PLC at the system checkpoint
(point prior to scanning the cyclic S5 program).
The STATUS VAR function is started with the <FORCE> key. Press the <ENTER> key after
entering the operand identifier and the parameters (e.g. I 1.0, T 1, QB 1). The signal state appears
in the display. Press the <BREAK> key to return to the initial state.
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
Note:
The <SHIFT> key must be pressed before the "B" or ”Y” when entering "IB", "QB" or "FY".
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaaaaaa
aaaa
The FORCE function can only be implemented in connection with STATUS VAR. Input bytes, output
bytes and flag bytes can be forced.
Select direct signal state display first ( 4.7.2). The following appears when you press <FORCE>.
*STATUS*IB 0
KM :0000 0111
You can now position the cursor with the <ARROW RIGHT> and <ARROW LEFT> keys and set
the signal state. "1" signifies "Signal state 1", "0" signifies "Signal state 0". Press the <ENTER>
key to execute the FORCE function, and observe the signal state.
Press <BREAK> to return to the STATUS VAR function. The FORCE function is not executed.
You may have to adapt the user program when using the PG 605U from version V1.2 onward in
order to be able to manipulate timers and counters.
The PLC can be in the RUN or STOP mode. As with the FORCE VAR function, the manipulating of
timers and counters can only be implemented within the direct signal state display function.
The manipulating of timers and counters affects the data block set in the programmer. The data
word with the number of the counter or timer to be manipulated is influenced.
Program Structure
The following sequence of operations must be programmed in the user program to transfer the
setting to the timer:
Note:
For reasons of clarity, the number of the data word and the number of the timer or counter
should be identical.
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaa
Timers and counters in the S5-101U are located in different areas in the data block. In the other
PLCs, timers and counters can have their own data block.
Since there is only one data block in the S5-101U for timers and counters, data words 0 to 15 are
accessed for manipulating timers, and data words 16 to 32 for manipulating counters.
DW 0 : T0 DW 16 : Z0
DW 1 : T1 DW 17 : Z1
: :
: :
DW 15 : T15 DW 31 : Z15
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaa
Note:
Before the programmable controller is started, all variable timers and counters must be preset
with values that are not critical for the process to be controlled.
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaa
Select STATUS VAR and press the <STATUS> key ( Table 2-1.). DB 11 appears as the default in
the display (not in the case of the S5-101U). Type in the block containing the data word to be
manipulated. Press the <ENTER> key to transfer the DB setting. The time set appears in the
display. It consists of a value between 1 and 999 (before the point) and the time base 0 to 3 (after
the point).
*STATUS* T 1
KT : 12.3
You can enter a new time after pressing the <STATUS> key. Press the <ENTER> key to transfer
the value entered and to store it in the data block. Press the <BREAK> key to return to the initial
state.
If either the block selected or the relevant data word is not available, message "*88" appears (
Appendix B).
Select the DISPLAY function with the <DISPLAY> key and enter a <1>. Press the <ENTER> key.
The first block of the block list and the relevant initial address are displayed. You can scroll
through the block list with the <ARROW DOWN> key. You can terminate block list display and
return to the initial state with the <BREAK> key.
Select the DISPLAY function with the <DISPLAY> key and enter a <1>. Then enter the block
type (OB, PB, FB or "*" for DB) and the block number (0 to 255). Press the <ENTER> key. The data
of the block selected appears in the display. Press the <BREAK> key to return to the initial state.
Select the DISPLAY function with the <DISPLAY> key and enter a <2>. Press the <ENTER> key.
The interrupt stack is displayed as a bit pattern. See Tables 4-1 and 4-2 of your programmable
controller manual for an explanation of the display.
You can scroll the display with the <ARROW DOWN> key. Press the <BREAK> key to return to
the initial state.
