BS 1125 - 1987
BS 1125 - 1987
@ British Standards Institution.No patt of this publication may be photocopied or otherwise reproduced without the prior permission in writing of BSI
Foreword
Contents
Page
Foreword Inside front cover
Committees responsible Back cover
Specification
Section one. General
1 Scope 2
2 Definitions 2
3 Marking 2
Appendices
A Distortion and dead load tests 9
B Front thrust t e s t 9
C Impacttest 9
D Volume of discharge test 9
E Rate of discharge test for full flush 10
F Options: Information to be supplied by the
purchaser 11
Figures
1 Flush pipes 6
2 Front thrust t e s t apparatus 9
3 Test flush pipe for low level cistern 10
'
BS 1125 : 1987
Specification. Section one
*Marking BS 1125 on or in relation to a product i s a claim by the manufacturer that the product has been manufactured t o the requirements
of the standard. The accuracy of such a claim is therefore solely the manufacturer's responsibility. Enquiries as to the availabilitypf third
\ ---
party certification should be addressed to the appropriate certification body.
4 General requirements 5.2.7 Front thrust test for cisterns for use at low levels
(including close coupled). The complete cistern, when
Cistern shells, siphons and associated components shall be installed and filled as described in appendix A and tested
made from materials which under the conditions of use are by the method described in appendix B, shall not distort
one of the following: to such an extent that any part becomes detached or
(a) non-corroding e.g. plastics; inoperable.
(b) protected against the types of corrosion caused by 5.2.8 Impact test. The complete cistern, when installed and
the action on them of the water with which the cistern filled as described in appendix A and tested as described in
i s to be used; appendix C, shall show no defect after one impact, and after
(c) highly resistant to corrosion by the action of the being emptied shall show no defect after one more impact.
water with which the cistern i s to be used, ¡.e. they
corrode only a t a rate which is insufficient to affect
adversely the durability or efficiency of the cistern. 6 Softsolder
Before dissimilar metals are used in the construction of a
Any soft solder used in the construction of cistern shells,
cistern, the manufacturer shall ensure avoidance of the
siphons or associated components shall comply with the
possibility of electrolytic action.
requirements of BS 219, and shall be of type F or type J as
given in table 1 of BS 219 : 1977,
BS 1125 : 1987
Section two
shall discharge 9";':: L. Dual flush type cisterns shall 13.3 Bottom connection warning pipes
BS 1125 : 1987
Section three
Dimensions to
back o f pipe
i525
or
675
///4 5 5 t 10
65 mm min.
overlap
Telescopic
joints (optional) 1
Back wall
BS 1-125: 1987
Section three
19.2 Bottom connection inlet pipe assemblies NOTE. To facilitate the fitting of a BS 1212 float operated valve in
the bottom connection cistern, the purchaser may order the inlet
19.2.1 General. Bottom connection inlet pipes shall be of shank of the float operated valve to be only 12:; m m in length.
such a height that the position of the float operated valve
complies with clause 14. Any joint in the bottom connection inlet pipe assembly
The bottom connection inlet pipe assembly shall terminate which is inside the cistern, shall be sealed in a manner
a t the bottom end below the cistern with an externally which complies with 19.3.
screwed shank. The external shank shall have a G % B All bottom connection inlet pipe assemblies shall be
thread as specified in BS 2779. The length of effective provided with a stay a t the upper end to prevent distortion.
thread available, after the assembly has been fixed to the
19.2.2 Metal bottom connection inlet pipe assemblies.
cistern shell, shall be not less than 12 mm.
Metal bottom connection inlet pipes shall be of copper tube
The shank dimensions for the inlet connection relating to complying with table X of BS 2871 : Part 1 : 1971, or be
the counterbore and thickness shall comply with BS 1212 : of copper alloy tube not less than 1 mm thick. Backnuts for
Part 1, Part 2 or Part 3. metal bottom connection inlet pipes shall be of metal in
The connection of the inlet pipe assembly to the cistern accordance with table 1 of BS 1212 : Part 1 : 1953.
shell shall be by means of a flange of not less that 36 mm
19.2.3 Plastics bottom connection inlet pipe assemblies.
diameter inside the cistern, integral with or jointed to the
Plastics bottom connection inlet pipes and backnuts shall
shank or to the inlet pipe, and a washer. If the inlet hole i s
be moulded from acetal resin or a rigid plastics material
made to suit a 19 mm connection, then provision shall be
having equivalent physical properties. Backnuts of plastics
made for locating the inlet pipe centrally in the inlet hole.
materials shall be such that, when a torque of 15 Nam is
Below the cistern, a backnut and washer, or other suitable
means, t o ensure and maintain a watertight joint shall be applied in tightening the backnut of the inlet, there shall be
provided. no sign of distortion of the threads of the backnut.