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
aaaaaaaaaaaaaaaaaa
Byte
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
ZU-
TER
NAU
ASP
ASP
NUR
KEIN
ANZ1
aaaaaaaaaaaaaaaaaa
STOP
STOP
CA-DA
STAND
EPROM
SCHAL-
aaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
AN-
QVZ
RAM
ASP
NUR
SCH
FEHL
ANZ0
aaaaaaaaaaaaaaaaaa
ZEIGE
PBST
CE-DA
STOP
SYNCH
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
SUF
SCH
OVF
BST
NINT
NEU-
aaaaaaaaaaaaaaaaaa
KOLIF
KOPF
NINEU
START
UAFEHL MAFEHL
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
ZYK
END
SCH
SCH
TAET
TRAF
aaaaaaaaaaaaaaaaaa
E0VH
NENZ
REMA
PROM
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
IRRELEVANT
IRRELEVANT
OR
BAU
NNN
ADR
aaaaaaaaaaaaaaaaaa
ASP
NUR
SYSFE
BATT-
PUFFER
ISTACK Display
EEPROM
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
AF
BR
OR
OR
OR
STS
PEU
ADR
FEHL
aaaaaaaaaaaaaaaaaa
SPAB
PROM
STATUS
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
AS
VKE
VKE
VKE
VKE
NAU
BAU
ASP
aaaaaaaaaaaaaaaaaa
BARB
SUMF
STUEB
LÜCKE
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
FA
UR
FKT
FKT
FKT
ADR
RAM
ASP
FEST
aaaaaaaaaaaaaaaaaa
FEHL
ERAB
ENDE
BARB
QUITT
LADEN
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
System
SD7
SD6
SD5
Data Word
aaaaaaaaaaaaaaaaaa
SD211
SD212
SD213
SD214
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
4-15
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
4-16
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
aaaaaaaaaaaaaaaaaaaa
Byte
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
ACCUM 1 (low)
ACCUM 2 (low)
ACCUM 1 (high)
ACCUM 2 (high)
aaaaaaaaaaaaaaaaaaaa
ISTACK Display
Programming and Operator-Process Communication
aaaaaaaaaaaaaaaaaaaa
Nesting depth (0 to 6)
VKE
VKE
VKE
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
FKT
FKT
FKT
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
System
Data Word
aaaaaaaaaaaaaaaaaaaa
SD203
SD204
SD205
SD206
SD207
SD208
SD209
SD210
Table 4-1. Interrupt Stack (S5-90U, S5-95U, S5-100U, S5-101U, S5-115U) (Continued)
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa
PG 605U Manual
System Parameters
1
PAR 1 Input modules
1
PAR 2 Output modules
1
PAR 3 Process input image
1
PAR 4 Process output image
1
PAR 5 Flag memory
1
PAR 6 Time register
1
PAR 7 Data register
1
PAR 8 SD area in PLC memory
1
PAR 10 End address of user memory
1
PAR 11 System program memory
2
PAR 12 Length of the DB list
2
PAR 13 Length of the SB list
2
PAR 14 Length of the PB list
2
PAR 15 Length of the FB list
2
PAR 16 Length of the OB list
1
Address
2
Length in bytes
1
aaaaaaaaaaaaaaaaaaaa
1
0
aaaaaaaaaaaaaa
4-20
21
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
Bit
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
1
0
aaaaaaaaaaaaaaaaaaaa
20
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
PAR 22
PAR 21
PAR 20
PAR 19
PAR 18
PAR 17
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
Length in bytes
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
no CPU
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
System Parameters
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
S5-101U/ S5-115U
aaaaaaaaaaaaaa
Reserve
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
of the PLC
aaaaaaaaaaaaaaaaaaaa
CPU identifier
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
S5-90U/S5-95U/S5-100U/
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
1
0
0
0
23
Programming and Operator-Process Communication
1
1
0
0
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
Bit
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
1
0
1
0
22 21
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
1
0
0
1
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
20
Table 4-4. CPU Identifier in SYSPAR
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
software release
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
Programmer interface
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
S5-115U
S5-101U
S5-100U
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
byte 44 is valid
CPU identifier in
S5-90U/S5-95U/
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
of the PLC
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaa
PG 605U Manual
To display new PLCs in the SYSPAR display, a second CPU identifier must be defined. The
"Controller input buffer -1" information (bytes 39 and 40 from the SYSPAR) is not evaluated by
To execute the PLC START special function, the mode selector on the PLC must be set to RUN.
Select the PLC START function with the <SPECIAL> key ( Table 2-1.) and enter a <2>. Press the
<ENTER> key. The display prompts you to confirm that the PLC is to be started. Press the
<ENTER> key. If you want to return to the initial state, press the <BREAK> key.
Select the PLC STOP function with the <SPECIAL> key ( Table 2-1.) and enter a <1>. Press the
<ENTER> key. The display prompts you to confirm that the PLC is to be stopped. Press the
<ENTER> key. If you want to return to the initial state, press the <BREAK> key.
The COMPRESS PLC MEMORY function using the <SPECIAL> and <3> keys is used to remove
invalid blocks in the PLC (resulting from corrections and block deletions) and thus compress the
PLC memory.
Select the COMPRESS PLC MEMORY function with the <SPECIAL> and <3> keys. Press the
<ENTER> key to compress the PLC memory.