The bottom connection inlet pipe assembly shall either: 19.3 Hydraulic test
(a) terminate a t the top end with a horizontal outlet All bottom connection inlet pipe assemblies with float
designed to accommodate a nominal size % float operated valves connected thereto shall be capable of
operated valve with an inlet shank complying with withstanding a pressure of 20 bar without leaking or
BS 1212; or sweating while held in the closed position.
(b) be supplied with a float operated valve integral with
or jointed to the inlet pipe.
20 General requirements flushing cistern and the flush pipes shall be detachable
from the flushing cistern. The lower end of the flush pipes
20.1 Flush pipes shall be constructed in accordance shall be finished with a plain end.
with 20.2,20.3 and 20.4 and also with either clause 21
or 22.
21 Special requirements for flush pipes for
20.2 Materiais
use with cisterns at high level
Flush pipes shall be made of one of the following materials:
(a) steel; Flush pipes for use with cisterns a t high level shall have an
internal diameter, before forming and the application of
(b) unplasticized PVC or a suitable copolymer.
any finish, of not less than 32 mm. Their other dimensions
shall be as shown in figure 1. They shall be either of one-
20.3 Construction
piece construction or made of sections, and shall be
20.3.1 Steel flush pipes. Steel flush pipes shall be manufac- watertight throughout their length. Where the upper end
tured from seamless or welded tube of a minimum thickness of the flush pipe has a flange, it shall be integral to assist in
of 1 mm and shall be completely protected inside and making it a watertight and airtight joint.
outside by either vitreous enamelling or hot dip galvanizing.
If vitreous enamelled, flush pipes shall comply with ES 3830.
If hot dip galvanized, they shall comply with BS 729. 22 Special requirements for flush pipes for
20.3.2 PVC flush pipes. PVC flush pipes shall be use with cisterns at low level
unplasticized and the wall thickness before forming shall
be not less than 1.5 mm. Flush pipes for use with cisterns a t low level shall have an
internal diameter, before forming and the application of
20.4 Ends any finish, of not less than 35 mm.
The upper end of the flush pipes shall be provided with
means of making a watertight and airtight joint to the
Appendices
Appendix A. Distortionand dead load tesils the bottom and on the centre line of the cistern. Carry out
the test a t ambient temperature or, in case of dispute,
Fasten the cistern, complete with i t s fitments and cover, a t 20 f 2 OC, Ensure that the cistern cover is in position
by i t s normal fixing devices to a solid background. Fill the during the test.
cistern with water to the marked water line. Apply the
dead load 6 mm from the end of the operating lever arm
for 30 s. Appendix D. Volume of dischargetest
D.l Preparation
Appendix B. Front thrust test
Fasten the cistern, complete with i t s fitments, float operated
Apply horizontally a front thrust of 110 N through a valve as specified in BS 1212 and type 127 float complying
150 mm diameter disk as high up as possible to the front with BS 2456, or Water Authority approved float operated
of the cistern on i t s centre line. Face the disk with a soft valve, by i t s normal fixing devices to a solid background.
material such that the face will conform to the contour of For high level cisterns, connect a back wall flush pipe of
the cistern shell. Ensure that the cistern cover is in position diameter 32 mm and overall length as shown in figure 1.
during the test.
For low level cisterns connect a flush pipe diameter 35 mm
A convenient method of applying this thrust is shown in with other dimensions as shown in figure 3.
figure 2.
Connect a water supply that i s controlled by a stop valve
and i s fitted, if necessary, with a pressure regulating valve
t o give a static pressure of 3 f 0.5 bar a t the inlet to the
Appendix C. Impact test cistern float operated valve, Adjust the float operated valve
so that the valve closes when the water level reaches the
Suspend a 1 kg steel ball by a fine wire 2.5 m long, the point
marked water line of the cistern. Fit the cistern cover with
of suspension being located vertically over the point of
i t s fastening screws, if provided.
impact. Release the ball from a point directly in front o f
the cistern a t a horizontal distance of 1 m away from the Place a vessel under the open end of the flush pipe.
point of impact, the point of impact being 75 mm from
I r - - - - - - -
COPYRIGHT British Standards Institution on ERC Specs and Standards
Licensed by Information Handling Services 9 i.
t
!
BSI BSxLL25 87 1h24hhï 0002b04 O m
BS 1125 : 1987
Appendices D to E
Siphon inver
i 1
J
i40 rnax.
For test purposes, length i20 min.
o f engagement of flush
pipe in siphon t o be
50 mrn max.