You can select the DISPLAY CHECK function with the <SPECIAL> and <4> keys. Press the
<ENTER> key. A test pattern appears in the display. You can check this display for errors.
You can invert the display with the <ARROW DOWN> key. Press the <ARROW DOWN> key
again to change the pattern back.
The display check is terminated approximately 6 s after pressing the <BREAK> key.
4.9.4
aaaaaaaa aaaaaaaa
Note:
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
PG 605U Manual
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
6.1
5.1
4.1
3.1
2.1
1.1
Key Check
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
6.2
5.2
4.2
3.2
2.2
1.2
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
6.3
5.3
4.3
3.3
2.3
1.3
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
6.4
5.4
4.4
3.4
2.4
1.4
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
6.5
5.5
4.5
3.5
2.5
1.5
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
6.6
5.6
4.6
3.6
2.6
1.6
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
Numbers are assigned to the individual keys. The display prompts you to press the relevant key.
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa
4-23
The key check is started by pressing the <SPECIAL> and <5> keys. Press the <ENTER> key to
aaaa aaaa
Programming and Operator-Process Communication PG 605U Manual
*KEY. CHCK*
KEY 1.1
1.1
•
•
•
*KEY. CHCK*
KEY 6.6
6.6
*KEY. CHCK*
XX ERRORS
After completion of the key check, press the <BREAK> key to return to the initial state.
4.10
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
Note:
Note:
4.10.2
4.10.1
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
PG 605U Manual
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
Deleting Blocks
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
Delete Functions
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
want to return to the initial state instead, press the <BREAK> key.
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
the block in question. If you want to return to the initial state instead, press the <BREAK> key.
The PLC must be stopped for the DELETE BLOCK function (not in the case of the S5-115U).
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
aaaaaaaa aaaaaaaa aaaaaaaa aaaaaaaa
4-25
Press the <SHIFT> key again and enter the block type (OB, PB, FB or "*" for DB) and the block
Select the Overall Reset function with the <SHIFT> and <INSERT> keys ( Table 2-1). After
Select the DELETE BLOCK function by pressing the <SHIFT> and <INSERT> keys ( Table 2-1).
number (0 to 255). If you press the <ENTER> key, the display prompts you to confirm that the
pressing the <ENTER> key, the display prompts you to confirm that Overall Reset of the PLC is to
block indicated is to be deleted. Press the <ENTER> key again to execute the command and erase
be executed. Press the <ENTER> key again to execute the command for Overall Reset. If you
aaaa aaaa aaaa aaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
4
3
2
1
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
Appendix
Appendix
Appendix
Appendix
aaaaaaaaaaaaaa
D
C
Appendices
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
System Overview
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
.....
.....
.....
.....
aaaaaaaaaaaaaa
Installation Guidelines
aaaaaaaaaaaaaa
Technical Specifications
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
Error Codes
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
Function Overview
aaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
aaaaaaaaaaaaaa
A STEP 5 Operations
*
A
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
A
A
A
A
A
A.1
O
O
O
O
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
AN
AN
AN
AN
AN
ON
ON
ON
ON
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
I
I
I
I
T
T
T
T
F
F
F
F
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
C
C
Q
Q
Q
Q
Operation
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
”Assign” key.
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
Logic Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
A
A
A
A
A
A
A
A
A
A
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
O. I
I
Keys
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
O. F
F
O. T
T
O. N
N
C
N
O. N
O. N
O. N
N
N
N
O. Q
Q
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
I
I
F
F
T
T
C
Q
Q
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
A-1
Appendix A contains an overview of the STEP 5 operation set. Each character in a STEP 5 operation
is entered by pressing the corresponding key ( Table 2-1). The ”=” character is used as the
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
)
A-2
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
O
O
A(
O(
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
ON
UW
OW
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
XOW
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
C
C
Operation
Operation
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
X
X
X
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
B
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
Function
X
X
X
E
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
O
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
A(
O(
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Keys
Keys
*
*
*
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
O. N
O. C
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
2
2
2
C
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
6
5
4
<Shift> key
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
*
!
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
=
=
=
S
S
S
R
R
R
A.3
A.2
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
<
>
<=
>=
><
=
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
I
I
I
F
F
F
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Q
Q
Q
Operation
Operation
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
F
F
F
F
F
F
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Set/reset operations
Compare operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
Parameter
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
0.0 to 255.7
0.0 to 127.7
0.0 to 127.7
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Compare Operations
Set/Reset Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
X
X
X
X
X
X
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
X
X
X
B
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
Function
E
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
<
<
>
>
>
=
=
=
=
S
S
S
R
R
R
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
I
I
I
Keys
Keys
<
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
=
=
F
F
F
F
F
F
Q
Q
Q
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
F
F
F
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
”
”
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
A-3
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
I
A-4
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
D
A.4
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
+F
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
- F
SLW
SRW
CFW
CSW
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Operation
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S = System operations
Arithmetic Operations
0 to 15
0 to 15
0 to 255
0 to 255
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
Arithmetic Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
X
X
X
X
X
X
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
*
*
*
Keys
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
R
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
L
2
2
3
3
F
F
W
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
3
2
0
1
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
<Shift> key
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
*
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
R
R
A.5
SI
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
SF
SS
SE
SD
CD
CU
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
T
T
T
T
T
T
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
C
C
C
C
Operation
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
0 to 127
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
X
X
X
X
X
X
X
X
X
X
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
Timer and Counter Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
R
R
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
*
*
Keys
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
C
C
SI
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
2
2
1
SD T
T
CD C
CU C
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
1
0
9
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
<Shift> key
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
”
”
”
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
A-5
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
A-6
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
A.6
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
LC
LC
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
T
T
IB
C
C
Operation
KF
IW
KT
DL
FY
PY
KC
DR
QB
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
FW
PW
DW
QW
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Load operations
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
0 to 999
0 to 127
0 to 127
0 to 254
0 to 255
0 to 127
0 to 127
0 to 255
0 to 255
0 to 255
0 to 254
0 to 255
0 to 126
0 to 127
0 to 126
0 to 127
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
0.0 to 999.3
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Load Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
- 32768 to+32767
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
*
*
*
*
Keys
L
L
L
L
L
L
L
L
L
L
L
L
L
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
I
I
0
0
0
0
0
T
F
F
P
P
C
Q
Q
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
4
3
2
1
0
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
K
K
K
Y
Y
B
B
W
W
W
W
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
<Shift> key
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
F
T
C
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
*
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
T
T
T
T
T
T
T
T
T
T
T
C
A.8
A.7
JC
JC
JU
JU
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
BEU
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
BEC
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
IB
Operation
Operation
Block calls
IW
FB
FB
DL
FY
PB
PB
PY
DB
DR
QB
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
FW
PW
DW
QW
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Transfer operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Block Calls
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
0 to 254
0 to 255
0 to 255
0 to 255
0 to 255
0 to 254
0 to 255
0 to 126
0 to 127
0 to 126
0 to 127
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
Parameter
Transfer Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
B
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
Function
E
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
*
*
*
*
*
Keys
Keys
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
T
T
T
T
T
T
T
T
JC
JU
JU
JC
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
I
I
1
1
1
0
0
0
F
F
P
P
Q
Q
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
2
1
3
7
6
5
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
B
Y
B
B
W
W
W
W
FB
FB
PB
PB
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
<Shift> key
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
A-7
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
A-8
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
A.9
JZ
JP
JN
JC
JU
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
JO
TB
JM
A.11
A.10
BLD
STP
TBN
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
NOP 0
=
=
=
=
=
=
=
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
D
D
Operation
Operation
Operation
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Jump operations
STEP 5 Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
S = System operations
B = Basic operation set
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
0 to 255
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Miscellaneous operations
Parameter
Parameter
Parameter
0.0 to 255.15
0.0 to 255.15
Jump Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Miscellaneous Operations
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
X
X
X
B
B
B
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
group *
group *
group *
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Function
Function
Function
E
X
X
X
X
X
X
X
E
X
X
E
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
S
S
S
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
*
*
*
*
*
*
*
*
*
*
Keys
Keys
Keys
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
JC
JU
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
=
=
0
1
0
1
1
1
1
1
2
2
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
8
0
9
8
7
6
5
4
8
7
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
<Shift> key
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
”
”
”
”
”
”
”
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
Parameter
Parameter
Parameter
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
B
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
Error Codes
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
B
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
*33
*32
*30
*29
*22
*20
*18
*15
*14
*12
*11
*08
*07
*06
*05
*04
*03
*02
*01
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
code
Error
aaaaaaaaaaaaaa
measures.
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
controller
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
DMA error
Line break
aaaaaaaaaaaaaa
Parity error
illegal block
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Wrong mode
USART error
Bad PG RAM
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Timer expired
aaaaaaaaaaaaaa
Buffer overflow
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Block in EPROM
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Error Codes
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
No ISTACK in cycle
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa
Guide)
aaaaaaaaaaaaaa
function
function
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
rename block
Retry function
Retry function
Retry function
Retry function
aaaaaaaaaaaaaa
Rename block
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Replace programmer
Replace programmer
Replace programmer
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa
Compress PC memory or
programmer, if necessary
programmer, if necessary
aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Corrective measure
aaaaaaaaaaaaaa
B-1
Appendix B presents a list of error codes, a description of each code, and suitable correction
Error Codes
aaaaaaaaaaaa aaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
B-2
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
*83
*82
*81
*79
*78
*77
*76
*75
*73
*71
*70
*59
*56
*51
*50
*49
*48
*47
*46
*45
*44
*42
*39
*35
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
code
Error
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Error Codes
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
No CPU
exceeded
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Wrong PC type
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Illegal multiplier
Illegal jump label
Address too long
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PC memory error
No such statement
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Unknown command
No RAM submodule
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
parameter
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Replace PC
Correct block
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Retry function
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Terminate block
Terminate block
aaaaaaaaaaaaaa aaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
PG 605U Manual
*97
*90
*88
*87
*86
*85
*84
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
code
Error
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
PG 605U Manual
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
position
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
No block in programmer
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Description
aaaaaaaaaaaaaaaaaa
Retry function
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
Corrective measures
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaa
B-3
Error Codes
aaaaaaaaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
C
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
Function Overview
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
C
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
Status
aaaaaaaaaaaa
AG-Stop
AG-Start
Suchlauf
Ausgabe
aaaaaaaaaaaa
Status Var
aaaaaaaaaaaa
Anzeigetest
Tastaturtest
Steuern Var
aaaaaaaaaaaa
Positionieren
AG urlöschen
aaaaaaaaaaaa
aaaaaaaaaaaa
Baustein löschen
PG 605U Handbuch
Systemparameter
aaaaaaaaaaaa
Funktion
aaaaaaaaaaaa
Eingabe (Datenbausteine
AG-Speicher komprimieren
Einfügen von Anweisungen
aaaaaaaaaaaa
aaaaaaaaaaaa
*
aaaaaaaaaaaa
Unterbrechungsstack (USTACK)
Überschreiben von Anweisungen
aaaaaaaaaaaa
aaaaaaaaaaaa
)
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
Function Overview
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
Suchbegriff
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
5
4
3
2
1
3
2
1
1
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
Neue Anweisung
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
Baustein
Operand
Operand
Baustein
Baustein
Baustein
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
The table below shows you the main functions of the PG 605U
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
Tasten
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
Baustein
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaa aaaaaa aaaaaa aaaaaa aaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaa
aaaaaaaaaaaa
4.6
4.5
4.3
4.2
aaaaaaaaaaaa
4.9.4
4.9.3
4.9.2
4.9.1
4.9.1
4.8.3
4.8.2
4.8.1
4.8.1
4.7.3
4.7.2
4.7.1
4.4.3
4.4.2
4.4.1
aaaaaaaaaaaa
4.10.2
4.10.1
aaaaaaaaaaaa
Kapitel
aaaaaaaaaaaa
Funktionsübersicht
aaaaaaaaaaaa
C-1
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
D
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
aaaaaaaaaaaa
Bolivia Guatemala
Sociedad Comercial e Siemens S.A.
Industrial Hansa Ltd. Ciudad de Guatemala
La Paz
Asia (continued)
Yemen (Arab Republic)
Tihama Tractors &
Engineering Co.o., Ltd.
Sanaa
or
Siemens Resident Engineer
Sanaa
Australasia
Australia
Siemens Ltd.
Melbourne
Brisbane
Perth
Sydney
New Zealand
Siemens Liaison Office
Auckland
P
Power
- supply 2-1
Program block 2-1
Program-dependent
signal state display 4-10
Programming 4-1
- data blocks 4-5
S
Search function 4-8, 4-9
- address 4-9
- label 4-9
- operand 4-9
- statement 4-9
Search item 4-9
Set/reset operations A-3
Shift key 2-2
Signal state 4-10
Signal state display
- direct 4-11
- program-dependent 4-10
Special function 4-21
Starting 4-21
Statement
- deletion 4-8
- entry 4-2
- insertion 4-8
- overwriting 4-8
STATUS 4-10
STATUS VAR 4-11
STEP 5 operations A-1
Stopping 4-21
System overview 1-1
System parameters 4-19, 4-20
- display 4-19
T
Technical specifications 2-1
Test function 4-10
Test pattern 4-22
Timer operations A-5
Transfer operations A-7
W
Weight 2-1